Infinite Transtector 700 AV/T-S Series User manual

Series 700 AV/T-S Power Conditioner
160K(i) Power Conditioner with
Voltage Regulation (60 Hz)
Owners Manual
Quad Output Power Conditioner for Novalis
TX with ExacTRAC and OBI Options
160K(i) 60 Hz Model Front Access Design
Important safety instructions - save these instructions and review prior to using equipment
▪112084-BRL2 Rev 5

160K(i) 60 Hz Power Conditioner | Owners Manual 2
TABLE OF CONTENTS
Receiving and Inspecting the Unit 3
General Description 4
Safety Precautions 5
Preliminary Installation 6-7
Weights, BTU and Dimensions 7
Input Wire Size, Grounding and Output Wiring 8-9
Installation 10-13
Bypass Switch 14
Start - up and Operation 15
Preventive Maintenance 16
Performance Checklist 17
General Troubleshooting 18
Parts List 19
Warranty 20
APPENDIX A 21
Cabinet Layout 22-24
Seismic Calculations 25
Symbol Library 26
Notes 27

3
1402-001
RECEIVING & INSPECTING THE UNIT
INSPECTING THE POWER PROCESSOR
Upon receipt of the unit, visually inspect for shipping damage. If any damage is found, the Purchaser
must contact the Carrier immediately and le a shipping damage claim.
NOTE: Be sure to remove the front and side panels, and inspect the inside of the unit for shipping damage.
If any internal damage has occurred or any external damage that could affect the operation of the unit,
please contact Transtector.
FOR ASSISTANCE CALL 1-800-882-9110 X 6112 (8am-5pm Pacic Time)
AFTER HOURS CALL 1-800-521-4792
STORING
If it is necessary to store the unit for a period of time before it is installed, be sure to place the unit in a
clean, dry area. To prevent excessive dust from accumulating on the unit, it is advisable to protect it by
replacing it in the original container (if possible). If the original container is not available it is recommended
that all openings that lead internally into the unit are covered so that dust, water or any other substance
cannot enter the internal components of the system. The unit must be handled at all times with the same
care you would give to any piece of precision industrial equipment.
REMOVING THE POWER PROCESSOR FROM PALLET
Please take special care when removing the unit from the pallet. Proper equipment must be used for
lifting and moving, and all safety precautions should be taken. Each unit is bolted to a wooden pallet.
In order to properly remove the cabinet from the pallet, all bolts connecting the unit to the pallet must be
removed completely. The unit can then be lifted off the skid using a pallet jack or a fork lift, as shown
below. When lifting the unit off of the pallet, be sure to take proper safety precautions. Serious injury and/
or unit damage can result otherwise.

160K(i) 60 Hz Power Conditioner | Owners Manual 4
GENERAL DESCRIPTION
The Series 700AV/T-S Power Processor is designed to supply reliable, clean regulated power to critical
loads. An efcient design with state of the art micro-processor controlled solid state devices provide
immunity to all line disturbances.
The basic design consists of a three phase triple shielded isolation transformer with seven separate voltage
taps per phase. Output regulation is achieved by monitoring the input and automatically switching taps
anytime the input line sags or surges. The use of a triple shielded isolation transformer provides superior
common mode and transverse mode noise attenuation. Automatic switching occurs during current zero
allowing noise free switches for both leading and lagging power factor loads that are connected to the
Series 700AV/T-S.
MONITOR
Monitoring of the Series 700AV/T-S is simple, clean and effective. Three green light indicators are utilized
to display “POWER ON”. These indicator lights are connected directly to the output (line to neutral for each
phase) and indicate that the Series 700AV/T-S is operating properly with just a quick glance.
The Series 700AV/T-S is also provided with “INPUT OUT OF RANGE” red indicating LEDs for each phase.
If any phase of the input voltage source exceeds the specied +10%, -15% from nominal, the appropriate
phase LED is illuminated.
In addition, a red “ALERT” light is provided as an over temperature indicator. If an over temperature
condition exists, the “ALERT” light will illuminate and shut down the output. Over temperature thermal
sensors are strategically located at critical points on the regulator assemblies and transformer. The main
AC input circuit breaker must be turned off in order to reset the “ALERT” light.
OUTPUT VOLTAGE METERS
Two (2) digital output meters are provided. One monitors the 208/120 VAC output and the other monitors
the 480/277 VAC output. Each meter monitors and displays Line-to-Line and Line-to-Neutral voltages.
Minimum and maximum voltage values are recorded in EPROM. High and low output voltage limit alarms
are programmable and a visual indication given if limits are exceeded.
PROTECTION
Protection is accomplished very effectively to minimize failures and the cost of repairs. A total of ve major
devices protect the Series 700AV/T-S.
1. The input is protected with an integrally mounted AC circuit breaker for abnormal current overloads
and provides a convenient means of disconnecting utility power.
2. The main transformer is protected by fuse links connecting the SCR regulators together, and are
designed to clear in the event that two or more SCR’s should fail. This will prevent a transformer tap
short and the possibility of transformer failure.
3. Overtemp sensing devices are mounted at critical points on the SCR regulating assembly and the
main transformer. When an overtemp condition exists the “ALERT” light will illuminate and hold until
the overtemp is corrected. There are no automatic shut-off circuits for the “ALERT” condition. The
main AC input breaker must be turned off in order to reset the “ALERT” light.
4. Each output of the Series 700AV/T-S is protected with an integrally mounted AC breaker for abnormal
current overloads and provides a convenient means of disconnecting power from the load.

