Incon TS-STS User manual

TS-STS Sump Test System
Quick Start Guide
TS-STS Overview
The TS-STS system includes a TS-STS console within a convenient
portable case, leak testing probes with 50 feet of cable, and probe
hanging hardware (slip rings and chain).
After all fittings within the sump are sealed, the sump is filled with a
water-based test solution that covers all sump penetration holes. The
probe is installed so the float is floating on the surface of the test solution.
The TS-STS console is quickly programmed with the site name and
address, number of sumps, the 7-digit code-names for each sump, and
the correct Time/Day/Date before leak testing.
Pressing the Testkey at the console keypad starts sump leak tests for
all sumps. The test time is 15 minutes and tests for a level change
greater than 0.002 inches.If the level of a sump drops more than the
leak limit during the test, the Sump Leak Test Report will show a fail
result when the test is finished. Leak tests can also be programmed
(scheduled) to start at desired times.
When finished, leak test reports will automatically print out at the console
printer. Extra copies of this report can be printed using the report key. A
newly completed Sump Leak Test will overwrite the previous results
stored in memory. Save sump leak test reports and provide copies as
evidence of compliance with regulations.
Recommendation: Use a computer and the Tech version of
System Sentinel™ to record site data, sump code-names, and test
results. Test results can also be extracted from Comm Port 1 at
the bottom of the TS-STS console (also see Section 4).
Reference Federal and State regulations for leak limit and test
time requirements. Recommendations for locating the
TS-STS
console outside of the (Class
I
, Division 1, Group D) Hazardous Areas
during testing, are based on NFPA 30, NFPA 30A and NFPA 70 (NEC).
TS-STS Sump Test System
Quick Start Guide
INCON P/N 000-3004 Rev.D Feb. 2009 ©www .fraklinfueling.com
This document may change without prior notice. INCON®is a Registered Trademark of Franklin Fueling Systems
TS-STS Installation
1
Pg 1
NOTE
1.) Required Materials:
a.) Tape to secure the probe cable b.) Safety cones & signs
c.)Grounded, 3-pronged extension cord
d.)Flat pieces of metal to suspend leak testing probe over sumps
2.) Work safely — install Safety Cones and Signs at the site
3.)The probes are precision instruments — handle with care!
4.)The STS probes are shipped with cables attached, do not remove
the cable from the probe end... remove at the console case only.
5.)Inspect probes for proper float movement before use, then install
probes as shown in Section 1
6.)Connect the yellow probe cables to the receptacles at the TS-STS
case.
Make sure to line up keyways before inserting cable and
tightening the screw-on connector.
7.)Locate the TS-STS case outside of the Hazardous Area and tape
the cable down to prevent probe movement during the test and to
reduce tripping hazards
8.)Setup / Program the TS-STS console per Section 2
9.)Start sump leak test(s) on sumps that are ready
10.)Always clean, dry, and store probes in the probe carrying case after
each use
11.) Test each of the probes on a monthly basis to ensure its ability to
detect leaks. Install the probe in a test container and initiate a test.
After 5 minutes, remove about 0.12 inches of water. When the test
completes, the test report should show a Failed result if the probe
is working properly.

Figure 1.1 Typical Leak Detection Probe – Dispenser Sump Installation
Overview Figure 1.2 Leak Detection Probe Installation
Dispenser Sump
TS-STS
SUMP TEST SYSTEM
BUILDING
SUMP TEST SYSTEM
TS-STS
1
4
SUMP
3
2
20 Feet - Min. Distance
Per NFPA 30A
DISPENSER
1 / 2 DISPENSER
3 / 4
INCON RECOMMENDS
TESTING DISPENSOR
SUMPS IN GROUPS
SO OTHER DISPENSORS
ARE LEFT IN SERVICE
DURING TESTING
GROUNDED
3 PRONG
EXTENSION
CORD REQ'D
SAFETY
CONES
DISPENSER
7 / 8
DISPENSER
5 / 6
Pg 2
SPLIT RING
TS-STS
SUMP TEST SYSTEM
SUMP TEST SYSTEM
FLAT METAL
/ ANGLE IRON
REQUIRED
TO SUSPEND
PROBE
(
SIDE VIEW
)
TS-STS
STS-PRB-12
LEAK TESTING
PROBE WITH:
TSP-SSP
STAINLESS
STEEL FLOAT
DISPENSER SUMP
WITH TEST SOLUTION
(Side View)
RECEPTACLES
FOR FOUR
SCREW-IN, PROBE
CABLE PLUGS
3
2
1
POWER CORD
WITH A GROUNDED
3-PRONGED
PLUG
4
SUMP

