Heinner HDU-M10 User manual

www.heinner.com
28
Thank you for chosing this product!
Please read this instruction manual carefully before using it
ion
This manual is conceived for ofering you all of the necessary info regarding instalation, using
and maintenance of the machine. For a correctly and safely use of the machine, please, read
this manual before instalation and using.
I. INTRODUCTION
II. PACKAGE CONTENTS
Dehumidifier
Instruction Manual
Warranty card
and keep it for later informat

www.heinner.com
29
III. SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following
instructions must be followed. Incorrect operation due to ignoring of instructions may
cause harm or damage.
This symbol indicates that ignoring instructions may cause death or serious
injury.
This symbol indicates that ignoring instructions may cause moderate injury
to your person, or damage to your appliance or other property.
WARNING
1. Do not exceed the rating of the power outlet or connection device.
Otherwise, it may cause electric shock or fire due to excess heat generation.
2. Do not modify power cord length or share the outlet with other appliances.
It may cause electric shock or fire due to heat generation.
3. Disconnect the power if strange sounds, smell, or smoke comes from it.
It may cause fire and electric shock.
4. Do not use the machine near flammable gas or combustibles, such as gasoline,
benzene, thinner, etc.
It may cause an explosion or fire.
5. Do not operate or stop the unit by switching on or off the power.
It may cause electric shock or fire due to heat generation.
6. Do not insert or pull out plug with wet hands.
It may cause electric shock.
7. You should never try to take apart or repair the unit by yourself.
It may cause failure of machine or electric shock.
8. Do not drink or use the water drained from the unit.
It contains contaminants and couls make you sick.
9. Do not damage or use an unspecified power cord.
It may cause electric shock.
10. Do not place the unit neat a heat source.
Plastic parts may melt and cause a fire.
11. Before cleaning, turn off the power and unplug the unit.
It may cause electrical shock or injury.
12. Do not take the water bucket out during operation.
It may cause bucket full protect of the unit and cause electric shock.

www.heinner.com
30
CAUTION
13. Do not use the unit in small spaces.
Lack of ventilation can cause overheating and fire.
14. Do not put in places where water may splash onto the unit.
15. Place the unit on a level, sturdy section of the floor.
16. Do not cover the intake or exhaust openings with cloths or towels.
17. Never insert your finger or other foreign objects into grills or openings. Take
special care to warn children of these dangers.
18. Always insert the filters securely. Clean filter once every two weeks.
19. Care should be taken when using the unit in a room with the following persons:
Infants, children, elderly people, and people not senstive to humidity.
20. Do not place heavy object on the power cord and take care so that the cord is not
compressed.
21. If water enters the unit, turn the unit off and disconnect the power, contact a
qualified service technician.
22. Do not use in areas where chemicals are handled.
23. Do not climb or sit on the unit.
24. Do not place flower vases or other water container on top of the unit.
Water may spill inside the unit, causing insulation failure and electrical shock or fire.
•The manufactures nameplate is located on the rear panel of the unit and contains
electrical and other technical data specific to this unit.
•Be sure the unit is properly grounded. To minimize shock and fire hazards, proper
grounding is important.
•The power cord is equipped with a three-prong grounding plug for protection
against shock hazards.
•Your unit must be used in a properly grounded wall receptacle. If the wall
receptacle you intend to use is not adequately grounded or protected by a time delay
fuse or circuit breaker, have a qualified electrician install the proper receptacle.
•Ensure the receptacle is accessible after the unit installation.
•Do not operate your air conditioner in a wet room such as a bathroom or laundry
room.
•The unit’s circuit board (PCB) is designed with a fuse to provide overcurrent
protection. The specifications of the fuse are printed on the circuit board, such as:
T3.15A/250V (or 350V), etc.

