Hawk ORCA User manual

ORCA
Sonar System
Sludge and Settling Level Interface Monitoring
User Manual
Sultan Sonar Manual Rev 1.0
A Higher Level of Performance
www.hawkmeasure.com
For more information, please visit >

Table of Contents
ORCA Sonar System
2
Contents
Overview 3
Principle of Operation 3
Function 3
Benefits 3
Features 3
System Components 4
Auto Scum Cleaner 4
OSIRT Transducer 4
OSIR Amplifier 4
Dimensions 5
OSIR Remote Amplifier 5
OSIRMELx* - Mounting Pole 5
OSIRSCE - Impact Plate 5
OSIRSCE Impact Plate 6
OSIRT302S4 Transducer 6
OSIRSCA Actuator 6
OSIRT302SH Transducer 6
OSIRSCD Floating Sonar 6
Mounting Bracket 7
Assembly 8
Mounting Bracket / Pole assembly 8
Mounting Bracket / Pole assembly 9
Dimensions & Mounting Connection 10
Impact Plate Mounting Connection 10
Mounting & Hardware Assembly 11
Impact Plate Assembly 11
*A: Important Cabling Steps to Follow 11
Installation Guide 12
Installation Guide 12
Round Tanks – Centre Feedwell 12
Rectangular Tanks – End Feed 12
Ball float 12
Impact Plates 12
Wiring 13
Wiring - Remote Transmitter 13
Wiring Extension 13
Actuator Cable Specication 14
Probus PA - Foundation Fieldbus (PA/FF) 15
DeviceNet 16
Probus DP 17
Setup Procedure 18
Powering The Unit 18
Quickset 19
Typical High & Low Level 19
App Type 20
Interface Table 20
Bed Depth 20
App Type2 21
Interface Table 21
Clarity 21
Output Adjustment 22
Comms Type 23
Comms Type (Menu) 23
Modbus 23
HART 23
Cleaning Menu 24
Cleaning 24
Actuator 24
Setup Procedure 25
Advanced 25
(1) Gain4 default settings 25
(2) Gain-Over-Distance bias 25
Relay Actions 26
Operating Diagnostics 27
Operating State 27
Application Calibration 28
How to set up the unit -
Bed Level + Hindered / settling layer measurement 28
Bed Depth 28
How to set up the unit - Bed Level + Clarity 29
Bed Depth 29
How to set up the unit - Hindered Layer + Clarity 30
Troubleshooting 31
Unit is measuring incorrect Bed or Space 31
PLC indication does not match measurement 31
Some menu options are missing 31
Error Codes 32
Unit Specs & Health Checks 33
ORCA Electric Actuator Troubleshooting 34
Part Numbering 35
Remote Electronics 35
Remote Sonar Transducer 36
Automatic Scum Cleaner 37
Accessories 37
Specications 38
Warranty and Liability 39

ORCA Sonar System
Overview
3
Benets
• Improved efficiency and control of the thickener process
• Fully automated plant systems with reliable interface level monitoring
• Advanced warning of process upset or hydraulic in-balance
• Reduced maintenance with automatic cleaning mechanism warranty (no blades to replace)
• Reduced site operational costs significantly with improved process & extraction control
• Improved health and safety on site (no manual dips required).
Principle of Operation
The ORCA Sonar Series transducer emits a high powered low frequency sonar pulse, which is reflected
from the interface density selected. The reflected signal is processed using specially developed software
algorithms that eliminate unwanted densities and stratified layers, allowing measurement of Bed or RAS
levels. It can be calibrated to measure lighter densities such as the hindered / free settling layer & floc or one
of the outputs could be used for a “Clarity” output, similar to a basic turbidity transmitter measuring solids in
suspension. The unit can include two outputs to measure two different interfaces simultaneously.
Function
The ORCA Series Sonar, sludge blanket and interface controller, consists of a microprocessor based
transmitter, with easy menu driven programming via keypad, PC or 3G modem. The ORCA controller works
together with appropriate sonar transducer and transducer cleaning mechanism.
Features
• Dual independent analogue outputs to track two
different interfaces, or clarity simultaneously, with
the one sonar sensor
• Easy to use pre-set calibrations to track specic
density interfaces, eg: oc / uff layer, Bed
• Industrial scum cleaning mechanisms that do not
require maintenance
• Control room graphics of tanks and interfaces via
GosHawk II
• Wide range of communications: Modbus, HART,
Foundation Fieldbus, DeviceNet, Probus DP and
Probus PA
• 3G remote support capability for calibration,
commissioning or technical back-up
• 3 programmable relays.