Figure 1.3 Typical Leak Detection Probe – Turbine Sump Installation
Overview Figure 1.4 Leak Detection Probe Installation
Turbine Sump
—❖—
Pg 3
STP
SPLIT RING
TS-STS
SUMP TEST SYSTEM
SUMP TEST SYSTEM
FLAT METAL
/ ANGLE IRON
REQUIRED
TO SUSPEND
PROBE
(
SIDE VIEW
)
TS-STS
STS-PRB-12
LEAK TESTING
PROBE WITH:
TSP-SSP
STAINLESS
STEEL FLOAT
TURBINE SUMP
WITH TEST SOLUTION
(
Side View
)
POWER CORD
WITH A GROUNDED
3-PRONGED
PLUG
3
RECEPTACLES
FOR FOUR
SCREW-IN, PROBE
CABLE PLUGS
1
2
4
SUMP
TAPE / WEIGHT DOWN
CABLE TO PREVENT
ACCIDENTAL
MOVEMENT DURING
LEAK TESTING
(PROBE CABLE
PN: 600-0200
= 50 FEET)
Turbine
Sump
2
TS-STS
SUMP TEST SYSTEM
GROUNDED
3 PRONG
EXTENSION
CORD REQ'D
SAFETY
CONES
BUILDING
SUMP TEST SYSTEM
TS-STS
1
4
SUMP
3
2
Tank Pad
Turbine
Sump
1
10 Feet - Min. Distance
Per NFPA 30A
Turbine
Sump
3

Setup - Program the Console
2
SELECT MENU OPTION
SETUP
SETUP MENU (MORE)
EXIT SYSTEM SUMPS CLK/CAL
HU
MENU
Press the
MENU
key and follow
7the highlighted sequence below
to view the Setup Menus
SETUP MENU (MORE)
EXIT SYSTEM SUMPS CLK/CAL
SETUP MENU (MORE)
EXIT SYSTEM SUMPS CLK/CAL
SETUP MENU (MORE)
COM PORTS
Press the Down key ▼ to see next display
Display
Menu Select Keys
(M1 – M4)
Keypad:
(Multi-Function,
Alphanumeric)
ACK SHIFT key
Report Printer
(thermal printer)
NaNa
NaNa
Navigatingvigating
vigatingvigating
vigating
Menus:Menus:
Menus:Menus:
Menus:
•Push the
UP/DOWN
keys ▲
▼to show
other menus or other
choices
•Use menu keys
(M1
to
M4)
to access menus
or to help edit text
•Press the
ENTER
key
to make a setup choice
or to move down in the
menu
tree
•Press the
CANCEL
key to cancel before
entry or to move up
and out of the menu
tree
Editing Text:
•Press the
M1
key to move the cursor to the left
•Use
M2
to move the cursor to the right
•Use
M4
to backspace & delete text to the left of the cursor
Follow the highlighted sequence at left to program the
console.
Menus are in indented format (lower levels to the right).
The setup program factory default settings are shown
in ITALIC TEXT. The console will auto-exit the setup
mode if no key is pressed after 3 minutes.
Minimum Setup Requirements
1) From SETUP>SYSTEM (SYSTEM INFO), program the
System ID data and the No. (number of) Sumps
2) SETUP>SUMPS>DATA>SUMP N>NAME>Sump Name (code-
name for each containment sump that will be leak tested)
3) SETUP>CLK/CAL>Set Time (input the correct time), Set Date
(input the correct date), Set Day (choose the day of the week)
ACK
SHIFT
ab
KEY
#
12
3
Input
Alphanumeric
Text
(in setup mode):
Press the
ACK
SHIFT
key at the keypad
1, or 2, or 3 times to
cycle between the
unique key characters
(at positions 1, 2, and 3).
Select and press a key
to input the desired
alphanumeric character.
M1
LEFT
M2
RIGHT
M3 M4
M1
LEFT
M2
RIGHT
M3 M4
M1
LEFT
M2
RIGHT
M3 M4
M1
LEFT
M2
RIGHT
M3 M4
M1
LEFT
M2
RIGHT
M3 M4
NOTES
Pg 4

