ICT Protege PRT-ENTR-17 User manual

PRT-ENTR-17
Protege Vandal Resistant Touchscreen Entry
Station
Installation Manual

The specifications and descriptions of products and services contained in this document were correct at the time
of printing. Integrated Control Technology Limited reserves the right to change specifications or withdraw
products without notice. No part of this document may be reproduced, photocopied, or transmitted in any form or
by any means (electronic or mechanical), for any purpose, without the express written permission of Integrated
Control Technology Limited. Designed and manufactured by Integrated Control Technology Limited, Protege® and
the Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other brand or product
names are trademarks or registered trademarks of their respective holders.
Copyright © Integrated Control Technology Limited 2003-2022. All rights reserved.
Last Published: 10-Feb-22 11:07 AM
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 2

Contents
Introduction 6
Supported Protocols 7
SIP Servers 7
Connections 8
Connection Terminals 8
Installation Wiring 8
Ethernet Connection 9
Power Requirements 10
12V DC 4A Power Supply 10
Power over Ethernet (PoE) 11
Output Connection 11
Mounting and Installation 12
Mechanical Diagram 13
Face Plate Removal 14
Surface Mounting 15
Flush Mounting 17
Postal Lock Installation 20
Postal Lock Connection 21
Hardware Configuration 22
Power On Sequence 22
Defaulting the Entry Station 22
Temporarily Defaulting the IP Address 22
Programming the Entry Station 23
Entry Station Web Interface 23
Initial Setup of the Entry Station 23
Add the SIP Account 23
Home Page 24
Call Settings 24
Volume Settings 24
Sounds 24
Device Settings 25
Network Configuration 25
Display Settings 26
Directory Sync 26
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 3

Time and Date 26
Operators 27
Changing the Admin Password 27
Creating New Operators 27
Standalone Functionality 28
Directory 28
Directory CSV Import / Export 28
Output Control 28
Configuring Output Operation 28
Programming Lock Codes 29
Viewing the Camera Feed 29
Protege GX Integration 30
Protege GX Integration Prerequisites 30
Protege GX Directory Integration 31
Configuring the Entry Station's SOAP Settings 31
Protege GX Custom Field Programming 31
Adding Protege GX Users to the Directory 32
Custom Entry Station Directories 33
Protege GX Module Integration 35
User PINOperation 35
Providing Protege GX User Access 35
Door Control 35
Elevator Control 37
Protege GX Camera Integration 40
Calling a Protege GX Workstation 41
Troubleshooting 42
Protege WX Integration 43
Protege WX Integration Prerequisites 43
Protege WX Directory Integration 44
Configuring the Entry Station's SOAP Settings 44
Adding Protege WX Users to the Directory 44
Protege WX Module Integration 45
User PINOperation 45
Providing Protege WX User Access 45
Configuring the Entry Station in Protege WX 45
Linking a Door to the Entry Station 46
Protege WX Postal Lock Configuration 47
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 4

Introduction
Tough, durable and extremely robust, the Protege Vandal Resistant Touchscreen Entry Station is the ideal solution
for creating an outstanding user experience. The 17” touchscreen entry station is designed to be the first thing
people notice as they approach the building, and their gateway for gaining access.
The entry station provides an intuitive interface for visitors to communicate with tenants, building management or
a concierge, and connects guest to off-site locations such as corporate housing owners. VoIP and video capability
enable users to view live video from multiple sources and utilize two-way voice communication to SIP compliant
phones and intercoms, providing the ability to grant entry from virtually anywhere.
Features of the entry station include:
⦁Vandal resistant and waterproof (IP65 rated) enclosure.
⦁17" touchscreen display.
⦁Built-in high resolution camera with wide viewing angle.
⦁Speaker and microphone for full duplex audio communication.
⦁Fully SIP compliant to allow communication with other Protege intercoms and third-party SIP devices
including external and mobile phones.
⦁12V DC power supply input or PoE.
⦁One programmable open collector output.
⦁Onboard postal lock input.
⦁A surface mount model designed for mounting directly onto a wall or flat surface.
⦁A flush mount model designed for mounting into a wall cavity so the front plate is flush with the wall surface.
⦁Optional flush mount rough-in box allows a cavity to be built in place for the entry station during construction.
⦁Protege GX and Protege WX integration for directory list population and extension listings.
⦁Interact with Protege integrated system controllers to allow control of doors and programmed outputs.
⦁A customizable graphics page displays a background image such as a floor plan or company branding.
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 6