System Components
ORCA Sonar System
4
Auto Scum Cleaner
OSIRSCA Pictured with Mounting Pole
OSIR Amplier
OSIRT Transducer

Dimensions
ORCA Sonar System
5
14 mm (0.6”)
74 mm (2.9”)
78 mm (3.1”)
107 mm (4.2”)
111.5 mm (4.4”)
4 mm (0.2”)
50 mm (2”)
131.5 mm (5.2”)
7.5 mm (0.3”)
192.5 mm (7.6”)
141.5 mm (5.6”)
190 mm (7.5”)
182.5 mm (7.2”)
147 mm (5.8”)
167.5 mm (6.6”)
147 mm (5.8”)
30.7 mm (1.2”)
158 mm (6.2”)
108 mm (4.3”)
190 mm (7.5”)
174 mm (6.9”)
192.5 mm (7.6”)
182.5 mm (7.2”)
30.0
20
.
2
33.029.029.033.0
1
6
.
2
OSIR Remote Amplier
OSIRSCE - Impact PlateOSIRMELx* - Mounting Pole
22.0
M25 x 1.5 Ext Thd
mates with Pole Adaptor
HAW_P_ST-SS-TC
27.0
M25 x 1.5 Ext Thd
mates with Cable
Gland Adaptor
HAW_P_ST-SS-EPEC
26.5
*X mm
588mm
605mm
300mm
588mm
605mm
300mm

Dimensions
ORCA Sonar System
6
α°
500mm (19.6”)
252mm (9.9”)
650mm (25.6”)
500mm (19.6”)
252mm (9.9”)
650mm (25.6”)
X
X
605mm (23.8”)
252mm (9.9”)
650mm (25.6”)
42.5
o
42.5
o
X
X = Decent Range
Distance from safety
rail or Bridge may vary
X
130mm (5.1”)
200mm (7.9”)
1" BSP Nipple
130mm (5.1”)
230mm (9.0”)
1" BSP Nipple
OSIRSCE Impact Plate OSIRSCA Actuator OSIRSCD Floating Sonar
OSIRT302S4 Transducer OSIRT302SH Transducer

Dimensions
ORCA Sonar System
7
252.0
5.0
240.0
Rail / Bridge
Mounting U bolts
440.0
330.0
111.5
20.0
25.0
79.5
365.8139.5
650.0
150.0
(A) Base Plate
(A) Base Plate
Mounting Bracket

Assembly
ORCA Sonar System
8
Mounting Bracket / Pole assembly
11
4
12
10
9
8
3
6
13
7
14
15
18
19
20
1
13
2
5
16
17
11
4
12
10
9
8
3
6
13
7
14
15
18
19
20
1
13
2
5
16
17
OSIRSCA pictured

Assembly
ORCA Sonar System
9
Item
No.
Part Number Description Qty
1OSIRxxx ORCA Transmitter 1
2SUNHOOD Stainless Steel Sunhood 1
3SA-SS-AAFB Stainless Steel Front Bracket 1
4SA-SS-AARB Stainless Steel Rear Bracket 1
5LAUS061196E Actuator Actuator (only with OSIRSCA/OSIRSCD) 1
6ST-SS-EPEC Pole to Cable Gland Adaptor with M16 cable gland 1
7ST-APC-26.8-INT SS Internal Pipe Clamp 1
8ST-APC-26.8-EXT SS External Pipe Clamp 1
9ST-SS-EP Mounting Pole 1
10 OSIRTxxxxxxxx Sonar Transducer 1
11 ZPP-M5X20MM M5x20 Phillips Pan Head 8
12 U-BOLT 50mm x 8DIA U-Bolt with nuts and washers 4
13 BOL-M10x15SS M10 x 15mm SS Bolt 4
14 BOL-M10x50SS M10 x 50mm SS Bolt with washer & nyloc nut 1
15 BOL-M10x40SS M10 x 40mm SS Bolt with washer & nyloc nut 2
16 ST-SS-TC Sonar Pole Adaptor 1
17 GLA-M16 M16 Cable gland IP68 with washer 1
18 Washer-M10 M10 washer for M10x40mm & M10x50mm SS Bolt 6
19 Nut-M10 M10 nut for M10x40mm & M10x50mm SS Bolt 5
20 Nut-M8 M8 nyloc nut for 50mm U-bolt 8
Mounting Bracket / Pole assembly
11
4
12
10
9
8
3
6
13
7
14
15
18
19
20
1
13
2
5
16
17