Setup>System menu Continued...
COLD BOOT (Replaces all custom-setup data with default values)
IF YOU CONTINUE, ALL SYSTEM PROGRAMMING
AND DATA WILL BE LOST...
:
PRESS ENTER IF YOU ARE SURE THAT
YOU WANT TO CONTINUE WITH COLD BOOT
Setup>Sumps menu
SUMPS
DATA
N = Sump number
SUMP DATA
SUMP 1
Select sump and program new name
SUMP
2
:
SUMP
4
SUMP DATA N
NAME (Rename the sump using a
SUMP NAME N Code-Name for each Sump)
SUMP N code-names can be up to 7
alphanumeric characters long
(e.g. ULD SMP, SUP SMP, DSP 1-2)
Setup Menu
EXIT SYSTEM SUMPS CLK/CAL COM PORTS
Setup>System menu
SYSTEM INFO
SYSTEM ID (customize the Site ID information)
LINE 1
LOCATION LINE 1 (input 24 characters Max)
INCON Enter the Business Name
LINE 2
LOCATION LINE 2 (input 24 characters Max)
INTELLIGENT CONTROLS INC Enter other Business data
LINE 3
LOCATION LINE 3 (input 24 characters Max)
P.O. BOX 638 Enter the Street Address
LINE 4
LOCATION LINE 4 (input 24 characters Max)
SACO ME 04072 Enter the City and Zip code
LINE 5
LOCATION LINE 5 (input 24 characters Max)
1-800-984-6266 Enter the Business Number
NO. SUMPS (enter total number of sumps [4 max.])
NUMBER OF SUMPS
1
SUMPTST (sump leak test, start time + leak limit)
START TIME (Do not set when tests are started from the front panel)
SUMP TEST START TIME Tests are 15 minutes in length
00.28.00
(12:28 am in 24 hour format)
Input
time in 24 hour format...
Add 12 to pm times from 1 to 11:59 pm
LEAK LIM
LEAK LIMIT
0.002
(There is a fixed threshold of .002 level units.)
NOTE: The Leak Limit Threshold of 0.002 is not
an adjustable setting.This is a fixed value.
Pg 5

Leak Testing /
Console Operation
Setup>Clk/Cal menu
CLOCK/CALENDAR
DAY SAV
DAYLITE SAVINGS
ENABLED Enable
= allows daylight savings time changes
DISABLED Disable = does not
TM STYLE Select the time style for displays & reports
TIME STYLE
12 HOUR
24 HOUR
DT STYLE Select the time style for displays & reports
DATE STYLE
MM/DD/YY
DD/MM/YY
YY/MM/DD (YY = Year, MM = Month, DD = Day)
SETTIME Input current time in 24 hour format
SET SYSTEM TIME Two digits are required, use leading
HH:MM:SS
zeros before single digits
(e.g. input 05 not 5)
Add 12 to p.m. times
from 1 to 11:59 p.m.
SET DATE Input current DATE
SET SYSTEM DATE
YYYY:MM:DD
(YYYY = year, MM = Month, DD = Day)...
2 digits are required for month and day –
use leading zeros before single digits
(e.g.. input 04 not 4)
SET DAY
SET SYSTEM DAY OF WEEK Select the current day
SUNDAY
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
—❖—
3
SYSTEM SUMP
OKAY OKAY
SYSTEM SUMP
WARNING OKAY
SYSTEM SUMP
NO PAPER OKAY
SYSTEM SUMP
OKAY OKAY
SYSTEM SUMP
OKAY TEST
LEVEL SUMP 1 SUMP 2 SUMP 3 SUMP 4
INCHES 2.01 3.09 1.76 3.12
SELECTFUNCTION 10:39:08 AM 10-29-2001
DISPLAY PRINTER
SYSTEM SUMP
OKAY LEAK
Displays:
1.) Normal Display
2.) Press the Check key
to check the time and
date.
3.) The System –
Warning message
alternates with the
No Paper (if out).
Replace printer
paper before starting
sump leak tests.
4.) Press the Level key
to check the test fluid
level in sumps (sumps
can’t be leak tested if
empty).
5.) Press the Test key at
the keypad & and the
menu select key
(M1 M2
or
M3)
and
follow instructions to:
• Show the Status of
tests including Start
time / date
• Start tests, and to
• Abort leak test(s)...
Okay & Testing are
alternately displayed
when a sump leak
test is running.
SELECT LEAK TEST OPTION
STATUS START ABORT
M1
LEFT
M2
RIGHT
M3 M4
Pg 6

