INSTRUCTION MANUAL
DISPLACER TYPE LEVEL SWITCH
HM-30, 90 Series

HM-30, 90 Series
HITROL CO., LTD. 2
You should be careful where CAUTION is marked to carry
out the work.
You should be well-informed of the contents where
WARNING is marked before carrying out the work.
.
You should be aware of where NOTICE is marked to carry
out the work.
Table of Contents
Overview ................................................................. 3
Operating Principles ............................................. 3
Characteristic ............................................................. 3
Applications ............................................................. 4
Specification ............................................................. 4
Weather-Proof Version ...................................................... 4
Ex-proof Version ................................................................... 4
Process Condition Rating .................................... 5
Product Configuration and Technical Data ....................... 5
Dimensions and Detailed Technical Specifications .... 6
Weather-Proof Version ...................................................... 6
Ex-Proof Version ................................................................... 8
Contact Form ......................................................................... 9
Guide Pipe Version ........................................................... 10
Chamber Version ............................................................... 10
Switch Action and Specification ................................ 11
Wiring ................................................................... 12
SPDT Wiring ............................................................................ 12
DPDT Wiring............................................................................. 12
Installation .............................................................. 13
Precautions for Installation ............................... 14
Failure Check ....................................................... 14
Maintenance ........................................................... 14
Precautions for Removal..................................... 15
Precautions for Transportation and Assembly ............ 15
Precautions for Grounding ................................. 15
Precautions for Inserted External Wire
(Ex-proof) .. 15
Safety and Environment ........................................ 16
Marking ................................................................. 16
User Training ........................................................ 17
Warranty and Contact ........................................ 17

HM-30, 90 Series
HITROL CO., LTD. 3
HM-30, 90 Series is a level detector with ON/OFF contact signals to detect upper and lower limits
of vessel. It is firmly designed to be used in high temperature and pressure with excellent
reliability. It is mainly used as a water level detector for boilers of power plants and refining
equipment of petrochemical plants.
HM-30, 90 Series is installed on top of tank or connected chamber and works with buoyancy of displacer and
tension of spring.
If the displacer is submerged when the level of measure object rises, it becomes lighter because of the buoyancy,
where the spring that was compressed by the weight of displacer is released so the core rises within the enclosing
tube. The magnet which is connected with the switch responds to trigger the switch when the core rises.
■ Solid structure and long service life
■ Applicable to high temperature and pressure vessels
■ Current operation state display
■ Customizable with special material (Alloy)
■ Explosion proof version (HM-90-Ex, HM-90H-Ex)
■ ASME B31.1, ASME B31.3 (if chamber design is required)
Overview
Operating
Principles
Characteristic
Core
Enclosing tube
Spring holder
Chain (Wire)
Displacer
Cover
Extension Spring
Base

HM-30, 90 Series
HITROL CO., LTD. 4
Applications
Specification
■ Feedwater heater ■ Steam drum
■ Condensate drip pot ■ Flash tank
■ Separator ■ Receivers
■ Accumulator
Weather-Proof Version
Model HM-30 HM-90 HM-90H
Installation Top
Ambient Temperature -20˚C ~ +80˚C
Process Temperature
Max.
-40˚C ~ +120˚C
Max.
-40˚C ~ +120˚C
Max.
-40˚C ~ +200˚C
-40˚C ~ +350˚C
-40˚C ~ +500˚C
Process Pressure ATM Up to 63kg/cm2 (900#)
Contact Form SPDT, DPDT
Enclosure Weather-Proof (IP65)
Switch Type Snap Switch, Hermetical Sealed Switch
Process Connection 50A JIS 10K FF(6T)
80A JIS 10K RF (Std.)
Material Displacer SUS 304 / SUS 316L
Chamber N/A C.S / SUS 304 / SUS316L / Others
Cable Entry C.S; PF 3/4”(F) / AL; PF 3/4”(F) (Std.)
Ex-proof Version
Model HM-90-Ex HM-90H-Ex
Installation Top
Ambient Temperature -20˚C ~ +80˚C
Process Temperature Max.
-40˚C ~ +120˚C
Max.
-40˚C ~ +200˚C
-40˚C ~ +350˚C
-40˚C ~ +500˚C
Process Pressure Up to 63kg/cm2 (900#)
Contact Form SPDT, DPDT
Enclosure Ex-Proof (Ex d IIC T4, IP65)
Switch Type Snap Switch
Process Connection 80A JIS 10K RF (Std.)
Material Displacer SUS 304 / SUS 316L
Chamber C.S / SUS 304 / SUS316L / Others
Cable Entry AL; PF 3/4”(F) (Std.)

