HBX THM-0600 User manual

HBX Control Systems Inc.
Installation Manual
THM-0600 Touch Screen Programmable Thermostat
Version 1.0.0
THM-0600

© 2020 HBX Controls2
INTRODUCTION
This manual will help with the installation, parameter setting, troubleshooting
and general maintenance requirements for the controller. To guarantee the
safe and reliable operation of this control, you must rst read this manual in
detail and take particular note to any and all warnings or caution directives
prior to connecting to AC power. Only suitably qualied individuals with formal
training in electrical and HVAC controls should attempt the installation of this
equipment. Incorrect wiring and installation will affect the warranty provided
with this unit. Wiring must be completed in accordance with the codes and
practices applicable to the jurisdiction for the actual installation.
The HBX THM-0600 is a microprocessor based controller and as such is not to
be regarded as a safety (limit) control. Please consult and install the heating or
cooling appliance in accordance with the manufacturer’s recommendations.
TABLE OF CONTENTS
Introduction Index
Safety symbols and Warnings Index
Receipt and Inspection 1
Description 1
Technical data and dimensions 1
Programming THM-0600 2 - 15
- Navigating the THM-0600 2
- Setting the THM-0600 2 - 5
- Special Functions 2 - 6
- Setup Menu 7 - 19
Installation and Wiring 20-22
Troubleshooting Guide 23-24
Limited Warranty 25
Index
WARNING: This product can expose you to chemicals including lead, which
is known to the State of California to cause cancer and birth defects or other
reproductive harm. For more information go to www.P65Warnings.ca.gov.
!
SAFETY SYMBOLS
Precaution
A measure taken in advance to prevent dangerous or an
unpleasant event.
Drawing Reference
Refer to the specied electrical or mechanical drawing at
the back of the manual.

1
RECEIPT & INSPECTION
After receiving, inspect the unit for any possible physical damage that may
have occurred during transportation. After unpacking the unit make sure the
box contains:
• 1 x Universal sensor (Part #029-0045)
• 1 x Thermostat THM-0600
• 1 x Thermostat Wall Cutout Template
• Instruction Manual
DESCRIPTION
The THM-0600 is a programmable thermostat designed to be used with the
ZON- 0600 Zone Control, and ThermoLinx mobile app.
It is normal for the THM-0600 screen to remain off up to 120 seconds
upon start-up.
The THM-0600 has two external sensor inputs, multiple heating/cooling modes
and can function as a digital setpoint/aquastat.
Some features of the THM-0600 are:
• Dual stage heating or cooling
• P.I.D. algorithm
• Large, full colour touch screen display
• Humidity Control
• Includes external sensor
Technical Data
2 x External Thermistor Input
1 x Power and Communication
1 x Humidity Sensor
Input power: 5VDC 120mA
Dimensions: 80 x 110 x 26mm
ETL Listings:
Only used with ZON-0600
ETL Control No. 3068143
Storage: +10C to +40C
Languages: English
TECHNICAL DATA AND DIMENSIONS
80
3.150
110
4.331
27.90
1.099
14.82
.584
70.50
2.776
45
1.772
13.08
.515
Front View Side View
Bottom View
The THM-0600 is only compatible with the ZON-0600 Zone Control

© 2020 HBX Controls2
INSTALLATION AND WIRING
Mounting Instructions
In order to assure proper room temperature, it is important to identify the ideal
location of the thermostat. It should be approximately 5 feet from the oor
and at least 1 foot from door openings on an interior wall. Avoid exposing the
thermostat to direct sunlight, to air ows (doors, windows, etc.) as well as to
heat sources. Ensure the cavity that the thermostat will be installed in is well
insulated.
1 2 3 4
1 - 2: External Room Sensor
3 - 4: Aux Sensor
TH: Communication
& Power from
ZON-0600
Use a screwdriver to gently pop the front cover off from the top of the thermostat, and
then remove the front to expose wiring terminals.
Do not use the screwdriver on the bottom of the thermostat. This can cause damage to
the THM-0600
External Room Thermistor
On the THM-0600, the room
thermistor switch is located on
the bottom left corner of the
thermostat.
Toggling this switch will allow the
user to alternate between the
built in room thermistor on the
THM-0600, or an external room
thermistor connected to pins 1 and
2 on the THM-0600.
INTERNAL ROOM
EXTERNAL ROOM