5
1402-001
**** WARNING ****
THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE
ENCLOSURE OF THE POWER SUPPLY SYSTEM.
CAUTION MUST BE TAKEN WHEN WORKING WITH THE SYSTEM.
IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY QUALIFIED
ELECTRICAL PERSONNEL ONLY.
SAFETY PRECAUTIONS
**** CAUTION ****
RISK OF ELECTRICAL SHOCK AND HIGH SHORT CIRCUIT CURRENT.
THE FOLLOWING PRECAUTIONS SHOULD BE OBSERVED
WHEN WORKING ON THE UNIT:
1) REmOvE wATChES, RINgS, OR OThER mETAL ObjECTS.
2) USE TOOLS wITh INSULATEd hANdLES.
3) wEAR RUbbER gLOvES ANd bOOTS.
**** CAUTION ****
- FOLLOW ALL STANDARD AND LOCAL ELECTRICAL CODES.
- dO NOT ALLOw wATER OR FOREIgN ObjECTS TO gET INSIdE ThE UNIT.
- dO NOT PLACE ObjECTS OR LIqUIdS ON TOP OF ThE UNIT.
- DO NOT LOCATE THE UNIT NEAR RUNNING WATER.

160K(i) 60 Hz Power Conditioner | Owners Manual 6
PRELIMINARY INSTALLATION
INSTALLATION CONSIDERATIONS
Prior to installing the Series 700AV/T-S, be sure to take into consideration the site you have selected.
Power Conditioners produce heat and therefore require ventilation as well as accessibility. Consider
these factors.
CHOICE OF LOCATION
These units are intended for installation in a temperature-controlled, indoor area free of conductive
contaminants.
The unit has been completely inspected and extensively tested under various load conditions prior to
shipment. Care to install it at a proper location will assure long trouble-free operation.
The unit is air cooled with the air intake at the front and exhausts at the top. Therefore, it should be installed
in a clean, dry place with enough clearance to allow a free ow of air. Allow a minimum of 36” in front of
the 700AV/T-S for installation, operation, and maintenance. There is no clearance required on either the
left or right hand side of this enclosure. Either or both sides, as well as the rear of the enclosure, can be
set ush up against a wall. Input and output conductors should then enter/exit via the top and/or bottom
of the enclosure as indicated.
▪Ventilation ▪Input Source Voltage
▪Size of the Power Conditioner ▪Receiving Facilities
▪Weight Load ▪Distribution of Power
▪Audible Noise Requirements ▪Room Temperature
▪Remote Emergency Power Off (Repo) ▪Clearances
▪Monitors ▪Accessibility
▪Options ▪Excessively Long Power Runs
▪Clean Environment ▪Proper Ground Techniques
NO CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
36" CLEARANCE REQUIRED IN FRONT
TOP VIEW
FRONT