Leak Testing /
Console Operation Continued...
ACK
SHIFT
SELECT SUMP REPORT
TEST LEVEL
M1
LEFT
M2
RIGHT
M3 M4
JW
REPORT
9
SELECT SUMP
SUMP 1 SUMP 2 SUMP 3 ALL
M1
LEFT
M2
RIGHT
M3 M4
SELECT ALARM TYPE
SYSTEM SUMP ALL
M1
LEFT
M2
RIGHT
M3 M4
SELECT (SYSTEM / SUMP) ALARM STATUS
ACTIVE CLEARED HISTORY
M1
LEFT
M2
RIGHT
M3 M4
6.) To view an alarm/warning, press the M1 or M2 Key under the
word Alarm / Warning. While viewing the alarm, press the
ACK
SHIFT key at the keypad to acknowledge.
Cleared and
transient alarms should be acknowledged prior to starting
another test.
7.) Press the Report key at the keypad to show various report
choices.
—❖—
Reports
4
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001 12:15 PM
SUMP LEAK TEST REPORT
SUMP 2
TEST STARTED 12:00 PM
TEST STARTED 10/31/01
BEGIN LEVEL 7.0230 IN
END TIME 12:15 PM
END DATE 10/31/01
END LEVEL 7.0209 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT: FAILED
Reports can printout automatically or on
demand from the keypad. The
Sump Leak Test and Alarm
Reports print automatically.
The other reports, such as
the Sump Level Reports,
Alarm Reports, and Sump
Test Reports can be printed
on demand.
Press the menu select keys
and choose the type of report
that you wish to printout.
Alarm reports will print as
soon as an alarm is detected.
Leak test reports print
automatically after the leak test is finished.
Note that
when a new leak test is complete the data will
overwrite a previous result.
Of the three reports shown here, one is a Level
Summary report and two are Sump Leak Test
Reports.
Up to 4 sumps can be leak-tested at the same
time.
REPORTS continued...
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001 12:15 PM
SUMP LEAK TEST REPORT
SUMP 1
TEST STARTED 12:00 PM
TEST STARTED 10/31/01
BEGIN LEVEL 2.0120 IN
END TIME 12:15 PM
END DATE 10/31/01
END LEVEL 2.0120 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT: PASSED
INCON
INTELLIGENT CONTROLS INC.
P.O.. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001 11:58 AM
SUMP LEVEL REPORT
SUMP 1
2.012 IN
SUMP 2 7.201 IN
SUMP 3 3.218 IN
SELECT REPORT
SUMP ALARM
M3 M4
M2
RIGHT
M1
LEFT
Pg 7
1.
2.
3.

INCON P/N 000-3004 Rev.D Feb.2009 © Franklin Fueling Systems www .franklinfueling.com
This document may change without prior notice.
INCON
®
is a Registered Trademark of Franklin Fueling Systems
A digital copy of the Sump Test Report can be retrieved from the TS-STS
console through the communications port (Comm Port 1). This port is
located at the bottom side.
As with the printed reports, this data is overwritten when a new test is
run, so it must be collected after each test. The data can be stored in a
database as opposed to saving the printouts.
For more information on this feature contact INCON Technical Service at
1-800-984-6266.
——
Reports Continued...
4
Pg 8