HM-30, 90 Series
HITROL CO., LTD. 5
■ HM-90 Series
Base
Cover
Cooling
fin
Terminal box
Process
Condition
Rating
Product
Configuration
and Technical
Data
Application ratings for each product according to process conditions
Model
Process HM-30/90 Series
Ambient Temp. Change
A
Process Temp. Change A
Vibration (Motor) C
Corrosivity B
Slurry B
Steam A
Viscosity/ Adhesive B
A = Very Good: It has little or no effect on the performance of the product, and is suitable for application.
B = Good: The product can handle the conditions, but it may be affected by performance, so it should be noted for maintenance. (Cleaning)
C = Poor: The product does not meet the conditions.
Carbon Steel Housing (Weather-Proof)
Carbon Steel Housing + Terminal Box (Weather-Proof)
Aluminum Housing (Weather-Proof, Ex-Proof)
Aluminum Housing + Terminal Box (Weather-Proof)
Wetted parts
<Standard>
<Protection Tube>
<Side to Side>
Flange
Chain
Extension
spring
Extension
spring
Extension
spring
Spring holder
Spring holder
Spring holder
Displacer Displacer
Wire
Guide pipe
Flange
Flange
Wire
Chamber
Displacer
Process
Conn.
flange
Terminal box
Base
Cover
Cooling
fin

HM-30, 90 Series
HITROL CO., LTD. 6
Weather-Proof Version
Some tolerances may occur with actual products.
Dimensions
and Detailed
Technical
Specifications
The dimensions on the following pages are indicated in [mm].
Process
Temp. ~120˚C ~200˚C ~350˚C / ~500˚C ~500˚C (Opt.)
C.S +
Aluminum
Housing
(S/W 1ea)
C.S +
Aluminum
Housing
(S/W 2~3ea)
C.S +
Aluminum
Housing
(S/W 4ea)

HM-30, 90 Series
HITROL CO., LTD. 7
Some tolerances may occur with actual products.
Process
Temp.
~120˚C ~200˚C ~350˚C / ~500˚C ~500˚C (Opt.)
Aluminum
Housing
(S/W 1ea)
Aluminum
Housing
(S/W 2~3ea)
Aluminum
Housing
(S/W 4ea)

HM-30, 90 Series
HITROL CO., LTD. 8
Ex-Proof Version
Some tolerances may occur with actual products.
Process
Temp. ~120˚C ~200˚C ~300˚C ~350˚C
Aluminum
Housing
(S/W 1ea)
Aluminum
Housing
(S/W 2~3ea)
Aluminum
Housing
(S/W 4ea)

HM-30, 90 Series
HITROL CO., LTD. 9
Contact Form
Some tolerances may occur with actual products.
1F 2F
1F 2F

HM-30, 90 Series
HITROL CO., LTD. 10
Guide Pipe Version
Chamber Version
Some tolerances may occur with actual products.
HM-90A
HM-90B

■ Switch Action
The core rises within the enclosing tube because of buoyancy when the level of
rises and the displacer is submerged. The magnet which is connected with the switch responds to
trigger the switch when the core rises.
■
Switch Specifications by Process Temperature
Switch
Action and
Specification
Std. Type
Std. Type
Core
Enclosing tube
HITROL CO., LTD.
The core rises within the enclosing tube because of buoyancy when the level of
rises and the displacer is submerged. The magnet which is connected with the switch responds to
trigger the switch when the core rises.
Switch Specifications by Process Temperature
Opt. Type Process Temp.
~ 200˚C
~ 350˚C
Opt. Type Process Temp.
Snap switch
Magnet
Core
Enclosing tube
HM-30, 90 Series
11
The core rises within the enclosing tube because of buoyancy when the level of
measure object
rises and the displacer is submerged. The magnet which is connected with the switch responds to
Contact Rating
AC 250V, 15A
DC 125V, 0.5A
AC 250V, 5A
DC 125V, 0.5A
Contact Rating

