Honeywell ExitLED PRO M ST User manual

GB
ExitLED PRO
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com
Installation:
DS1
Step 6: The control of maintained or non maintained operation of the luminary
is achieved through Switch 4 of DS1. For maintained operation, switch number 4 must be in ON position. For non-
maintained operation, switch number 4 must be in OFF position.
Step 5: In case you use a module connect it on the PCB.
Step 4. Connect the battery cable to its respective connector on the PCB.
Two additional labels are included in the package, one for 3 hours duration (180) and one for 8 hour duration
(480). Depending on the selected duration, the installer must cover the default 1 hour (60) printing with one
that has the required duration.
Please take notice of the orientation of the label.
The user can select one of the 3 available minimum autonomy durations: 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is
achieved through Switches 2 & 3 of DS1. Switch 1 is not used.
Step 1: For double sided pictogram, install the appropriate pictograms to both
sides, push up until you hear click sound. For single sided pictogram, there
is one blind pictogram in the package.
Step 2: Install the retaining clip to hold the pictograms.
Step 3: Dismantle the luminaire by sliding the mounting part as shown in
picture. Fasten the mounting part (with screws from within) to wall (with
or without supplied spacers) or ceiling (with or without supplied spacers).
See the next page for mounting methods.
56
4
2
13
50mm
50mm
347mm
205mm
155mm
804029000
Maintained operation
ON
1 2 3 4
ON
1 2 3 4
Non-maintained operation
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
1h
(default position) 3h 8h
Dip Switch Positions (DS1)

Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com
GB
Mounting Methods
Ceiling Mounting
23
To mount the luminaire to the ceiling, with or wihout supplied spacers, the mounting holes must face
towards to the ceiling.
Step 1: Dismantle the luminaire by sliding the mounting part as shown in picture.
Step 2: Slide the plastic part with the terminals to the mounting part, until you hear click sound.
Step 3: Install the ground wire as shown in picture.
Step 4: Fasten the mounting part with the supplied mounting accessories. Drill a hole on a black grommet
and pass the mains cables through it.
Step 5: Connect the mains cables to terminal blocks: L for live wire, N for neutral and PE for ground. Power
2
supply cables cross section should be 0.8 - 3 mm . The C1 and C2 terminals are used for elBus
communication optional), DALI communication (optional), or voltage free contact (optional).
Tighten the cable tie around the cables.
Step 6: Slide the main body of the luminaire back to the mounting part.
Step 8: Slide the aluminium protective covers to both sides of the luminaire, until you hear click sound.
Step 7: Fasten the screw on the side of the luminaire.
1
8
Screw
Wall Plug
Power
Cable
L NPE
C1C2
64
7
5

Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com
GB
Mounting Methods
Wall Mounting
23
1
8
Screw
Wall Plug
Power
Cable
L NPE
C1C2
64
7
5
Step 6: Slide the main body of the luminaire back to the mounting part.
Step 3: Install the ground wire as shown in picture.
Step 4: Fasten the mounting part with the supplied mounting accessories. Drill a hole on a black grommet
and pass the mains cables through it.
To mount the luminaire to the wall, with or wihout supplied spacers, the mounting holes must face towards
to the wall.
Step 1: Dismantle the luminaire by sliding the mounting part as shown in picture.
Step 2: Slide the plastic part with the terminals to the mounting part, until you hear click sound.
Step 7: Fasten the screw on the side of the luminaire.
Step 5: Connect the mains cables to terminal blocks: L for live wire, N for neutral and PE for ground. Power
2
supply cables cross section should be 0.8 - 3 mm . The C1 and C2 terminals are used for elBus
communication optional), DALI communication (optional), or voltage free contact (optional).
Tighten the cable tie around the cables.
Step 8: Slide the aluminium protective covers to both sides of the luminaire, until you hear click sound.

GB
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com
Technical description
Part no.:
Battery (NiMH):
Battery Protection:
Min./Max. Charge Current: 50 / 170 mA
Overcharge protection / Deep discharge protection
o
5 to 40 C
Up to 95%
16 hours
Produced in accordance with:
Ambient Temperature Range:
Maximum Power Consumption:
Operation Voltage:
Relative Humidity:
Charging Time:
Technical lifetime (light source):
Lumen output, normal:
> 100000 hours
220lm
ExitLED PRO M ST LED 230V w/pict 138h
4W / 4.25VA
220-240V AC, 50-60 Hz
138011
3.6V / 1.7Ah
IP40
1h / 3h / 8h manually selected (default 1h)
Degress of cover protection:
Emergency Mode Duration:
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
Charge Voltage Range: 3.0 - 4.5 V
Lumen output, emergency (1h/3h/8h): 220/185/75lm
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
1000 gr
4 years
At the end of their useful life the packaging, product
and batteries should be disposed of via a suitable
recycling centre. Do not dispose of with your normal
household waste. Do not burn.
Disconnect mains, carefully remove the luminaire from the ceiling or wall. Dismantle the luminaire.
Disconnect the battery and install a new one of the same type and charatecteristics.
Note: In case of mains power disconnection for a period of more that two months, the battery must be
disconnected.
NOTE! The light source is non-user replaceable.
In case that the luminaire no longer meets its rated duration of operation, the battery must be replaced.
Important notice when installing luminaires within the same area!!!
To avoid that luminaires perform their battery test at the same day, connect the battery packs with more
than 1,5 minutes inbetween.
Battery Replacement:
Note: In case of battery replacement, this must be replaced with parts of the same type and characteristics.
The replacement must be performed by the manufacturer of a competent person.
Note: If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person
in order to avoid hazard.
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent,
or a similar qualified person.

GB
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com
Indicator LEDs
LED Status explanation
Description
GREEN
RED
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery fault
Battery test (Duration: 1h,3h,8h)
Light source test (Duration: 3s)
Light source fault
Battery fault and light source fault
Off On Slow Blink Fast Blink
Push the test button for >10 seconds to delete all indicated errors. Then the luminaire enters regular operation mode.
Dimming
This test will last for the chosen capacity and can only be performed when the
battery is fully charged (steady green LED). The light source will be lit and the
green LED will flash during this test sequence.
Selftest functions
Manual tests can only be performed if both mains and battery are connected.
The ExitLED PRO is a self-contained maintained/non-maintained luminaire with selftest function.
Every 6 months the luminaire will perform a battery condition test. The test will last for the chosen capacity. The light
source will be lit and the green LED will flash during this test sequence.
Note: When using DALI or Wireless communication, the frequencies and schedules for tests will instead be determined
by the connected PC software.
By pressing the test button briefly (less than 5 seconds) an emergency operation
test is performed. The light source will be lit for approximately 3 seconds, the
green LED will flash during this test sequence.
Every 15 days the luminaire will perform an emergency operation test. This will turn on the light source for
approximately 3 seconds. The green LED will flash during this test sequence.
Manual test functions
By pressing the test button for between 5 and 10 seconds a battery condition test
is performed.
Resetting errors
By pressing the test button continuously for 15 seconds, when luminaire is connected to mains, the luminosity will be
reduced to 10% of its total luminance. In emergency mode the light output will remain unchanged.
To restore the original settings, repeat the above procedure.
The dimming setting remains stored in the luminaire even when both mains and battery voltages are disconnected.
TEST
This manual suits for next models