7
1402-001
OUTPUT KVA
CONTINUOUS
INPUT
BREAKER SIZE
OUTPUT BREAKER SIZE MAX OUTPUT CURRENT
75 kVA 300A @ 208V
250A @ 240V
150A @ 480V
100A @ 600V
150A, 3P @ 208V Accelerator
70A, 3P @ 480V BL Generator
60A, 3P @ 480V OBI
30A, 1P @ 120V BL Computers
208/120V 125A Accelerator
480/277V 70A BL Generator
480/277V 55A OBI
120V 25A BL Computers
WEIGHTS, BTU AND DIMENSIONS
OUTPUT KVA WEIGHT OPERATIONAL
BTU/HR
TYPICAL
MAXIMUM
BTU/HR
DIMENSIONS
75 kVA 2,194 lbs
995.18 kg
5,115* 10,230 34.5” w x 35.875” d x 76” h
87.63 cm x 91.12 cm x 193.04 cm
* Stated BTU’s / Hr is at 75kVA rated load, 100% duty cycle. Operational BTU’s / Hr is typically at
50% of rated load. Input over current protection provided by others.
**** CAUTION ****
INPUT AND OUTPUT BREAKER SIZE

160K(i) 60 Hz Power Conditioner | Owners Manual 8
NOTE: Refer to the latest edition of The National Electric Code Requirements for over-current protection
and wire sizing.
INPUT WIRE SIZE, GROUNDING AND OUTPUT WIRING
A. Conduit should be used for both input and output wiring.
B. Input wire size is based on the NEC table 310.16. Specifying not more than 3 connections in a raceway
based on an ambient of 30°C and wire rated for 90°C (Note: amperages will need to be adjusted for
40° C ambient applications).
C. Input phase conductors are terminated directly to the input circuit breaker terminals.
Wire range:
208 VAC 300 Amp breaker #1 AWG to #600 KCMIL
240 VAC 250 Amp breaker #3/0 AWG to #350 KCMIL
480 VAC 150 Amp breaker #14 AWG to #3/0 AWG
600 VAC 100 Amp breaker #14 AWG to #3/0 AWG
D. Input ground lug TA-250, max wire range 6 AWG - 250 MCM one piece.
E. Output is a 4 wire (5 including ground). If four (4) current carrying conductors are used in a raceway
the neutral is assumed to be current carrying and the wire must be de-rated as indicated in table 310.6
on the NEC.
Example: 1. Assume #10 wire max current = 25 Amps.
2. Multiply 25 x .8 = 20
3. 20 Amps is max current for #10 wire in a raceway with 4 conductors.
NOTE: Installation is subject to local codes - verify with a local electrical inspector.
F. All output ground and neutral terminals are copper bus bars w/ two holes. Double bolted lug are
recommended. Manufactured by Burndy
RECOMMENDED LUGS: Double bolted type as supplied by Burndy Copper Compression lug, 2 hole
Type YA, ¼” stud, ¾” spacing.
YA6CL-2TC14E2 #6 wire YA4CL-2TC14E2 #4 wire YA2CL-2TC14E2 #2 wire
YA1CL-2TC14E2 #1 wire YA25L-2TC14E2 #1/0 wire YA26L-2TC14E2 #2/0 wire
YA27L-2TC14E2 #3/0 wire YA28L-2TC14E2 #4/0 wire X 2
Output connections are made directly to the output breaker(s) and output neutral and ground lugs
provided. The load current is not to exceed 80% of the output breaker(s) rating, and not to exceed
the rated total current.

9
1402-001
F. Continued
Output wiring sizes:
208/120 VAC 150 Amp breaker #14 AWG to #3/0 AWG
480/277 VAC 70 Amp breaker #14 AWG to #3/0 AWG
480/277 VAC 60 Amp breaker #14 AWG to #3/0 AWG
120 VAC 30 Amp breaker #14 AWG to #2 AWG
G. Output neutral to ground bonded during manufacturing of the power conditioner. Output Neutral is
already grounded by the factory.
H. Installation is subject to local codes. Verify with a local electrician inspector.
common

160K(i) 60 Hz Power Conditioner | Owners Manual 10
INSTALLATION
CABINET OUTLINE - FRONT VIEW
BOTTOM VIEW
76.000
3.000
AIR INLET
FRONT VIEW
Ø.562 x 1.000
34.500
OUTPUT CONDITIONED POWER
INPUTOUT OF RANGE
ALERT
CBA