www.heinner.com
31
IV. WARNING FOR USING R32/R290 REFRIGERANT
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources
(for example: open flames, an operating gas appliance or an operating electric heater).
Do not pierce or burn.
Be aware that the refrigerants may not contain an odour. Appliance should be installed,
operated and stored in a room with a floor area according to the amount of refrigerant
to be charged. For specific information on the type of gas and the amount, please refer
to the relevant label on the unit itself.
Appliance should be installed, operated and stored in a room with a floor area larger
than 4 m2. Compliance with national gas regulations shall be observed.
Keep ventilation openings clear of obstruction.
The appliance shall be stored so as to prevent mechanical damage from occurring.
A warning that the appliance shall be stored in a well-ventilated area where the room
size corresponds to the room area as specified for operation. Any person who is
involved with working on or breaking into a refrigerant circuit should hold a current
valid certificate from an industry-accredited assessment authority, which authorises
their competence to handle refrigerants safely in accordance with an industry
recognised assessment specification.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be
carried out under the supervision of the person competent in the use of flammable
refrigerants.
The appliance shall be stored in a room without continuously operating open flames
(for example an operating gas appliance) and ignition sources (for example an operating
electric heater).
Caution: Risk of fire/flammable
materials

www.heinner.com
32
Explanation of symbols on the unit (For R32/R290 refrigerant only):
WARNING This symbol shows that this appliance used a flammable
refrigerant. If the refrigerant is leaked and exposed to an
external ignition source, there is a risk of fire.
CAUTION This symbol shows that the operation manual should be
read carefully.
CAUTION This symbol shows that a service personnel should be handling
this equipment with reference to the installation manual.
CAUTION This symbol shows that information is available such as the
operating manual or installation manual.
1. Transport of equipment containing flammable refrigerants. See transport regulations
2. Marking of equipment using signs See local regulations
3. Disposal of equipment using flammable refrigerants See national regulations.
4. Storage of equipment/appliances. The storage of equipment should be in accordance
with the manufacturer's instructions.
5. Storage of packed (unsold) equipment. Storage package protection should be
constructed such that mechanical damage to the equipment inside the package will not
cause a leak of the refrigerant charge. The maximum number of pieces of equipment
permitted to be stored together will be determined by local regulations.
6. Information on servicing
a. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating
system, the following precautions shall be complied with prior to conducting work on the
system.
b. Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a
flammable gas or vapour being present while the work is being performed.
c. General work area
All maintenance staff and others working in the local area shall be instructed on the nature
of work being carried out. Work in confined spaces shall be avoided. The area around the
workspace shall be sectioned off. Ensure that the conditions within the area have been
made safe by control of flammable material.

www.heinner.com
33
d. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially flammable atmospheres. Ensure that the
leak detection equipment being used is suitable for use with flammable refrigerants, i.e.
non-sparking, adequately sealed or intrinsically safe.
e. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the charging area.
f. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing
any pipe work that contains or has contained flammable refrigerant shall use any sources of
ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition
sources, including cigarette smoking, should be kept sufficiently far away from the site of
installation, repairing, removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the area around
the equipment is to be surveyed to make sure that there are no flammable hazards or
ignition risks. No Smoking signs shall be displayed.
g. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into
the system or conducting any hot work. A degree of ventilation shall continue during the
period that the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
h. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer's maintenance and service guidelines
shall be followed. If in doubt consult the manufacturer's technical department for
assistance. The following checks shall be applied to installations using flammable
refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant; Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.

www.heinner.com
34
i. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is necessary to continue operation, an
adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking; that there no live electrical components and wiring are exposed while charging,
recovering or purging the system; that there is continuity of earth bonding.
j. Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed covers, etc. If it is
absolutely necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical point to
warn of a potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of protection is
affected. This shall include damage to cables, excessive number of connections, terminals
not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure
that apparatus is mounted securely. Ensure that seals or sealing materials have not
degraded such that they no longer serve the purpose of preventing the ingress of flammable
atmospheres. Replacement parts shall be in accordance with the manufacturer's
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to
working on them.
k. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment in
use. Intrinsically safe components are the only types that can be worked on while live in the
presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result
in the ignition of refrigerant in the atmosphere from a leak.
l. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.

