Henny Penny CBC/CBR-103 User manual

Model CBC/CBR-103,104,105,106,107
3-1. INTRODUCTION This section provides explanations of all controls, along
with operating procedures and daily maintenance. Read the
Introduction, Installation and Operation ections before
operating the unit.
Wait at least 4 hours before plugging the unit into an
electrical supply The gases and oils in the refrigeration
system need to settle before operating the compressor, or
damage to the compressor could result
3-2. OPERATING CONTROLS Refer to figure 3-1.
Fig. I em Descrip ion Func ion
No. No.
3-1 1 Power witch A rocker switch that turns electrical power off and on to
the unit; located on the bottom of the control panel
3-1 2 Digital Display hows the temperatures and the information in the Technical
Mode
3-1 3 The up and defrost button is used to increase setpoint
values, as well as programming values; also, automatic
defrost cycles are programmed in the controls, but to
manually start a defrost cycle, press and hold for 3
seconds to start a manual defrost cycle
(“DEF/ ET’ shows in display)
3-1 4 The down button is used to decrease setpoint values, as
well as programming values
3-1 5 Press the set button to view the setpoint temperature, or
hold it for it for 4 seconds to enter the Program Mode;
once in the Program Mode, press to view other
parameter setpoints; press , along with and
to change the parameters.
SECTION 3. OPERATION
3-1 303

Model CBC/CBR-103,104,105,106,107
Figure 3-1
3 2 1
4 5
303 3-2
3-2. OPERATING CONTROLS
(Con inued)

Model CBC/CBR-103,104,105,106,107
3-3. BASIC OPERATION 1. Turn power switch to ON position.
2. Wait for temperature to reach operating temperature,
36 to 38° F (2.2 to 3.3° C).
3. Place chilled, prepackaged product into case.
Do no s ock produc in he case beyond he load heigh
limi of 9 inches (23 cm), or over he fron edge. Prod-
uc empera ures may become unsafe, and increase
opera ing cos s.
Do not use mechanical devices or other means to quicken
the defrosting process, other than those recommended by
the manufacturer, or damage to the unit could result
Do not use electrical appliances inside the food storage
areas of the unit, unless they are of the type recommended
by the manufacturer, or damage to the unit could result
3-4. CLEANING Weekly:
1. Remove all electrical power supplied to the unit by unplug-
ging the power cord from the wall, or by turning off the
wall circuit breaker.
2. Clean interior and exterior surfaces with a soft cloth, soap and
water.
Do not use steel wool, other abrasive cleaners or
cleaners/sanitizers containing chlorine, bromine, iodine
or ammonia chemicals, as these will deteriorate the
stainless steel, and glass material, and shorten the life of
the unit
Do not use a water jet (pressure sprayer) to clean the
unit, or component failure could result
3. Clean around the electronic controls with a soft, damp cloth.
4. Reconnect the electrical power to the unit and unit is now
ready for operation.
3-3 303

Model CBC/CBR-103,104,105,106,107
3-4. CLEANING Every 3 Mon hs:
(Con inued) 1. Remove all electrical power supplied to the unit by unplug-
ging the power cord from the wall, or by turning off the
wall circuit breaker.
2. Remove all product from the unit.
3. Remove the riser and trays from the unit and clean with
soap and water at a sink.
4. Clean interior surfaces with a soft cloth, soap and water.
Do not use steel wool, other abrasive cleaners or
cleaners/sanitizers containing chlorine, bromine, iodine
or ammonia chemicals, as these will deteriorate the
stainless steel, and glass material, and shorten the life of
the unit
Do not use a water jet (pressure sprayer) to clean the
unit, or component failure could result
5. Clean around light fixtures with a soft, damp cloth.
6. Reconnect the electrical power to the unit and unit is now
ready for operation.
If he power cord is damaged, have a qualified service
echnician replace i o preven elec rical shock or
proper y damage.
303 3-4

Model CBC/CBR-103,104,105,106,107
3-5. PROGRAMMING 1. Press and hold for 4 seconds. The “DEF/ ET” light
flashes in display.
Tempera ure Se poin
2. Press the or to change the temperature setpoint,
within 5 seconds. After 5 seconds, the last entered setpoint
stays in memory.
O her Parame ers
3. Press to access the other parameters. Each press of the
accesses the next parameter. The parameters are:
d: (differential) (-15...15 range)
LS: lower set; lower user-access setpoint limit
(-55...99 range)
The units are programmed to defrost 3 times a day, at 8
hour intervals, lasting 30 minutes Do not program the
setpoint temperature below 33° F (1° C), or ice build-up
will decrease efficiency
HS: (higher set) upper user-access setpoint limit
(-55...99 range)
CA: (calibration) temperature readout offset to allow for
possible error due to probe location. (-15...15 range)
rP: (relay protection) elect relay status in case of probe defect.
“on” = compressor ON in case of probe defect
“of” = compressor OFF in case of probe defect
PS: (protection system-short cycle) select type of compressor
protection desired (the actual time delay is set with the next
parameter):
“0”=delay before start - in seconds
“1”=delay before start - in minutes
“2”=delay after stop - in minutes
“3”=delay between starts - in minutes
P : (protection time) select the time delay setting for compres-
sor protection. (0...31 range)
3-5 303

Model CBC/CBR-103,104,105,106,107
3-5. PROGRAMMING dS: (defrost system (computation)) dF=digifrost feature;
Con inued defrost start time based on total compressor running time.
rt=real time; defrost start frequency, based on real time
dI: (defrost interval) defrost frequency in hours, based on the
selection of “d ”
dE: (defrost endurance) total (maximum) length of a defrost
cycle, expressed in minutes. (1...99 range)
dL: (display lock) temperature display is locked during a
defrost cycle. (0...31 range)
“n”=no (readout continues to display the actual tempera-
ture, even during a defrost cycle
“y”=yes (readout is locked)
dr: (display read-out) select the type of visualization in case of
temperature display lock during defrost (see prameter dL)
“C”=the temperature displayed at the start of a defrost is
locked and does not change during this cycle
“dF”=during the defrost “dF” is displayed
do: (defrost at power on) selects whether or not, the system
goes through the defrost cycle at start-up (or after power
failure)
“n”=no
“y”=yes
dd: (defrost delay at power on) delay of defrost cycle, in
minutes. (0...99 range)
Error Code “E1”
This is the only error code in these controls. It indicates a tempera-
ture sensor failure, such as, a shorted sensor, a sensor break, or
absence of sensor.
It can also indicate an under-range in the system temperature (-55).
In case of an over-range in the system temperature, “99” shows first
in the display, followed by “E1”.
303 3-6
Other manuals for CBC/CBR-103
1
This manual suits for next models
4
Other Henny Penny Refrigerator manuals