11
1402-001
INSTALLATION (continued)
CABINET OUTLINE - TOP AND BOTTOM VIEW
8.000
(4)Ø.875 KNOCK-OUTS
TERMINATION ACCESS AREA
TOP INPUT/OUTPUT
OUTPUT FILTER, OUTPUT TERMINATIONS
AND CURRENT TRANSFORMERS.
REMOVABLE TOP PANEL PROVIDES
ACCESS TO TRANSFORMER,
TERMINATION ACCESS AREA
BOTTOM INPUT/OUTPUT
14.000
6.895
23.000
15.875
3.716
5.690
6.895
30.271
2.739
30.750
Ø.562 x 1.000
2.469
3.875
34.500
BOTTOM VIEW
FRONT
TOP VIEW

160K(i) 60 Hz Power Conditioner | Owners Manual 12
INSTALLATION (continued)
CABINET OUTLINE - RIGHT SIDE VIEW
TERMINATION ACCESS AREA
OPTIONAL SIDE OUTPUT
4.850
8.250
4.5002.810
35.500
RIGHT SIDE VIEW
AIR FLOW

13
1402-001
INSTALLATION (continued)
INPUT AND OUTPUT CONNECTIONS
1. Input connections are made directly to the unit’s 3 pole main input circuit breaker and input lug provided.
Note the bottom access wire run route illustrated below.
2. Output connections are made directly to the output breaker(s) and output neutral and ground lugs
provided. The load current is not to exceed 80% of the output breaker(s) rating, and not to exceed
the rated total current.
BOTTOM ACCESS WIRE RUN ROUTE
SEPERATION PLATE
OUTPUT METERS
70A 480V
OUTPUT
BREAKER
60A 480V OUTPUT BREAKER
COPPER BUS
OUTPUT TERMINATIONS
TO TOP)
(CUSTOMER'S INPUT CONNECTS
INPUT CIRCUIT BREAKER
SCALE 1 : 2
DETAIL A
BYPASS SWITCH
FRONT VIEW
30A 120V
OUTPUT
BREAKER
150A 208V
OUTPUT
BREAKER
OUT OF RANGE &
MONITOR ALERT
LIGHTS
A
OUTPUTCONDITIONED POWER
INPUTOUT OF RANGE
ALERT
CBA
WIRE RANGE: 6 AWG - 250 MCM
INPUT GROUND LUG (1) TA 250

160K(i) 60 Hz Power Conditioner | Owners Manual 14
BYPASS SWITCH
**** CAUTION ****
Prior to switching from one position to another- turn off the AC input breaker.
The manual bypass switch is a break before make switch located on the Series 700 AV/T-S. The manual
bypass switch is used to bypass all power electronics in case of failure.
This is a no load switch and MUST only be operated when the unit is OFF. The bypass switch should be
in the “NORMAL” position unless a problem occurs with the system. If a problem occurs, turn OFF the
main AC circuit breaker and turn the bypass switch to the “BYPASS” position. Re-energize the system
by turning on the AC circuit breaker and contact the Customer Support Department for repairs.
NORMAL MODE
With the switch in the normal position, the Series 700 AV/T-S will provide clean and regulated power to
the critical loads. The Series 700 AV/T-S should have the switch in the normal position unless a failure
has occurred.
BYPASS MODE
With the switch in the bypass position, the Series 700 AV/T-S will provide clean power to the critical loads.
In the bypass position, the unit will not regulate the incoming voltage. The Series 700 AV/T-S should be
placed in the bypass position when a failure of the system has occurred. This provides the user with some
protection until a service technician arrives.
REMOTE EMERGENCY POWER OFF (REPO) OPTION
The REPO is operated by a remote push button that when depressed will shunt trip the Series 700 AV/T-S
input breaker and disable the unit. This option may be added to units in the eld.
Contact the Customer Support Department if you wish to add this option.

