Split-Core Low Current 4-20mA & 0-5VDC
DC Current Transducer
quick install
Installer's Specifications
)";"3%0'&-&$53*$4)0$,&91-04*0/03"3$'-"4)
t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT
4FF/'1"&JOUIF64"PSBQQMJDBCMFMPDBMDPEFT
t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBEVOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
%0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST
'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ
%"/(&3
Wiring ExamplE
H970HCA H970HCA
DimEnsions
/05*$&
t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT
t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF
Technology Open loop Hall effect
Amperage Range 0 to 50/100/200 ADC (slide switch selectable)
Sensor Supply Voltage 12 to 30VAC/DC
Supply Current 35mA max.
Isolation 600VAC rms
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Output 4-20mA and/or 0-5VDC
Accuracy ±3% F.S. combined linearity, hysteresis, and repeatability
The product design provides for basic insulation only.
Disconnect and lock out power to the conductor to be monitored.1.
Choose a location for the sensor. The monitored conductor must pass through the2.
iris, and the sensor must be at least ½" from any uninsulated conductors.
Install the adjustable mounting bracket to the back of the enclosure using the3.
included screws.
Connect 12-30VAC/DC to the terminals marked Power (+) and Gnd (-).4.
Wire the output (mA or VDC) connections between the sensor and the controller.5.
Snap the sensor over the conductor to be monitored and clip the assembly to the6.
mounting bracket.
Set the field-selectable switch to the desired amperage level (see page 2).7.
CONTROLLER
+
–
4-20mA
DC
Load
CONTACTOR