3
How to set target temperature
How to see Current Demand
Zone 1
LIVING ROOM
72.3
°F
10:00am
Heat Target
74°F
72.3
°F
Zone 1
LIVING ROOM
Current Demands
Fancoil Heat
Floor
75°F
Target
74°F
10:00am
Zone 1
LIVING ROOM
Floor
75°F
Target
74°F
72.3
°F
10:00am
Zone 1
LIVING ROOM
Floor
75°F
Target
74°F
72.3
°F
10:00am
Outdoor
47°F
Outdoor
47°F
Outdoor
47°F
Outdoor
47°F
Zone 1
LIVING ROOM
72.3
°F
10:00am
Heat Target
74°F
72.3
°F
Zone 1
LIVING ROOM
Current Demands
Fancoil Heat
Floor
75°F
Target
74°F
10:00am
Zone 1
LIVING ROOM
Floor
75°F
Target
74°F
72.3
°F
10:00am
Zone 1
LIVING ROOM
Floor
75°F
Target
74°F
72.3
°F
10:00am
Outdoor
47°F
Outdoor
47°F
Outdoor
47°F
Outdoor
47°F
Note: To view the outdoor
temperature, you must be
connected to a WiFi network.
Additionally, you must also
set a location for your system
on the ThermoLinx app in
settings.
100%9:41 AM
City:
App Degrees:
Contractor Code:
Key: 12345
Location Time Zone
Alaska
-9hrs GMT
Calgary
°C°F
Pacific
-8hrs GMT
Central
-6hrs GMT
Mountain
-7hrs GMT
HOME 83°F
PROGRAMMING THM-0600
Navigating the Thermostat
The touchscreen of this thermostat makes
it easy to change used settings. Touch
any item to adjust its setting excluding the
time on the home screen.
Simply touch the temperature to adjust
your desired target temperature. Pressing
the menu icon on top right corner
allows you to view the main “Setup
Menu” options. Pressing the back icon
allows you to return to the home screen
or setup menu.
Touching the area below the current
temperature allows you to see what
current demands are present.
ZONE 1
LIVING ROOM
Floor
75°F
Target
74°F
72.0
°F
Humidity
30%
10:00am Outdoor
47°F

© 2020 HBX Controls4
Special Functions
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
ATHM-0123
Heat Only
Low
None
Air
None
0°
Setting the Thermostat
Special Functions
Enter the “Special Functions” screen by touching and holding down the
menu icon for 5 seconds (from the status screen). To select the desired
option, simply touch any item to adjust it’s setting.
Unlock Thermostat
Repeat the same process as locking
the thermostat. Press and hold the time
(clock) on the top left corner on the main
screen for 20 seconds. The lock on the
screen will go away.
Zone 1
LIVING ROOM
Floor
70°
F
Target
72°
F
72.0
°F
10:00
am
Special Functions
Type
Heat Only
Backlight
View Auto
Room Offset 0°F
Setbacks
Geo Mode
Outdoor
47°
F
Zone 1
LIVING ROOM
Floor
70°
F
Target
72°
F
72.0
°F
10:00
am
Special Functions
Type
Heat Only
Backlight
View Auto
Room Offset 0
°F
Setbacks
Geo Mode
Outdoor
47°F
No settings will be able to be changed when the thermostat is locked.
Only on the Thermolinx mobile app you will have the ability to still make
changes. When the Thermostat is locked, only minimal temperature target
adjustment can be made. 2°C/3°F above/under.
When the thermostat is locked the menu bar is no longer displayed. To
access special functions, hold the spot where the icon would appear (top
right corner).
Lockout Thermostat
In the special functions menu, press and
hold the lock icon on the top right
corner for 20 seconds. The screen will
automatically go to the main screen and
the thermostat will display a lock icon.
Sync Code
This number is the identier used in the
HBX ThermoLinx App to connect to your
thermostat.