Supported Protocols
The entry station supports the following protocols:
⦁SIP
⦁DHCP Client
⦁RTP
⦁Audio Encodings:
-PCMU (G.711 mu-law)
-PCMA (G.711 A-law)
SIP Servers
The entry station supports SIP servers that comply with SIP protocol standards including Asterisk and 3CX.
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 7

Connections
Connection Terminals
The entry station has two connection terminals.
⦁The ethernet connector provides network connectivity.
⦁The 9-Pin expansion connector provides a 12V DC power connection, postal lock input, and a programmable
output connection.
Ethernet Connector
9-PIN Expansion
Power Connector
Installation Wiring
The entry station is supplied with a 9-Pin expansion cable.
Red: 12VDC
Black: 0V GND
Green: Wiegand D0
White: Wiegand D1
Orange: Postal Lock
Brown: Reserved
Yellow: Reserved
Purple: Reserved
Blue: Output 1
Color Function
Red +12VDC
Black 0V GND
Green Wiegand D0
White Wiegand D1
Orange Input 1 (Postal Lock)
Brown Reserved
Blue Output 1
Yellow Reserved
Purple Reserved
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 8

Ethernet Connection
Ethernet connection allows installations to either use a dedicated Protege network (recommended for installations
with multiple entry stations), or simply connect the entry station to the building's existing network.
Entry Station
Ethernet Switch
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 9

Power Requirements
Specific power requirements must be met for the entry station to function correctly. If these are not met there is a
risk of damaging the unit or encountering performance issues.
Power requirements are listed in the Technical Specifications (see page49).
Voltage drop between the power supply and the entry station may cause the entry station to receive insufficient
voltage. If this occurs the display may be faint or flickering and the unit may reboot unexpectedly.
When designing the supply of power to the entry station, ensure that you account for the following factors which
may contribute to voltage drop:
⦁The run length (length of cable from power supply to entry station)
⦁The composition of the wire
⦁The CSA(cross-sectional area) / AWG of the cable
⦁The temperature of the cable and how the mechanical protection applied to the cable relates to the
temperature
After installation, we recommend that you measure the input voltage at the entry station to ensure that it is
sufficient for correct operation.
12V DC 4A Power Supply
Power is supplied to the entry station via a 12V DC power supply capable of supplying a minimum of 4A.
A Protege power supply module is recommended for this purpose, although any clean 12VDC 4A power supply is
suitable. When using a Protege power supply, connect V+ to the red wire and V- to the black wire of the 9-PIN
expansion cable, as illustrated below.
B+
B- L N
NAN+ N- NB
Power Supply
V1+ V-
V1+ V1+ V1+ V1+ V1+ V- V- V- V- V-
Mains Input
Red: 12VDC
Black: 0V GND
Green: Reserved
White: Reserved
Orange: Postal Lock
Brown: Reserved
Yellow: Reserved
Purple: Reserved
Blue: Output 1
Entry Station
Gel Cell Backup Battery
+
-
If using a Protege power supply module, a battery backup must be connected to the module network to provide a
monitored supply. The battery plays an important role in power conditioning and provides a continuous source of
power in the event of a power outage.
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 10