HM-30, 90 Series
HITROL CO., LTD. 12
Specifications of Temperature and Contact Form (SPDT, DPDT) are optional.
+ 외부 단자함
~ 500˚C AC 250V, 1A
DC 125V, 0.4A
Wiring
First of all, remove the product housing cover for wiring. For High or Low alarm, connect
the wires to the terminal COM-N.O of the switch block. For H/L Control, connect to COM-
N.C for water supply control and COM-N.O for water drainage control. The housing is
designed to prevent damage from dust or water, and if necessary, anti-corrosion (Epoxy
Coated) housing is optional.
■ SPDT Wiring
■ DPDT Wiring
Internal circuit
1
2
3
Common (COM)
Normal Open (N.O)
Normal Close (N.C)
Common (COM)
Normal Open (N.O)
Normal Close (N.C)
Common (COM)
Normal Open (N.O)
Normal Close (N.C)

Prevent the heat of content from being transferred to the instrument when installing the
■
Conditions for Installation and Adjustment
-
Default connection is top type but it is
According to the dimensioned drawing, the connection and main unit must be leveled
and it is recommended to install a bracket to support the product if necessary.
- Check Ex
-
the temperature of measure object exceeds 350
product
(HM
- If the
temperature
produc
t (HM
shown below.
Installation
HITROL CO., LTD.
Prevent the heat of content from being transferred to the instrument when installing the
Conditions for Installation and Adjustment
Default connection is top type but it is
customized to side to side, side to bottom.
According to the dimensioned drawing, the connection and main unit must be leveled
and it is recommended to install a bracket to support the product if necessary.
-proof rating and fluid temperature before applying an Ex
the temperature of measure object exceeds 350
˚
C, cannot use an Ex
(HM
-90H-Ex).
temperature
of measure object exceeds 120˚
C, use a high
t (HM
-90H, HM-90H-
Ex), and insulate the main unit and connection as
shown below.
Vessel
Isolation valve
HM-90B
HM-30, 90 Series
13
Prevent the heat of content from being transferred to the instrument when installing the
product.
customized to side to side, side to bottom.
According to the dimensioned drawing, the connection and main unit must be leveled
and it is recommended to install a bracket to support the product if necessary.
proof rating and fluid temperature before applying an Ex
-proof product. If
C, cannot use an Ex
-proof type
C, use a high
-temperature
Ex), and insulate the main unit and connection as

HM-30, 90 Series
HITROL CO., LTD. 14
Regular inspection ensures optimal performance of product. Take regular inspection and
maintenance at least every year.
■ Chamber
- The chamber is designed to endure high temperature and pressure, and its safety is confirmed
with non-destructive and water-pressure tests. However, corrosion can lead to leak in a harsh
working environment, so regular visual check and test are required.
■ Housing of Switch
- Check the sealing of housing cover and wire inlet to prevent penetration of dust or rain and
replace the sealing if it is old or damaged.
- Exposure to excessive heat or humid may damage the insulation of wire inlet. It may lead to short
circuit, so check the wiring and replace it if necessary in advance.
- Tighten the terminal carefully or it may be loosened because of vibration.
- Continuous process operation may be hindered by failure of switch block, so prepare a spare switch block.
- Remove the product from the vessel and check and reset the contact of level switch using a liquid
(ex. Water) on the process connection.
If there is a problem with operation, check the followings first.
■ Remove the cover and check the output contact of snap switch. (Check the output by connecting
COM with N.O or N.C using a tester.)
Replace the snap switch if necessary.
■ After checking the snap switch, remove the product and move up or down the displacer and
recheck the contact with the tester. When moving up of down the displacer, check the internal core
(magnet) and the fixed magnet on the switch block.
■ Recheck if the measuring point of fabricated product and level of measure object are leveled.
■ When moving up or down the displacer, check if the extension spring is correct displaced.
■ Use the same standard flange or screw.
■ Make sure to insert washers between bolts and nuts to prevent loosening.
■ Make sure to insert gaskets between flanges. (Select the gaskets in consideration of temperature of
content and pressure of vessel.)
■ Install an Ex-proof prodct only in an Ex-proof zone.
For maintenance, check the presence of measure object in the tank and remove it.
Learn how to adjust the switch block first, and contact the headquarters or dealership for any replacement required.
Do not insulate the housing and cooling fin.
Precautions
for
Installation
Failure
Check
Maintenance