5
2 Stage Heat Function
Select the “2 Stage Heat Function” for applications using
2 stage heating.
Heat Only Function
Select the “Heat Only Function” for applications using a
single heating source.
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Cool Only Function
Select the “Cool Only Function” for applications using a
single cooling source.
Heat and Cool Function
Select the “Heat and Cool Function” for applications
using a single heating source and a single cooling source.
2 Stage Cool Function
Select the “2 Stage Cool Function” for applications using
2 stage cooling.
Type - Select between Heating, Cooling, and a variety of combined modes.

© 2020 HBX Controls6
Low - Low Temperature Demand
High - High Temperature Demand
DHW - Domestic Hot Water (Digital Aquastat)
Fan - Fancoil Demand
Note: DHW only available in heat only type
Demand - This option allows the user to determine what happens when the
thermostat makes a call.
2 Heat with Cool Function
Select the “2 Heat with Cool Function” for applications
using 2 stage heating and 1 stage cooling.
2 Cool with Heat Function
Select the “2 Cool with Heat Function” for applications
using 2 stage cooling and 1 stage heating.
2 Heat and 2 Cool Function
Select the “2 Heat and 2 Cool Function” for applications
using 2 stage heating and 2 stage cooling.
This option is only available in Geo Mode. You must set
Geo mode to to enable this function.
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Cool Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat and Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Stage Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat with Cool
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Cool with Heat
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
2 Heat and 2 Cool
Low
None
Air
Floor
0°

7
The Priority Shield option allows a zone to ignore other
priorities from other zones.
A priority set to none will have no priority and will be
overridden by all other zone priorities.
Priority 1 is a timed priority of 60 minutes, generally used
for DHW.
Priority - This option allows the user to set a priority on a zone(s) over other
zone(s). Priorities range from 1 (highest) to 7 (lowest). Higher priorities will lock
out lower priorities until the demand has been satised. Multiple zones can be
given the same numbered priority.
Mode - This option allows you to select between Air, Floor and Dual sensor
modes. If you are setting your Thermostat as a DHW demand the thermostat
will automatically congure your sensor to a digital Aquastat.
Air
Thermistor within the thermostat sensing temperature
providing feedback for the specic room or zone being
controlled by the thermostat.
Floor
Sensor temperature providing feedback from the
oor surface to the thermostat. This mode will run the
thermostat on oor temperature only. Aux sensor will
automaically be set to oor.
Only available when heating modes are
the primary function. Must have oor sensor
connected.
Floor Mode: Differential
When in oor mode, the differential option is set to allow
a differential around the target to reduce the chances
of short cycling.
Ex. A differential of 4°F is 2°F above the setpoint and 2°F
below the setpoint.
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Differential
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Floor
Floor
6°
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Floor Min
Floor Max
Room Offset
Fancoil Setup
4-Pipe Geo
Dual
Floor
70°
80°
-20°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Differential
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Floor
Floor
6°
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Floor Min
Floor Max
Room Offset
Fancoil Setup
4-Pipe Geo
Dual
Floor
70°
80°
-20°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Differential
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Floor
Floor
6°
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Floor Min
Floor Max
Room Offset
Fancoil Setup
4-Pipe Geo
Dual
Floor
70°
80°
-20°
OFF

© 2020 HBX Controls8
Dual
Sensor temperature providing feedback for both the air
temperature and oor sensor temperatures. Aux sensor
will automaically be set to oor.
Only available when heating modes are
the primary function. Must have oor sensor
connected.
When using the external room/oor sensor on pins
1 and 2 ensure the dipswitch is set to external.
Dual Mode: Min/Max
Max - The thermostat will not allow the oor temperature
to go above this value, protecting the integrity of the
oor covering.
Min - The thermostat will not allow the oor temperature
to go below this value.
None – No external thermistor attached.
Floor – Displays the oor temperature using external 1
sensor
Room - Disregards internal sensor, uses external
Outdoor – Uses external sensor to display outdoor
temperature
RM/Ave – Averages auxiliary sensor and internal sensor,
or optional external room sensor
Floor Ave – Averages auxiliary and optional external oor
sensor in lieu of room sensor
Aux Sensor - Auxiliary thermistor
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Differential
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Floor
Floor
6°
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Floor Min
Floor Max
Room Offset
Fancoil Setup
4-Pipe Geo
Dual
Floor
70°
80°
-20°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Differential
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Floor
Floor
6°
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Floor Min
Floor Max
Room Offset
Fancoil Setup
4-Pipe Geo
Dual
Floor
70°
80°
-20°
OFF
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°