Dimensions & Mounting Connection
ORCA Sonar System
10
Impact Plate Mounting Connection
The top of the Impact Plate has 3 x 7mm bolt holes
which can be secured to an angle iron or equivalent
bracket. There is also a M25 (1.5”) threaded
connection for a mounting pole connection. The
Impact Plate is designed to swing parallel with the
counter weights. The surface sweeper must come
in contact with the legs of the Impact Plate which
swings the bracket lifting the transducer out of the
liquid. When the sweeper has cleared, it will drop
back in and use the counter weights to re-center. The
force of the movement will clear the sensor face of
any build up
Impact Plate Connection Point
Angle iron or equivalent
Swing
Bolt
90mm (3.54”)
50mm (1.97”)
7.00
(0.79”)
×3
M25 x 1.5 INT
THD THRU
ISOVIEW FOR
REFERENCE ONLY

Mounting & Hardware Assembly
ORCA Sonar System
11
Impact Plate Assembly
1
2
3
4
5
6
7
8
9
10
11
12
No. Description
QTY.
1
Impact Plate Dual Direction
1
2
Sonar Pole Adaptor
1
3
Impact Plate Counter Balance
1
4
Sonar Male Clevis Assembly
1
5
Sonar Female Clevis Assembly
1
6
M6×45 Stainless Steel Bolt
3
7
M10×40 Stainless Steel Bolt
1
8
M10×12 Stainless Steel Set Screw
4
9
M10×20 Stainless Steel Set Screw
2
10
M6 Stainless Steel Nut
3
11
M10 Stainless Steel Nyloc Nut
1
12
M10 Stainless Steel Washer
1
170mm
Right
30mm
Front
60mm
mm03
Back
160mm
550mm
Allow 550mm loose
cable
to perform the
looping of the cable
Use electrical tape to
hold cable in place
*A: Important Cabling Steps to Follow
*A

Installation Guide
ORCA Sonar System
12
ORCA Transmitter – Mounting Requirements
Select a suitable mounting position, preferably not in
direct sunlight. If necessary utilize a sunshade.
Observe the maximum and minimum temperature
specification.
Do not mount the sonar transmitter near high sources
of EMF, such as motor starters, variable speed drives
or 3 phase cables. Avoid mounting in high vibration
areas, or use rubber absorption mounts.
Be careful when removing the cable and compression
glands.
Installation Guide
Sonar Transducer – Mounting Requirements
The transducer should be half submerged in the liquid
and the transducer face must always be submerged.
Wrap cable entry and lower connection cable with
Teflon tape
Round Tanks – Centre Feedwell
Mount the sonar transducer and cleaning mechanism,
approximately one third radius between the outside
tank wall and the feedwell. This is the same whether it
is a moving or fixed bridge installation.
Do not mount near high infeed turbulence.
Choose a site installation where the infeed is least
disturbed.
High Level
20mA
0.500m
Low Level
4mA
X.xxm
Blanking /
non-measured
zone
1/2 Submerged
1/3 Radius
Rectangular Tanks – End Feed
Mount the sonar transducer and cleaning mechanism
away from high infeed turbulence. A clearance of
700mm from the side wall.
Do not mount directly over scraper, chain
mechanisms. Choose a site installation where the
infeed is least disturbed.
Ball oat
Mount the floating sonar transducer and cleaning
mechanism as close as practicable to the launders.
Mount at least 1.00 metres from side walls. Ensure
alignment guides are installed on the mounting
bracket for decanter ranges above 500mm.
Impact Plates
Leave an extra 2 turns of cable where the transducer
connects to the actuator to minimise stress and wear
on the cable (see Impact Plate Assembly).

