WARNING!
IMPORTANT SAFETY NOTE FOR INSTALLATION
For installations using wide-voltage-range-rated switchless power distribution units (PDU part
numbers E7671-63001, E7674-63001, E7675-63001, and E7676-63001) for connection to an
uninterruptable power supply (UPS) or other AC source:
nCHECK THE VOLTAGE before connecting any equipment to the PDU! Failure to check
the voltage could lead to severe equipment damage!
The voltage of the PDU receptacles equals the voltage of the receptacle to which the PDU is
connected. This voltage must be within the input voltage range of the equipment installed
in the rack.
nCHECK THE POWER SOURCE RECEPTACLE to be sure it is installed near the rack
and is easily accessible, so that the plug on the PDU power supply cord can serve as the
disconnect device for the rack.
nCHECK THE TOTAL INPUT CURRENT ratings of the equipment installed in the rack
to avoid overloading the PDU or any uninterruptable power supply (UPS) to which it may be
connected.
The output current rating of the PDU equals the output current rating of the power source to
which the PDU is connected, but not more than the maximum current rating (amperage)
marked on the PDU.
nCHECK THE GROUNDING, because when installing rack-mounted products with this
PDU, there is a risk of high leakage current. Reliable ground circuit continuity is vital for safe
operation of this product. To reduce the risk of electric shock, earth (ground) connection is
essential before connecting the PDU. Never operate this PDU with the ground conductor
disconnected.