
KW x 1000KW x 1000Three phaseThree phase
Line currentLine current 1.732 x Line Voltage1.732 x Line Voltage
3
For wiring recommendations refer to the wiring diagram. An
additional copy is provided inside the heater terminal box.
For wiring recommendations refer to the wiring diagram. An
additional copy is provided inside the heater terminal box.
WARNING
Retighten all electrical connections that may have
loosened during shipment. Failure to do so may result
in damage to the heater or risk of fire.
Wiring to the heater should be permanently installed in
metallic or non-metallic electrical grade conduit in accordance
with all applicable electrical codes, and should include a
grounding conductor if non-metallic conduit is used.
Wiring to the heater should be permanently installed in
metallic or non-metallic electrical grade conduit in accordance
with all applicable electrical codes, and should include a
grounding conductor if non-metallic conduit is used.
Confirm all unused conduit holes in the terminal box are
sealed with plugs suitable for the heater environment.
Confirm all unused conduit holes in the terminal box are
sealed with plugs suitable for the heater environment.
Attach a ground conductor to the mounting screw for the
heater in the terminal box, or by other appropriate means, per
NEC Article 250.
Attach a ground conductor to the mounting screw for the
heater in the terminal box, or by other appropriate means, per
NEC Article 250.
Field supply wiring must be rated for 600Vac. Use copper
conductors.
Field supply wiring must be rated for 600Vac. Use copper
conductors.
Be sure the terminal box cover is properly installed at all
times to ensure personnel protection. Also, contaminants can
create leakage, (shock) hazards, permanent heater damage
or failure and should be avoided.
Be sure the terminal box cover is properly installed at all
times to ensure personnel protection. Also, contaminants can
create leakage, (shock) hazards, permanent heater damage
or failure and should be avoided.
The electrical installation should include a service disconnect
switch in sight of the heater, as well as branch circuit over-
current protection and over-temperature protection, if not
provided with the heater.
The electrical installation should include a service disconnect
switch in sight of the heater, as well as branch circuit over-
current protection and over-temperature protection, if not
provided with the heater.
It is recommended to perform an insulation resistance test
prior to energizing the equipment. If the value is less than 1
Meg Ohm using a 500Vdc or similar tester, refer to
Maintenance and Troubleshooting sections.
It is recommended to perform an insulation resistance test
prior to energizing the equipment. If the value is less than 1
Meg Ohm using a 500Vdc or similar tester, refer to
Maintenance and Troubleshooting sections.
Where thermocouple extension wire is required between the
heater and remote controls, verify it is connected with proper
polarity, as shown on the wiring diagram. Failure to do so
may result in an uncontrolled heater. Refer to the wiring
diagram for the required wire type. Shielded wire is
recommended to reduce signal interference.
Where thermocouple extension wire is required between the
heater and remote controls, verify it is connected with proper
polarity, as shown on the wiring diagram. Failure to do so
may result in an uncontrolled heater. Refer to the wiring
diagram for the required wire type. Shielded wire is
recommended to reduce signal interference.
OPERATIONOPERATION
Cautions and SetupCautions and Setup Pipe
Material Maximum
Pipe Temperature
Steel 750°F
Stainless Steel 304 1400°F
CAUTION
Equipment should be operated by qualified personnel
only to prevent equipment damage or failure.
Ensure power ahead of the panel is off and perform the
following steps:
WARNING
DO NOT TURN ON HEATING ELEMENTS UNTIL
TANK IS COMPLETELY FULL OF FLUID.
Permanent damage may result if elements are
energized and the heater is not completely
submerged.
1. Exercise all switches, circuit breakers and operating
mechanisms to confirm they operate freely.
2. Conduct an insulation resistance to ensure the system is
free from short circuits or grounds.
INDEECO recommends that all safety interlocks be tested
during initial startup to ensure they properly disable the
heater. After 10 days of operation, retighten all electrical
connections.
Carefully review all instructions and become familiar with the
equipment, safety interlocks, and process temperature
controller provided before energizing the equipment.
For solid state non-indicating controllers, it is recommended
to dial the high limit controller set-point down to a point below
normal operating temperature, either during initial startup
operation or with only the control circuit on, and verify that the
contactors open, disconnecting heater power. Return the
controller to the desired setpoint.
DO NOT operate heaters at voltages in excess of that
marked on the heater. Excess voltage can shorten heater life
or overload the branch circuit wiring.
DO NOT operate heaters unless properly filled with liquid.
DO NOT leave heating systems operating unattended unless
a closed-loop process controller and over-temperature safety
equipment have been completely validated.
PID controlled systems must be auto-tuned after initial
installation to optimize control accuracy.
Refer to information noted below on Control Methods.
DO NOT operate heaters at pipe temperatures higher than
the recommended maximum. Excess temperatures can
cause premature failure. Generally, pipe materials are limited
to the following maximum temperatures.
During initial heating, it is recommended to slowly ramp up
the process setpoint and inspect the heating system for
problems such as excess pressure buildup, or binding of
equipment due to thermal expansion.