Installation Manual
PART 3: SOLAR WATER HEATER INSTALLATION
(CONT’D)
The gaskets in standard water heater flex hose connectors can become brittle and compressed over
time and begin leaking on the water heater. If not detected in a timely manner, even a drip or leak
may cause serious damage to the tank's electrical components or in extreme cases, may cause the
tank to leak from the outside in.
SOLAR HEAT EXCHANGER PIPING
Set the primary balance of the system components down following the piping detail in this manual.
Run ½" type M or greater copper pipes to and from the collector following the direction or supports,
penetrations and other relevant items.
Only copper, cast iron and brass are to be allowed in the collector piping loop due to transient oper-
ating temperatures that may reach as high as 300°F. PEX, PVC, CPVC and other polymers are
expressly prohibited in the piping network.
When making a connection to the heat exchanger, use Teflon Tape and joint compound to prevent
leaks. The connections to the heat exchanger are 1" NPT. Do not apply heat directly to the heat
exchanger thread connection when sweating fittings.
Line pressure and temperature gauge shall be installed in the collector supply and return lines to
allow for a simple diagnostic check of proper system operation. On a sunny day, the hot water return
line should be approximately 5°-12° warmer than the water in the collector supply line. Compare the
temperature readings in the two line thermometers . The ¾" cold water supply line to the SuperStor
Solar Storage Tank must be insulated with a minimum 7/8" x 1/2" pipe insulation to a minimum dis-
tance of 5' behind the storage tank, or to the wall if closer than 5'.
TANK SENSOR PLACEMENT
Make sure the sensor is secured inside the well located in the lower section of the water heater..
Secure the sensor by packing Rubatex insulation behind the sensor. This will also help the sensor
react to temperature change.
Freeze protection fluid must be used to protect the system from freezing and must be rated as non-
toxic. Use a mixture most appropriate for your climate. Do not use a higher glycol to water concen-
tration than necessary, as this will adversely impact heat transfer efficiency. See the DowFrost Data
Sheet in the back of this manual for recommended concentrations. A copy of the MSDS sheet must
be left with the end user of the Solar System. See “EMERGENCY OVERVIEW” as part of the
DowFrost Data Sheet in the back of this manual. The collector loop must be charged with a mixture
of heat transfer fluid and distilled or deionized water. The use of regular tap water as a mixing agent
is prohibited. Scheduled maintenance must be established to monitor and maintain the proper PH
level of the heat transfer fluid in the system to protect the heat exchanger and other components in
the system.
SOLAR HEAT EXCHANGER PIPING TO THE COLLECTOR PANEL
Listed below are the components needed for installation of the SuperStor Contender Solar Water Heater.
1. Solar Collector
Absorbs the sun's energy and transfers this energy into the the heat exchanger located on the bot-
tom of the SuperStor Solar Water Heater .
2. Solar Air Release Vent*
This air vent is used in the solar system to allow air contained in the system to be released.
The air vent valve must be designed to work in high temperatures( as high as 350°F) with a glycol
medium. (This is typical of solar heating systems.)
*Remove and cap the solar air release vent after commissioning the system.