Wiring
ORCA Sonar System
13
Driving 4-20mA from ORCA to user PLC
Modulating 4-20mA from PLC input
1
2
1
2
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
ANALOG1 TRANSDUCER
COMMS
DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
4-20mA
DC IN
AC IN
Is
+
-
4-20mA
BOTTOM TOP
ANALOG2
SONAR 234 REMOTE TRANSMITTER
1
Output 1Output 2
RED
BLK
BLU
WHT
BLK
BLU
BRN
GRN
YEL
SHLD
TRANSDUCER ACTUATOR
Junction Box for
wiring extension
RED
BLK
BLU
WHT
Shield
Separate
cable
shielding
Separate
potentiomer
wires from
power wires
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
FIELDBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
FIELDBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
PROFIBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
PROFIBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
V+
CAN_H
SHEILD
CAN_L
V-
Top
B (in)
A (in)
SHEILD
B (out)
A (out)
Top
Driving 4-20mA from ORCA to user PLC
Modulating 4-20mA from PLC input
1
2
1
2
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
ANALOG1 TRANSDUCER
COMMS
DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
4-20mA
DC IN
AC IN
Is
+
-
4-20mA
BOTTOM TOP
ANALOG2
SONAR 234 REMOTE TRANSMITTER
1
Output 1Output 2
RED
BLK
BLU
WHT
BLK
BLU
BRN
GRN
YEL
SHLD
TRANSDUCER ACTUATOR
Junction Box for
wiring extension
RED
BLK
BLU
WHT
Shield
Separate
cable
shielding
Separate
potentiomer
wires from
power wires
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
FIELDBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
FIELDBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
PROFIBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
PROFIBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
V+
CAN_H
SHEILD
CAN_L
V-
Top
B (in)
A (in)
SHEILD
B (out)
A (out)
Top
Wiring - Remote Transmitter Wiring Extension
Driving 4-20mA from ORCA to user PLC
Modulating 4-20mA from PLC input
1
2
1
2
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
ANALOG1 TRANSDUCER
COMMS
DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
4-20mA
DC IN
AC IN
Is
+
-
4-20mA
BOTTOM TOP
ANALOG2
SONAR 234 REMOTE TRANSMITTER
1
Output 1Output 2
RED
BLK
BLU
WHT
BLK
BLU
BRN
GRN
YEL
SHLD
TRANSDUCER ACTUATOR
Junction Box for
wiring extension
RED
BLK
BLU
WHT
Shield
Separate
cable
shielding
Separate
potentiomer
wires from
power wires
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
FIELDBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
FIELDBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
PROFIBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
PROFIBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
V+
CAN_H
SHEILD
CAN_L
V-
Top
B (in)
A (in)
SHEILD
B (out)
A (out)
Top
Foundation Fieldbus
Profibus PA
Driving 4-20mA from ORCA to user PLC
Modulating 4-20mA from PLC input
1
2
1
2
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
ANALOG1 TRANSDUCER
COMMS
DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
4-20mA
DC IN
AC IN
Is
+
-
4-20mA
BOTTOM TOP
ANALOG2
SONAR 234 REMOTE TRANSMITTER
1
Output 1Output 2
RED
BLK
BLU
WHT
BLK
BLU
BRN
GRN
YEL
SHLD
TRANSDUCER ACTUATOR
Junction Box for
wiring extension
RED
BLK
BLU
WHT
Shield
Separate
cable
shielding
Separate
potentiomer
wires from
power wires
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
FIELDBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
FIELDBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
SONAR 234 REMOTE TRANSMITTER
-
-
+
+
RELAY 1 RELAY 2 RELAY 3 ACTUATOR
NC
COM
NO
NC
COM
NO
NC
COM
NO
BLK
BLU
BRN
GRN
YEL
SHLD
PROFIBUS TRANSDUCER COMMS DC-IN AC-IN
RED
BLK
BLU
WHT
Test
B
A
N
L1
PROFIBUS
ENC
GND
BOTTOM TOP
DC IN
AC IN
V+
CAN_H
SHEILD
CAN_L
V-
Top
B (in)
A (in)
SHEILD
B (out)
A (out)
Top
DeviceNet / Profibus DP
Terminal plug located right hand side of main terminal
board.
DeviceNet Profibus DP