9
Example Actual Room Temperature 72 °F.
Direct Sunlight causes Thermostat to show 78 °F.
The user can put an offset of -6 °F to get the
temperatures to match.
Minimum value -20°F
Maximum value 20°F
If you are utilizing a fancoil, you will have access to the
following settings:
Fan On Demand
Zone On Demand
Temperature Averaging
Fan Mode
Damper Mode
Fancoil Setup: Fan On Demand
This option will turn the fan on with any fancoil demand.
Room Offset - This feature allows you to program an offset. In the case
that the thermostat is not reading the same temperature as the actual
temperature in the room.
Fancoil Setup - This setting takes you to the Fancoil Setup Menu.
Fancoil Setup: Zone On Demand
This option will turn the corresponding zone output on
with a fancoil demand.
Special Functions
ATHM-0000
Stat Type
Demand Type
Priority
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
Heat Only
Low
None
Air
Floor
0°
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF

© 2020 HBX Controls10
Fancoil Setup: Temperature Averaging
This option will average the temperature between
thermostats (User Selectable), when that average falls
below or above the setpoint, depending on if it’s in
heating or cooling, then the thermostat will make a call
for heating or cooling on the fancoil.
None - No temperature averaging
1-2 - Averaging between thermostats 1 and 2
1-3 - Averaging between thermostats 1, 2 and 3
1-4 - Averaging between thermostats 1, 2, 3 and 4
Fancoil Setup: Stage Delay
Use this setting to adjust the lagtime between stage 1
and stage 2. This option is only available when 2 heating
or cooling stages are selected.
Default - 15m
Range - 1m - 240m
Fancoil Setup: Damper Mode
This option utilizes the zone output as a damper zone.
OFF - No damper being utilized in current setup.
Single N/O: Corresponding zone output is utilizing
normally open dampers.
Single N/C: Corresponding zone output is utilizing
normally closed dampers.
2 Stage N/O - 1st stage is radiant and the second
stage is utilizing a normally open damper. This option
will require to use the next corresponding zone output
to accommodate for the second stage damper. This
option is only available for Zones 1 and Zone 3.
2 Stage N/C - 1st stage is radiant and the second
stage is utilizing a normally closed damper. This option
will require to use the next corresponding zone output
to accommodate for the second stage damper. This
option is only available for Zone 1 and Zone 3.
When damper mode is enabled you will not be
able to utilize 4-Pipe Geo mode.
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF
Fancoil Setup
Fan ON Demand
Zone ON Demand
Temp Average
Stage Delay
Damper Mode
OFF
OFF
None
15 mins
OFF

11
OFF - 4-Pipe Geo is disabled
ON - 4-Pipe Geo is enabled
4-Pipe Geo - Controls a 4 pipe system in a geothermal application.
This option will require to use the next corresponding zone output to
accommodate for cooling. This is only available for Zone 1 and 3.
When 4-Pipe Geo is enabled you will not be able
to utilize damper mode.
Save Current Settings - This option will save the current
settings in the event the settings get changed in the
future.
Load Current Settings - This options will load the last
saved current settings.
Factory Reset - Reset all settings back to default.
Default Setup - Restores the thermostat to factory default settings or
previously saved settings.
Selecting this option allows you to change the password.
No - Password will remain the same
Yes - The Thermostat will randomly generate a new
password
Password - Displays the current password to connect to the ThermoLinx App.
Passwords should be updated when device
ownership has changed.
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF
Special Functions
ATHM-0000
THM Mode
Aux Sensor
Room Offset
Fancoil Setup
4-Pipe Geo
Default Setup
Password
Air
Floor
0°
OFF