Power over Ethernet (PoE)
This must ONLY be installed with the supplied PoE injector (POE61W-560DG) and PoE splitter (POE45-120-R).
Mains Input
Entry Station
IN OUT
Ethernet Switch PoE Injector PoE Splitter
IN OUT
Red:12VDC
Black:0V GND
White:Positive
Black:Negative
Ethernet Connection
⦁Connect the Ethernet Switch to the IN port of the PoE injector.
⦁Connect the OUT port of the PoE injector to the IN port of the PoE splitter.
⦁Connect the OUTport of the PoE splitter to the RJ45 Ethernet connector on the back of the entry station.
9-PIN Expansion Power Connection
⦁Connect the white (positive)wire from the PoEsplitter to the red (12V DC) wire of the expansion cable.
⦁Connect the black (negative)wire from the PoEsplitter to the black (0V GND) wire of the expansion cable.
⦁Connect the expansion cable to the 9-Pin expansion connector on the back of the entry station.
Output Connection
The entry station has one onboard programmable open collector output suitable for digital relay control. It should
be connected as indicated in the diagram below:
1K5 OHM
LED
+12V AUX
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 11

Mounting and Installation
Before mounting, ensure that the screen of the entry station is in a position where it is not exposed to direct
sunlight. Correct positioning is essential to prevent the display from overheating. If it is not possible to install the
entry station facing the required direction, a sun cover must be used to reduce potential operating issues.
The below diagrams illustrate the ideal orientations for both the northern and southern hemispheres, and identify
the mounting positions that will require a sun cover.
N
S
E
W
Erehwon Apartment Directory
Touchanywhere to begin
S
N
E
W
No sun cover required
Display is not likely
to overheat
Requires sun cover to
prevent overheating
Northern Hemisphere
Southern Hemisphere
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 12

Mechanical Diagram
Camera
Speakers and Microphone
Touch
screen
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 13

Face Plate Removal
You must first remove the front face plate from the entry station to access the back plate for mounting.
To remove the front face plate, carefully insert both of the provided tools through the outer speaker holes and
push them all the way in to release the front section, then lift the cover out from the bottom.
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 14

Surface Mounting
The below diagrams indicate the dimensions of the surface mount enclosure and back plate, for use when
mounting the entry station directly onto a wall or flat surface.
Surface Mount Enclosure
424.49mm / 16.7”
438.71mm / 17.27”
338.92mm / 13.34”
271mm / 10.66”
67.36mm / 2.65”
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 15

Surface Mount Back Plate
420mm / 16.5”
353mm / 13.89”
112mm / 4.4”
102mm / 4”
19mm /
0.74”
30mm /
1.18”
54mm /
2.14”
70mm / 2.75”
180mm / 7”
155mm / 5.9”
24mm /
0.94”
240mm / 9.44”59mm /
2.3”
280mm / 11”
180mm / 7”
30mm /
1.18”
70mm / 2.75”
155mm / 5.9”
154mm / 6.06”
85mm /
3.34”
8mm / 0.3”
Cable Entry Point
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 16

Flush Mounting
The below diagrams indicate the dimensions of the flush mount enclosure and back box, for use when mounting
the entry station into a wall cavity so that the front plate is flush with the wall.
Flush Mount Enclosure
498mm / 19.6”
508mm / 20”
38.5mm /
1.51”
338.92mm / 13.34”
271mm / 10.66”
35.25mm /
1.38”
74.50mm / 2.9”
440mm / 17.3”
440mm / 17.3”
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 17

Flush Mount Back Box
370mm / 14.57”
424mm / 16.7”
440mm / 17.3”
159mm / 6.25”
90mm / 3.5”
100mm / 3.9”
61mm /
2.4”
27mm /
1.06”
6.5mm / 0.25”
162mm / 6.37”
159mm / 6.25”
159mm / 6.25”
61mm /
2.4”
Cable Entry Point
498mm / 19.6”
508mm / 20”
38.5mm /
1.51”
35.25mm /
1.38”
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 18

Flush Mount Rough-In Box
The below diagrams indicate the dimensions of the optional flush mount rough-in box, available for use when
building a cavity in place for the entry station during construction.
454.00
432.00
98.00
98.00
163.84
31.82
68.36317.3168.33
31.99
31.82
31.99
68.36317.3168.33
73.50
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 19

Postal Lock Installation
The supplied postal lock brackets enable you to fit compatible postal locks, as indicated by the diagram below.
u
v
1. USPS Master Locks
2. USPS Mailbox Locks
PRT-ENTR-17 | Protege Vandal Resistant Touchscreen Entry Station | Installation Manual 20