Actuator Cable Specication
ORCA Sonar System
14
Actuator Cable Specication
Note 1: Calculations based on:
4.0 Amps max actuator current and;
4.0 Volts drop across max cable length ( 2 wires)
Note 1: Note 2: Maximum terminal capacity is 1.5mm, which limits 16AWG cable to35m.
Note 3: For long cable runs, use 16 AWG to local junction box, then extend using 10-14 AWG.
Note 4: Also required: 3-wire cable for feedback potentiometer, 0.5mm - 1.0mm.
Gauge
AWG
Nom OD
mm
Resist
Ohm/1000ft
Resist
Ohm/m
Loss
V/m
Max Res
Ohm
Max Dist
m
10 2.9201 0.80 0.0035 0.028 1.00 141.1
12 2.4401 0.71 0.0056 0.045 1.00 89.1
14 1.9302 0.73 0.0090 0.072 1.00 55.8
16 1.5204 0.35 0.0143 0.114 1.00 35.0
18 1.2206 0.92 0.0227 0.182 1.00 22.0
20 0.965 0.90 0.0358 0.286 1.00 14.0
Actuator Motor Cable Guide
0.0
20.0
40.0
60.0
80.0
100.0
120.0
140.0
160.0
10 12 14 16 18 20
Wire Gauge (AWG)
Max Distance (m)

Probus PA - Foundation Fieldbus (PA/FF)
ORCA Sonar System
15
Probus PA - Foundation Fieldbus (PA/FF)
See dedicated manual for Profibus PA and FF available from http://www.hawkmeausure.com

DeviceNet
ORCA Sonar System
16
Set the BaudRate and the DeviceNet Address in
Sultan
Factory defaults of baudrate and FBusAdds are
125kbps and 63 in a Sultan unit with DeviceNet
CommType. To modify these values follow the
instructions below.
1. Go to the Output Adjustment menu
2. Use the Up and Down push buttons to reach the
CommType parameter
3. Make sure that the CommType is set to DeviceNet
4. Press the CAL button twice. If you see DeviceID do
not modify this parameter.
5. Use the Down push button to reach the BaudRate
parameter
6. The default value for the BaudRate is 125kpbs.
Press CAL button and use the Up and Down push
buttons to modify this value
7. Press CAL button when finished
8. Use the Down push button to reach the FBusAdds.
The default value of the Fieldbus Address is 63.
Press CAL button and use the Up and Down push
buttons to modify this value
9. Press CAL button again when finished
Output Data
Profibus DP and DeviceNet now transmit 18 bytes/9
words, description of the words is as follows (For
firmware version 5.54 and above)
1. Displayed Distance
(Space Distance is the Primary Variable)
2. Percentage (Percent of Range)
3. Hi Level (Upper Range)
Failed ~~~~~~ Search 0Echo Cfm : 1 =
True, 0 = False
Echo R : 1 =
True, 0 = False
DeviceNet
4. Low Level (Lower Range)
5. Status Flags
6. Displayed Distance2 (Second Variable)
7. Percentage2 (Second Percent of Range)
8. Displayed Distance3 (Third Variable)+
9. Percentage3 (Third Percent of Range)+
Bit F Bit E Bit 3 Bit 1 Bit 0
Bit0 = Echo was received inside the span.
Bit1 = Echo is Confirmed.
Bit3 = Searching is searching for an Echo.
BitF = Unit has Failed to detect an Echo.
+Only used for ORCA Sonar Clarity output.

Probus DP
ORCA Sonar System
17
Probus DP
Set the Profibus Address in Sultan
Factory defaults of FBusAdds is 126 in a Sultan unit
with Profibus CommType. To modify this value follow
the instruction below:
1. Go to the Output Adj menu
2. Use the Up and Down push buttons to reach the
CommType parameter
3. Make sure that the CommType is set to
Profibus DP
Failed ~~~~~~ Search 0 Echo Cfm : 1 =
True, 0 = False
Echo R : 1 =
True, 0 = False
4. Press the CAL button twice - If you see DeviceID
do not modify this parameter
6. Use the Down push button to reach the BaudRate
parameter. Note this cannot be modified
8. Use the Down push button to reach the FBusAdds.
The default value of the Fieldbus Address is 126.
Press CAL button and use the Up and Down push
buttons to modify this value
9. Press CAL button again when finish.
Output Data
Profibus/DeviceNet now transmit 18 bytes/9 words, description of the words is as follows (For firmware
version 5.54 and above).
1. Displayed Distance
(Space Distance is the Primary Variable)
2. Percentage (Percent of Range)
3. Hi Level (Upper Range)
4. Low Level (Lower Range)
5. Status Flags
6. Displayed Distance2 (Second Variable)
7. Percentage2 (Second Percent of Range)
8. Displayed Distance3 (Third Variable)+
9. Percentage3 (Third Percent of Range)+
Bit F Bit E Bit 3 Bit 1 Bit 0
Bit0 = Echo was received inside the span.
Bit1 = Echo is Confirmed.
Bit3 = Searching is searching for an Echo.
BitF = Unit has Failed to detect an Echo.
+Only used for ORCA Sonar Clarity output.