www.heinner.com
35
m. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
n. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection
equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used. Leak detection
equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated
to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is
confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall
be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and during
the brazing process.
o. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered to:
Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be flushed with OFN to render the unit safe. This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task. Flushing shall be
achieved by breaking the vacuum in the system with OFN and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum. This process shall be repeated until no refrigerant is within the system. When the
final OFN charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. This operation is absolutely vital if brazing operations on the
pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any
ignition sources and there is ventilation available.
p. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed. Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise the amount of
refrigerant contained in them. Cylinders shall be kept upright.

www.heinner.com
36
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the
system it shall be pressure tested with OFN. The system shall be leak tested on completion
of charging but prior to commissioning. A follow up leak test shall be carried out prior to
leaving the site.
r. Decommisioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall
be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
-Become familiar with the equipment and its operation.
-Isolate system electrically.
-Before attempting the procedure ensure that: Mechanical handling equipment is
available, if required, for handling refrigerant cylinders;All personal protective
equipment is available and being used correctly; The recovery process is supervised
at all times by a competent person; Recovery equipment and cylinders conform to
the appropriate standards.
-Pump down refrigerant system, if possible.
-If a vacuum is not possible, make a manifold so that refrigerant can be removed
from various parts of the system.
-Make sure that cylinder is situated on the scales before recovery takes place.
-Start the recovery machine and operate in accordance with manufacturer's
instructions.
-Do not overfill cylinders. (No more than 80 % volume liquid charge).
-Do not exceed the maximum working pressure of thecylinder, even temporarily.
-When the cylinders have been filled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and all
isolation valves on the equipment are closed off.
-Recovered refrigerant shall not be charged into another refrigeration system unless
it has been cleaned and checked.
s. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.

www.heinner.com
37
t. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely. When transferring
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total system charge is
available. All cylinders to be used are designated for the recovered refrigerant and labelled
for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be
complete with pressure relief valve and associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The
recovery equipment shall be in good working order with a set of instructions concerning the
equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In
addition, a set of calibrated weighing scales shall be available and in good working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition. Before
using the recovery machine, check that it is in satisfactory working order, has been properly
maintained and that any associated electrical components are sealed to prevent ignition in
the event of a refrigerant release.
Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the
refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note
arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If
compressors or compressor oils are to be removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The evacuation process shall be carried out prior to returning the compressor to
the suppliers. Only electric heating to the compressor body shall be employed to accelerate
this process. When oil is drained from a system, it shall be carried out safely.

www.heinner.com
38
NOTE:
All the illustrations in the manual are for explanation purpose only. Your machine may be slightly
different. The actual shape shall prevail. The unit can be controlled by the unit control panel alone
or with the remote controller. This manual does not include Remote Controller Operations, see the
<<Remote Controller Instruction>> packed with the unit for details.
V. IDENTIFICATION PARTS
Control panel
Air outlet grille
Bucket
Water level window (on some
models)
Casters (on some models)
Handle
Air intake grille
Air filter (behind the grill)
Drain hose outlet
Power cord band (used only when
storing the unit)
Power cord
Power plug

www.heinner.com
39
Handle
Control panel
Air intake grille
Air filter (behind the
grill)
Bucket
Air intake grille
Drain hose outlet
Power cord band (used only
when storing the unit)
Power cord
Power plug
Handle
Control panel
Air intake grile
Air filter (behind the grille)
Bucket
Water level window
Air intake grille
Drain hose outlet
Power cord band (used only
when storing the unit)
Power cord
Power plug

www.heinner.com
40
VI. POSITIONING THE UNIT
A dehumidifier operating in a basement will have little or no effect in drying an
adjacent enclosed storage area, such as a closet, unless there is adequate circulation
of air in and out of the area.
Do not use outdoors.
This dehumidifer is intended for indoor residential applications only. This
dehumidifier should not be used for commercial or industrial applications.
Place the dehumidifier on a smooth, level floor strong enough to support the
unit with a full bucket of water.
Allow at least 20cm of air space on all sides of the unit for good air circulation.
Place the unit in an area where the temperature will not fall below 5°C (41 F).
The coils can become covered with frost at temperatures below 5˚C (41 F),
which may reduce performance.
Place the unit away from the clothes dryer, heater or radiator.
Use the unit to prevent moisture damage anywhere books or valuables are
stored.
Use the dehumidifier in a basement to help prevent moisture damage.
The dehumidifier must be operated in an enclosed area to be most effective.
Close all doors, windows and other outside openings to the room.
Casters (At four points on the bottom of unit)
Casters can move freely.
Do not force casters to move over carpet, nor move the unit with water in the bucket.
(The unit may tip over and spill water.)
40 cm or more
20 cm or more
20 cm or more
20 cm or more
40 cm or more