HM-30, 90 Series
HITROL CO., LTD. 15
■ Check the level and presence of measure object in the tank before removing it.
■ Wear gloves when removing it, to prevent a burn.
■ If there is explosive gas atmosphere, do not open the cover.
■ Make sure that any O-ring or gasket is not damaged while ope
ning or closing the
cover of product.
■ Unlock the lock key before removing the cover.
■ Disconnect the cable before removing the snap switch.
■ Pay special attention to prevent any impact on the device during transportation or assembly.
■
Pay attention to prevent any damage to any packing when transporting or mounting
the machine to the vessel.
Make sure that it is not subject to any high impact when moving the product.
■ External ground is located on top of cable entry, and the grounding wire to connect external
ground must be 4㎟ (4mmSQ). (Internal ground is connected before shipment.)
Make sure to insert a washer if the terminal lug is removed from the ground terminal
and then re-connected.(Loosening prevention)
■ Use the cable gland connection or metal pipe line lead-in on the wire
inlet, and use a product
with equivalent Ex-proof certificate to connect it with the external line lead-in method.
■ For non-use external wire inlet, use a closed plug that passes safety certificate above equivalent
performance with the product.
Precautions
for
Removal
Precautions
for
Transportation
and Assembly
Precautions
for
Grounding
Precautions
for
Inserted
External
Wire
(Ex-proof)

HM-30, 90 Series
HITROL CO., LTD. 16
■ Product Identification
- The product identification mark is attached onto the housing and shows the model name, serial
number, working temperature, working pressure, and matters regarding output. The serial number
is a unique manufacturing number for the identification of products.
■ Understand the aforementioned and do not exceed 120℃ and 500℃ respectively for the liquid
in the general and high-temperature vessels to use the product. In addition, make sure that the
ambient temperature of housing is kept at -20 - +80℃. (However, Ex-Proof product is limited to a
maximum temperature of 350℃ for the liquid in the container.)
■ Make sure to use high-temperature cables with high-temperature products.(To prevent damage
to the cable).
■ An Ex-proof product is a pressure-resistant and Ex-proof type, so never open the cover during
operation.
■ Ex-proof products are designed according to Article 34 of the Industrial Safety and Health Act
and Article 58.4 of the Enforcement Rules of the same Act.
■ Precautions for Use
- Make sure to connect the product and vessel using required tools for sure.
- Keep the lock key safe and make sure that it is locked.
- Do not apply high impact to the product.
■ Precautions for Wiring
- Make sure to wire contacts correctly.
- Pay attention to prevent electric shock.
■ Disposal of Product
- Remove the snap switch of switch block from the housing before disposing a product.
- No part (ex. Mercury switch) has influence on the environment, so no special attention is required.
Safety and
Environment
Marking
User
Training
Weather-proof Version Ex-proof Version

HM-30, 90 Series
HITROL CO., LTD. 17
■Warranty and Service
This product is subject to the warranty for 2 years of shipment and unpaid service will be
provided for any damage found under normal operating conditions. If it is not about the
failure of product, the service charge will be payable.
You can request A/S at our website or by contacting our headquarters.
■ Headquarters ․ Factory ․ Laboratory Contact Number
ADRESS:
HITROL CO., LTD 141, Palhakgol-gil, Jori-eup, Paju-si, Gyeonggi-do, Korea
T E L : 031-950-9700 (Headquarters & A/S)
F A X : 031-943-5600 (Headquarters & A/S)
Do not apply a Non-ex-proof product in an Ex-proof zone.
An ex-proof product can be used where the environment and liquid inside the containers
are of zone 1 and 2.
Additional information after product installation
Since this product is set based on specific gravity 0.8 and 1, there is a slight error
depending on the usage environment.
If you want to measure in the correct section, you need to set it on site.