3.3 Technical data UltraGas®(250D-700D)
Type (250D) (300D) (400D) (500D) (600D) (700D)
• Nominal output 80/60 °C with natural gas 1kW 25-226 25-276 39-370 44-454 51-546 51-636
• Nominal output 40/30 °C with natural gas 1kW 28-246 28-300 44-400 49-500 57-600 58-700
• Nominal output 80/60 °C with propane gas 3kW 31-226 35-276 63-370 78-454 80-546 95-636
• Nominal output 40/30 °C with propane gas 3kW 34-246 39-300 70-400 87-500 91-600 109-700
• Nominal load with natural gas 1kW 26-232 26-282 40-376 45-470 52-566 53-660
• Nominal load with propane gas 3kW 32-232 36-282 65-376 80-470 84-566 100-660
• Working pressure heating maximum/minimum bar 5,0 / 1,0 5,0 / 1,0 5,0 / 1,0 5,0 / 1,0 5,0 / 1,0 6,0 / 1,0
• Working temperature maximum °C 90 90 90 90 90 90
• Boiler water content l 412 388 719 682 636 857
•Minimumwaterow l/h000000
• Boiler weight (without water content, incl. casing) kg 766 818 1268 1344 1448 1730
•Boilerefciencyatpartialloadat30%(accordingtoEN303)
(relatedtonet/grosscaloricvalue) %106,9/96,3 106,9/96,3 106,7/96,1 106,5/95,9 107,4/96,4 107,3/96,7
•Standardefciency 40/30 °C %109,6/98,7 109,6/98,7 109,7/98,8 109,7/98,8 109,7/98,8 109,8/98,9
(relatedtonet/grosscaloricvalue) 75/60 °C %107,1/96,5 107,1/96,5 107,2/96,6 107,2/96,6 107,2/96,6 107,3/96,7
• Stand-by loss at 70 °C Watt 960 960 1060 1060 1060 1500
• Standard emission rate Nitrogen oxides mg/kWh 26 29 39 38 38 41
Carbon monoxide mg/kWh 3 4 4 4 9 10
• Content of CO2in the exhaust gas maximum/minimum output %9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8
• Dimensions see table of dimensions
• Connections Flow/return DN DN80/
PN6
DN80/
PN6
DN80/
PN6
DN80/
PN6
DN80/
PN6
DN125/
PN6
Gas Inches 1“ 1“ 1½“ 1½“ 1½“ 1½“
Flue gas Ø inside mm 254 254 306 306 306 356
•Gasowpressureminimum/maximum
Natural gas E/LL mbar 18-80 18-80 18-80 18-80 18-80 18-80
Propane gas mbar 37-57 37-57 37-57 37-57 37-57 37-57
• Gas connection value at 0 °C / 1013 mbar:
Natural gas E - (Wo = 15,0 kWh/m3) Hu= 9,97 kWh/m3m3/h 23,1 28,2 37,6 47,0 56,6 65,2
Natural gas LL- (Wo = 12,4 kWh/m3) Hu= 8,57 kWh/m3m3/h 27,0 32,9 43,9 54,8 66 76,1
Propane gas (Hu= 32,7 kWh/m3) m3/h 8,9 10,9 14,5 18,1 21,9 25,2
• Operation voltage V/Hz 230/50 230/50 230/50 230/50 230/50 230/50
• Control voltage V/Hz 24/50 24/50 24/50 24/50 24/50 24/50
• Minimum/maximum electrical power consumption Watt 44/336 44/494 44/286 44/448 46/690 49/660
• Stand-by Watt 24 24 24 24 24 24
• IP rating (integral protection) IP 20 20 20 20 20 20
• Sound power level
- Heating noise (EN 15036 part 1) (room air dependent) dB(A) 72 75 69 72 75 77
- Exhaust noise is radiated from the mouth
(DIN 45635 part 47) (room air dependent/room air independent dB(A) 68 70 65 68 69 74
• Sound pressure level heating noise
(depending on installation conditions) 2dB(A) 62 65 59 62 65 67
• Condensate quantity (natural gas ) at 40/30 °C l/h 21,7 26,5 35,3 44,2 53,2 61,3
• pH value of the condensate pH ca. 4,2 ca. 4,2 ca. 4,2 ca. 4,2 ca. 4,2 ca. 4,2
• Flue gas system: requirements, values
Temperature class T120 T120 T120 T120 T120 T120
Volumeowratecombustionair Nm3/h 286 349 465 582 701 807
Fluegasmassow kg/h 383 468 624 780 940 1082
Maximumuegastemperatureatnominal
output and operation 80/60°C °C 69 71 69 70 71 69
Maximumuegastemperatureatnominal
output and operation 40/30°C °C 48 49 48 49 49 46
Feed pressure totalatthecombustionair/uegaspipe Pa 60 60 60 60 60 60
Maximumdraught/depressionatuegasoutlet Pa - 50 - 50 - 50 - 50 - 50 - 50
1 Data related to Hu. TheboilerseriesistestedforEE/H-settings.WithafactorysettingoftheWobbecoefcientof15.0kWH/m3operation at a
Wobbecoefcientof12,0upto15,7kWh/m3is possible without new settings.
2 See also notes at „Engineering“.
3 Data related to Hu. UltraGas®(250D-700D) can also be operated with propane/butane (liquid gas) mixtures.
• Boilerowresistanceseechapter3.6