www.heinner.com
41
When using the unit
When first using the dehumidifier, operate the unit continuously 24 hours.
This unit is designed to operate with a working environment between 5˚C and
35°C.
If the unit has been switched off and needs to be switched on again quickly,
allow approximately three minutes for the correct operation to resume.
Do not connect the dehumidifier to a multiple socket outlet, which is also
being used for other electrical appliances.
Select a suitable location, making sure you have easy access to an electrical
outlet.
Plug the unit into an electrical socket-outlet with earth connection.
Make sure the Water bucket is correctly fitted otherwise the unit will not
operate properly.
NOTE: When the water in the bucket reaches to a certain level, please be
careful to move the machine to avoid it falling down.
CONTROL PANEL FEATURES
Note: the following control panels are for explanation purpose only. The control of the
unit you purchased may be slightly different according to the models. Your machine ay
not contain some indicators or buttons. The actual shape shall prevail.

www.heinner.com
42
Indicator Function Indicator Function
Continuous dehumidifying
mode light
Continuous operation on
indicator light
Bucket full indicator light 40% 40% humidity level setted
mode operation on indicator
light
Power light 50% 50% humidity level setted
mode operation on indicator
light
Auto defrost indicator light 60% 60% humidity level setted
mode operation on indicator
light
Note about Auto defrost indicator light:
· When auto defrost is operation on, the indicator humidity level;
· The indicator light flashes at 5Hz under room temperature sensor error or
evaporator temperature sensor error;
· If the auto defrost indicator light flashes, unplug the unit and plug it back in. If error
repeats, call for service.

www.heinner.com
43
Power button
Press to turn the dehumidifier on and off.
Note: The power light illuminates when the unit is switched on and turns dark when the
unit is switched off. When Humidity/Temperature sensor malfunction occurs, the power
light blinks at 5 times per second (on some models).
Continue (CONT) button (on some models)
Select for the dehumidifier to operate continuously for maximum dehumidification until
the bucket is full. The Humdity set control pads cannot be used when Continuous
operation is on. Press this pad again to cancel Continuous operation and enter
dehumidifying mode.
Silent button (On some models)
Control the fan speed. Press to select either High or Low fan speed. Set the fan control
to High for maximum moisture removal. When the humidity has been reduced and
quiet operation is preferred, set the fan control to Low.
Timer button (On some models)
Press to initiate the Auto start or Auto stop feature, in conjuction with the buttons.
When the unit is on, press the Timer button to activate the Auto stop feature. When the
unit is off, press this button to activate the Auto start feature.
Press or hold the and button to change the Auto time by 0.5 hour increments, up to 10
hours, then at 1 hour increments up to 24 hours.
The control will count down the time remaining until start.
The selected time will register in 5 seconds and the system will automatically revert
back to display the previous humidity setting.
Turning the unit ON or OFF at any time or adjusting the timer setting to 0.0 will cancel
the Auto start or Auto stop feature.
When LED display window displays the code of P2, the Auto start or Auto stop feature
will also be cancelled.
UP/DOWN buttons (On some models)
Humidity Set Control buttons
The humidity level can be set within a range of 35% RH (Relative Humidity) to 85%RH
(Relative Humidity) in 5% increments. For drier air, press the button - and set to a lower
percent value (%). For damper air, press the - button and set a higher percent value (%).
TIMER set control buttons
Use the Up/Down buttons to set the Auto start and
Auto stop time from 0.0 to 24.