© 2020 HBX Controls12
Setting the Thermostat
Setup Menu
Enter the “Setup Menu” screen by touching the menu icon. To select the
desired option, simply touch any item to adjust it’s setting.
OFF - Disables scheduling
ON - Enabled scheduling
Weekday Settings (Monday to Friday) - Adjust four time
periods within the weekday program menu.
Weekend Settings (Saturday to Sunday) - Adjust four time
periods within the weekend program menu.
Setting a schedule
Time - Select the time for the schedule to be started by
pressing the time on the desired schedule event.
Cooling Temperature (Blue) - Select the cooling
temperature and adjust accordingly for each schedule
event.
Heating Temperature (Red) - Select the heating
temperature and adjust accordingly for each schedule
event.
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Time
8:00am
Heating
70
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Time
8:00am
Heating
70
Schedules - Allows themostat temperatures to be scheduled up to 4 time
periods for weekdays and weekends.
Heating/Cooling temperatures will only be
displayed if thermostat has a heating/cooling
type selected.
The cooling setting must be a minimum of 2°F
higher than the heating setting.

13
Heating Target - Change the minimum temperature for
your zone. If the temperature in the zone falls below this
temperature, heating will come on.
Cooling Target - Change the maximum temperature
for your zone. If the temperature in the zone increases
above this temperature, cooling will come on.
Auto - The thermostat maintains cooling and heating as
needed
Heat - Overrides the thermostat to heat only mode
Cool - Overrides the thermostat to cool only mode
Off - Disable heating and cooling on the thermostat
Heat Target - This allows the end user to select a heat
target when away mode is enabled.
Cool Target - This allows the end user to select a cool
target when away mode is enabled.
Heating/Cooling Target - The chosen setpoint for heating and cooling zones.
Targets will be accessible in relation to the thermostat type chosen.
Mode - This option allows setting of the thermostat mode to auto, heat, cool
or off.
Away Settings - Set the temperature for when the zone is in Away Mode.
Away mode will override the schedule to a lower/higher temperature.
This feature is unavailable if schedules are
enabled.
Away heat target must never exceed thermostat
target. Away cool target must never be below
thermostat target.
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekday
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Time
8:00am
Heating
70
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Weekend
6:00am
8:00am
4:00pm
10:00pm
70°
66°
72°
64°
Time
8:00am
Heating
70

© 2020 HBX Controls14
ON - Enables the thermostat zone to humidify or
dehumidify.
Auto - Enables the thermostat to humidify or dehumidify
to the target % automatically based on the outdoor
temperature. No manual adjustment is required. The
zoning system must be connected to a wi network
for this feature to be applicable or the thermostat
must utilize an external sensor monitoring the outdoor
temperature. You must enter your location on the
ThermoLinx app for Auto Humidity to work.
OFF - Disables the Thermostat zone to humidify or
dehumidify.
Fan w/ Humidity - This option will turn on your fan when
there is a humidity demand.
Target - When humidity is set to ON, use this setting to
manually adjust your humidity target.
Type - This option allows you to set the thermostat to
humidify or dehumidify.
Fan Settings: Fan Mode
OFF - Fan is off
ON - Enables the fan to run constantly, regardless of
whether the thermostat is calling for heating or cooling
INT - This setting will set the ON/OFF time for the
intermittent fan
Ex: The fan will come on for 15 min every 2H. Set (Int Fan
On: 15 min) & (Int Fan Off: 2H)
Humidity - Enable or disable humidity settings on the thermostat.
Humidity Settings - Congure humidity settings on the thermostat.
Fan Settings - Enable or disable fan settings on the thermostat.
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu

15
OFF - Screen backlight is off during idle
BRIGHT - Screen backlight is at 100%
DIM - Screen backlight is at 50%
°C - Display temperatures in Celcius
°F - Display temperatures in Farenheit
Backlight - This option adjusts the brightness of the thermostat screen during
idle.
Degrees - This option will change the thermostat temperature to either
Celsius (°C) or Farenheit (°F).
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Setup Menu
Schedules
Weekday Settings
Weekend Settings
Mode
Away Settings
Humidity
Humidity Settings
ON
Heat
OFF
ON
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu
Mode
Away Settings
Humidity
Humidity Settings
Fan Settings
Backlight
Degrees
Heat
OFF
ON
Bright
°F
Setup Menu

