
Water Line Connection
The installation of a bypass valve system is recommended to
provide for occasions when the water conditioner must be
bypassed for hard water or for servicing.
The most common bypass systems are the Autotrol® Series
256 bypass valve (Figure 4) and plumbed-in globe valves
(Figure 5). Though both are similar in function, the 256
Autotrol bypass offers simplicity and ease of operation.
INSTALLATION continued
B
Y
P
A
S
S
B
Y
P
A
S
S
B
Y
P
A
S
S
B
Y
P
A
S
S
Figure 4 Autotrol Series 256 Bypass Valve
Water
Conditioner
Water
Conditioner
Not in Bypass In Bypass
Figure 5 Typical Globe Valve Bypass System
Drain Line Connection
1. Ideally located, the unit will be above and not more than 20
feet (6.1 m) from the drain. For such installations, use an
appropriate adapter fitting (not supplied), to connect 1/2-
inch (1.3-cm) plastic tubing to the drain line connection of
the control valve.
2. If the unit is located more than 20 feet (6.1 m) from drain,
use 3/4-inch (1.9-cm) tubing for runs up to 40 feet (12.2 m).
Also, purchase appropriate fitting to connect the 3/4-inch
tubing to the 1/2-inch NPT drain connection.
3. If the unit is located where the drain line must be elevated,
you may elevate the line up to 6 feet (1.8 m) providing the
run does not exceed 15 feet (4.6 m) and water pressure
at conditioner is not less than 40 psi (2.76 bar). You may
elevate an additional 2 feet (61 cm) for each additional 10
psi (0.69 bar).
4. Where the drain line is elevated but empties into a drain
below the level of the control valve, form a 7-inch (18-cm)
loop at the far end of the line so that the bottom of the loop
is level with the drain line connection. This will provide an
adequate siphon trap.
5. Where the drain empties into an overhead sewer line, a
sink-type trap must be used.
CAUTION Never insert drain line into a drain, sewer line or
trap. Always allow an air gap between the drain
line and the wastewater to prevent the possibility
of sewage being back-siphoned into conditioner.
Drain Line Tube
Correct Way
Drain
Figure 6
NOTE: Standard commercial practices have been
expressed here. Local codes may require changes
to these suggestions.
Brine Line Connection
It will be necessary to install the brine tube and line to a fitting
installed on the air check. Use plumber tape on all threaded
connections.
Be sure all fittings and connections are tight so that premature
checking does not take place. Premature checking is when
the ball in the air check falls to the bottom before all brine
is drawn out of the brine tank. See Placing Conditioner into
Operation section.
Overflow Line Connection
In the absence of a safety overflow and in the event of a
malfunction, the BRINE TANK OVERFLOW will direct “overflow”
to the drain instead of spilling on the floor where it could cause
considerable damage. This fitting should be on the side of the
cabinet or brine tank.
To connect overflow, locate hole on side of brine tank. Insert
overflow fitting (not supplied) into tank and tighten with plastic
thumb nut and gasket as shown (Figure 7). Attach length of
1/2-inch (1.3-cm) I.D. tubing (not supplied) to fitting and run
to drain. Do not elevate overflow line higher than 3 inches (7.6
cm) below bottom of overflow fitting. Do not tie into drain line
of control unit. Overflow line must be a direct, separate line
from overflow fitting to drain, sewer or tub. Allow an air gap as
per drain line instructions (Figure 6).
Brine Tank Overflow Fitting
Installed
Connect 1/2-inch (1.3-
cm) Tubing or Hose and
Run to Drain
Figure 7
Low Voltage Transformer
Use only the included transformer for powering the 400 series
timers. Connect the plug of the transformer secondary cable to
the mating socket on the control (see Figure 8).
Be certain that the transformer is plugged into a correct
voltage source that is not controlled by a wall switch.
Autotrol®255 Valve / 400 Series Controls Service Manual SE12 • 7