15
1402-001
START UP
**** WARNING ****
THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE ENCLOSURE OF
THE POWER SUPPLY SYSTEM. CAUTION MUST BE TAKEN WHEN WORKING WITH
THE ENCLOSURE. IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY
QUALIFIED ELECTRICAL PERSONNEL ONLY.
NOTE: INITIAL START-UP SHOULD BE PERFORMED WITH NO LOAD ON SYSTEM.
1. Re-install all panels that may have been removed during installation.
2. Make sure the input circuit breaker is in the off position.
3. Energize the primary building power.
4. Turn on the main AC input breaker.
5. Verify that the output voltage is within the specied range.
6. Verify output phase rotation is correct.
7. Turn the system off.
8. Connect the loads one at a time and repeat Step 4.
OPERATION
MONITORING
Two (2) digital output meters shall be provided. One shall monitor the 208/120 VAC output and the other
shall monitor the 480/277 VAC output. Each meter shall monitor and display Line-to-Line and Line-to-
Neutral voltages. Minimum and maximum voltage values shall be recorded in EPROM. High and low
output voltage limit alarms shall be programmable and a visual indication given if limits are exceeded.
For function and use, see the monitor manual supplied with the Power Conditioner.

160K(i) 60 Hz Power Conditioner | Owners Manual 16
PREVENTIVE MAINTENANCE
**** WARNING ****
dANgER OF ELECTRICAL ShOCK, TURN OFF ALL POwER SUPPLYINg ThIS EqUIPmENT
PRIOR TO MAINTENANCE.
To ensure longer component life and trouble-free operation, minor preventive maintenance procedures
should be performed at regular intervals, for example once every year. More frequent inspection intervals
would be needed for more severe operating conditions and larger number of hours of continuous operation.
1. Remove front and side panels and at each service inspection any accumulated dust, dirt or foreign
particles should be carefully removed. Special care should be exercised in cleaning the thyristors
(SCR’s), heat sinks and the control assembly.
2. Inverse Parallel Silicon Rectiers (SCR’s) or Thyristors - The silicon controlled rectiers (SCR’s or
Power Mods) usually fail in the shorted mode. When this happens, normally the fusible link in series
with the SCR will be blown open to clear the short and prevent damage to the transformers. If a blown
SCR is suspected, contact Transtector for service.
3. A simple performance checklist has been developed for use in maintenance. See “Performance
Checklist” and check off items 1-7.
4. After items 1-7 have been checked on the “Performance Checklist”, the next step is to check the
operation of the system.
5. Replace front and side panels. Turn unit on with no load. Check item 8 on the “Performance Checklist”
6. Turn on loads and check items 9-10 off the “Performance Checklist”.
7. Check to make sure all fans are operational and check off item 11.
NOTE: Preventive Maintenance Plans are available. Please contact the Customer Support Group for
information. Call 1-800-882-9110 X6112.
Rick Ribbeck
Phone: (O) 208-635-6400 Ext. 5867 | (M) 208-762-6112
E-mail: [email protected]
E-mail: [email protected]
Transtector Systems
10701 Airport Dr.
Hayden Lake ID 83835
SERVICE
Transtector shall provide immediate phone support/consultation and if possible, same day parts shipment.
(contact must be prior to 12:00 PM PST). If necessary, on site service shall be scheduled the same day
for service to be conducted within 24 to 48 hours, based on customer requirements. Typical service hours
are 8 AM to 5 PM Monday through Friday.

17
1402-001
PERFORMANCE CHECKLIST
Company______________________________________________________________
Model #____________________________Serial #__________________
1. Customer Comments or Problems____________________________________
2. Power Processor Environment Clean and Dust Free Yes_______ No________
3. Phase Rotation Correct (ABC) Yes_______ No________
4. Electrically wired properly ie...Conductor Sizing, Breakers, Grounding
5. Verify Input Voltage (See specication tag)
6. Check Tightness of Electrical Connections:
______Input Connections______Output Connections______Heatsink Connections (SCR’s)
______Circuit Board Connections______By-Pass Switch______Fuse Connections
______Fan Connections______Transformer Connections
7. Exercise all circuit breakers-
______Input Breaker______Output Breakers
8. Input/Output Voltage Checks (Adjust as Needed).
No Load Input No Load Output
A-B__________VAC__________ A-N__________VAC A-B__________VAC
B-C__________VAC__________ B-N__________VAC B-C__________VAC
A-C__________VAC__________ C-N__________VAC A-C__________VAC
9. Available Load Input Available Load Output
A-B__________VAC__________ A-N__________VAC A-B__________VAC
B-C__________VAC__________ B-N__________VAC B-C__________VAC
A-C__________VAC__________ C-N__________VAC A-C__________VAC
10. Input/Output Current Checks (Balance as Needed).
Input Output
A__________Amps A__________Amps
B__________Amps B__________Amps
C__________Amps C__________Amps
N__________Amps
G__________Amps
11. Fans Operational_________________________________________________________