© 2020 HBX Controls16
Zone 7
Radiant
Damper
7
Zone 1 and 3 are running 1st stage radiant and then
2nd stage damper with cooling
Damper
5
Zone 5
Radiant
C
R
L
N
120 V AC
24 VAC
Zone 1 Zone 3
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
Fancoil
R W Y G C
Fancoil
Heat/Cool
Pump
DO NOT CONNE CT
POWE R HERE
GR
POWER
120
17
NL
1615
0
43
I
TT 1
0
65
I
TT 2
5
TH 1
109
6 5
1211
6 5
1413
6 5
1615
6 2
Y G
2019
2
X
21
2
5A
1
PUMP 1
1 2
1 1
PUMP 2
3 4
1
5A
HBX ZON-0600 Zone Control
N
ZN 1
7 8
H N
9 10
H
ZN 2
N
11 12
H
ZN 3
N
13 14
H
ZN 4
N
5 6
H
ZONE
POWER
5A5A5A5A
1
21
1
W R
Fancoil
Outputs
0
87
I
TT 3
Demand
Outputs
1
1817
1
Thermostat Signal
Communication
Fancoil
Outputs
EXT
THM
TH 2 TH 3 TH 4
Aux. Therm
Input
THM-0600 Drawing 1

17
Zone
Pumps
Zone 1 Zone 2 Zone 3
1 2 3
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
DO N OT CONNECT
POWER HE RE
GR
POWER
120
17
N
L
1615
0
43
I
TT 1
0
65
I
TT 2
5
TH 1
109
6 5
1211
6 5
1413
6 5
1615
6 2
Y G
2019
2
X
21
2
5A
1
PUMP 1
1 2
1 1
PUMP 2
3 4
1
5A
HBX ZON -0600 Zone Control
N
ZN 1
7 8
HN
9 10
H
ZN 2
N
11 12
H
ZN 3
N
13 14
H
ZN 4
N
5 6
H
ZONE
POWER
5A5A5A5A
1
21
1
W R
Fancoil
Outputs
0
87
I
TT 3
Demand
Outputs
1
1817
1
Thermostat
Signal
Communication
Fancoil
Outputs
EXT
THM
TH 2 TH 3 TH 4
Aux. Therm
Input
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
DHW
Sensor
To use external room thermistor,
toggle dip-switch from Internal to
External on THM-0600
L
N
120 V AC
Room
Sensor
THM-0600 Drawing 2

© 2020 HBX Controls18
To use external room
thermistor, toggle dip-
switch from Internal to
External on THM-0600
Zone 1 Zone 3 Zone 4
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
Fancoil
R W Y G C
DO NOT CONNE CT
POWER HERE
GR
POWER
120
17
N
L
1615
0
43
I
TT 1
0
65
I
TT 2
5
TH 1
109
6 5
1211
6 5
1413
6 5
1615
62
Y G
2019
2
X
21
2
5A
1
PUMP 1
1 2
1 1
PUMP 2
3 4
1
5A
HBX
ZON -0600 Zone Control
N
ZN 1
7 8
H N
9 10
H
ZN 2
N
11 12
H
ZN 3
N
13 14
H
ZN 4
N
5 6
H
ZONE
POWER
5A5A5A5A
1
21
1
W R
Fancoil
Outputs
0
87
I
TT 3
Demand
Outputs
1
1817
1
Thermostat Signal
Communication
Fancoil
Outputs
EXT
THM
TH 2 TH 3 TH 4
Aux. Therm
Input
External Room
sensor
(029-0099)
Floor
Sensor
L
N
120 V AC
THM -0600
3
COMM
65
3
TH
2
TH
43
2
Thermostat
1
21
1
DO NOT
CONNECT
POWER
HERE
INT. ROOM
EXT. ROOM
HBX
TH TH
THM-0600 Drawing 3
Table of contents
Other HBX Thermostat manuals
Popular Thermostat manuals by other brands

Siemens
Siemens 5TG5930-1WH operating instructions