Setup Procedure
ORCA Sonar System
18
CAL
Bed
CAL
Unlock 0
Quickset
CAL
App Type
CAL
App Type
*Edit*
Density
Switch
Blocked Chute
Boom Protect
Alignment
Output Adj Advanced*
Advanced
(Tx Setup)
*Also Tx Setup
Operating Diagnostic Display
Unlock Code (default 0)
Main Menus
Amplifier /
Application
settings
Comms / Output
Settings
Transducer
settings.
Powering The Unit
When power is applied the unit will start up automatically. It will scroll through its boot diagnostics and display
the serial numbers, software version and model types for the amplifier and transducer
The unit will display its default operating screen depending on the App Type selected (default: Bed) on the
top line and a distance or % on the bottom line. The distance will be the programmed display mode (Default:
Level).
The unit will re-scan for the measurement whenever it is powered up.
The sensor face must be submerged in liquid in order to operate correctly.
CAL
RUN
CAL for select / proceed / edit
Arrows to scroll / adjust
RUN to re-active unit
*Do not adjust Advanced settings without expert knowledge

Setup Procedure
ORCA Sonar System
19
1/3 Radius
1/2 Submerged
High Level
20mA
0.600m
Low Level
4mA
X.xxm
Blanking /
non-measured
zone
Bed Depth
(Max Bed + 1m (3ft)
Max Bed
1m
Typical installation - Set ‘Low Level’ (4mA) to be the distance from the transducer face to the bottom of the
tank. High Level should be 0.600m for most accurate and reliable measurement.
Parameter Description Options
Unit Adjust displayed measurement unit Inches Feet Meters Centimeters
App Typ e Select Application Parameters for Output 1 See Unit Setup: 'App Type'
App Typ e2 Select Application Parameters for Output 2 See Unit Setup: 'App Type2'
Failsafe Set failsafe output & timer 20mA 4mA LastKnown 3.80mA 3.50mA
20.20mA
DispMode Set LCD measurement display mode Level Level% Space
Offset Add offset distance to output Adjustable
Amp Reset Restore Amplifier settings to factory default Yes / No
Quickset
The Quickset menu contains the basic parameters required to get the unit up and running.
It is one of the three main menu options in the internal software.
Typical High & Low Level

Setup Procedure
ORCA Sonar System
20
App Type
App Type is the first output and should be considered the primary measurement. If monitoring Bed level this
should be selected here. App Type has three pre-set application types.
• Bed (dense/heavy blanket layer).
• RAS (return activated sludge)
• Floc (Flocculent/hindered settling layer).
Parameter Description Options
App Typ e Set display readout Bed RAS Floc
Density Select interface to be measured See Interface Table below
Calibrat
• Manually fine tune sensor sensitivity
• Press CAL to fire a test pulse which will
return the depth measurement.
Higher value for lighter densities, lower
value for heavier densities.
Lo Level Set Lo Level measurement point (4mA) Adjustable
Hi Level Set Lo Level measurement point (20mA) Adjustable
Bed Depth(1) Set maximum expected Bed Depth - see Bed Depth(1)
for further information
Adjustable in depth (measured from
Sensor face down)
Fill Rate* Set potential filling rate for primary measurement Adjustable (units per hour)
Empty Rate* Set potential emptying rate for primary measurement Adjustable (units per hour)
*For most applications the unit is pre-calibrated with appropriate tracking speeds.
You will not need to adjust these settings.
Density
Selected (g/l) Typical Applications
0.1 - 0.6 Lighter layers
0.6 - 1.2 Hindered Layer Settling Layer
1.2 - 3.0 RAS
3.0 - 6.0 RAS Bed
6.0 -1 0.0 Bed
10+ Bed / Heavy Sludge
Inter face Table
1/3 Radius
1/2 Submerged
High Level
20mA
0.600m
Low Level
4mA
X.xxm
Blanking /
non-measured
zone
Bed Depth
(Max Bed + 1m (3ft)
Max Bed
1m
Bed Depth(1)
Bed Depth should be programmed to 1m (3ft) higher
than the application expected maximum depth
Table of contents
Other Hawk Sonar manuals