www.heinner.com
44
Mode/ button
Press to select the operation mode: consitnuously dehumidification –40%
humidity level –50% humidity vele –60% humidity level continuously
dehumidification
Display (On some models)
Shows the set % humidity level from 35% to 85% or auto start/stop time (0~24)
while setting, then shows the actual (±5% accuracy) room % humidity level in a
range of 30% RH (Relative Humidity) to 90%RH (Relative Humidity).
Error codes
AS Humidity sensor error Unplug the unit and plug it back in. If
error repearts, call for service.
ES Tube temperature sensor
of the evaporator error
Unplug the unit ad lug it back in. If
error repeats, call for service.
Protection code
P2 Bucket is full or bucket is
not in right position
Empty the bucket and replace it in the
right position.
Note: When one of the above malfunctions occurs, turn off the unit, and check
for any obstructions.
Restart the unit, if the malfunction is still present, turn off the unit and unplug
the power cord. Contact the manufacturer or its service agents or a similar
qualified person for service.
Other features
Bucket Full Light
Glows when the bucket is ready to be emptied, or when the bucket is removed
or not replaced in the proper position.
Auto Defrost
When forst builds up on the evaporator coils, the compressor will cycle off and
the fan will continue to run until the frost disappears.
Auto Shut Off
The dehumidifier shuts off when the bucket is full, or when the bucket is
removed or not replaced in the proper position. For some models, the fan motor
will continue to run for 30 seconds. Wait 3 minutes before resuming operation
after the unit has stopped, it can not be restart operation in the first 3 minutes.
This is to protect the unit. Operation will automatically start after 3 minutes.
Auto-Restart
If the unit breaks off unexpectedly due to the power cut, it will restart with the
previous function setting automatically when the power resumes.

www.heinner.com
45
VII. REMOVING THE COLLECTED WATER
There are two ways to remove collected water.
1. Use the bucket
When the unit is off, if the bucket is full, the unit will beep 8 times and the Full
indicator light will flash, the digital display shows P2.
When the unit is on, if the bucket is full, the compressor turns off and the fan
turns off after 30 seconds for drying the water of the condenser, then the unit will
beep 8 times and the Full indicator light will flash, the digital display shows P2.
Slowly pull out the bucket. Grip the left and right handles securely, and carefully
pull out straight so water does not spill. Do not put the tank on the floor because
the bottom of the bucket is uneven. Otherwise the bucket will fall and cause the
water to spill.
Throw away the water and replace the bucket. The bucket must be in place and
securely seated for the dehumidifier to operate.
The machine will re-start when the bucket is restored in its correct position.
NOTES:
When you remove the bucket, do not touch any parts inside of the unit. Doing so may
damage the product. Be sure to push the bucket gently all the way into the unit.
Banging the bucket against anything or failing to push it in securely may cause the unit
not to operate. When you remove the bucket, if there is some water in the unit you
must dry it.
2. Continuous draining
Water can be automatically emptied into a floor drain by attaching the unit with a
water hose (not included).
Remove the rubber plug from the back of the unit and store it in a safe location.
Insert the water hose into the unit from the drain outlet in the back of the unit.
Attach the water hose to the drain hose outlet of the unit.
Make sure the connection of the water hose and the drain hose outlet of the unit
is tight and do not let the water leak.
Then lead the water hose to the floor drain or a suitable drainage facility .The
drainage facilify should be lower than the drain outlet of the unit. Be sure to run
the water hose sloping downward and let the water to flow out smoothly. Do not
install the water hose.
NOTES:
When the continuous drain feature is not being used, remove the drain hose from the
outlet.
Table of contents
Other Heinner Dehumidifier manuals
Popular Dehumidifier manuals by other brands

Timberk
Timberk DH TIM 10 E5 instruction manual

Haier
Haier HD308 - 30 Pint Capacity user manual

Danby
Danby DDR45A3GDB Owner's use and care guide

Olimpia splendid
Olimpia splendid AQUARIA SLIM 14 P Instructions for installation, use and maintenance

Movair
Movair MOV10-10L Installation and owner's manual

Rowenta
Rowenta DH4110 manual