160K(i) 60 Hz Power Conditioner | Owners Manual 18
GENERAL TROUBLESHOOTING
SYMPTOM PROBABLE CAUSES
1. No Output on One or More Phases. A. No Input.
B. Blown Fuse.
C. Defective SCR or Power Mod.
D. Defective Control Card.
E. Defective Sense Card.
2. Output is too High or too Low. A. Input Out of Range.
B. Control Card Adjustment.
C. Defective Control Card.
D. Defective Sense Card.
E. Defective SCR or Power Mod.
3. Input Breaker Tripping Off. A. System Overloaded.
B. Defective Breaker.
C. Shorted Taps.
**** WARNING ****
THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE ENCLOSURE OF
THE POWER SUPPLY SYSTEM. CAUTION MUST BE TAKEN WHEN WORKING WITH
THE ENCLOSURE. IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY
QUALIFIED ELECTRICAL PERSONNEL ONLY.
Rick Ribbeck
Phone: (O) 208-635-6400 Ext. 5867 | (M) 208-762-6112
E-mail: [email protected]
E-mail: [email protected]
Transtector Systems
10701 Airport Dr.
Hayden Lake ID 83835
SERVICE
Transtector shall provide immediate phone support/consultation and if possible, same day parts shipment.
(contact must be prior to 12:00 PM PST). If necessary, on site service shall be scheduled the same day
for service to be conducted within 24 to 48 hours, based on customer requirements. Typical service hours
are 8 AM to 5 PM Monday through Friday.

19
1402-001
PARTS LIST
QTY 208 V INPUT 240 V INPUT 480 V INPUT 600 V INPUT DESCRIPTION
PART # PART # PART # PART #
2 112640 112640 112640 112640 OUTPUT METER
1 204936 204936 204418 204420 MAIN TRANSFORMER
1 204518 204518 204518 204518 AUTO TRANSFORMER
111173 11173 11173 11173 CONTROL TRANSFORMER
1 104036 110898 110924 110217 MAIN INPUT BREAKER
6 17666 17666 17666 17666 FILTER CAPACITOR
6 17538 17538 17538 17538 FILTER RESISTOR
3 16638 16638 16638 16638 SENSE FUSE (.75A)
3 18702 18702 18702 18702 CONTROL FUSE (FNQ-.6)
3 109580 109580 109580 109580 CONTROL FUSE (SC-30)
3 110894 110894 110894 110894 CONTROL FUSE (SC-1)
8 110895 110895 110895 110895 CONTROL FUSE (SC-3)
1 110896 110896 110896 110896 CONTROL FUSE (SC-5)
1 13789 13789 13789 13789 CONTROL RELAY
1 13696 13696 13696 13696 PILOT LIGHT - RED (ALERT)
3 109054 109054 109054 109054 PILOT LIGHT - GREEN (A,B,C)
3 107829 107829 107829 107829 PILOT LIGHT - INPUT OUT OF RANGE
3 23943 23943 23943 23943 SENSE BOARD
3 25723 25723 25723 25723 SNUBBER BOARD
3 420356 420356 420356 420356 MAIN CONTROL BOARD
1 100810 100810 100810 100810 BYPASS SWITCH
1 13765 13765 13765 13765 30A, 1P, 120V OUTPUT BREAKER
1 110212 110212 110212 110212 60A, 3P, 480V OUTPUT BREAKER
1 111822 111822 111822 111822 70A, 3P, 480V OUTPUT BREAKER
1 110924 110924 110924 110924 150A, 3P, 208V OUTPUT BREAKER
1 111601 111601 111601 111601 TVSS
3 301357 301357 301357 301357 HEATSINK ASSEMBLY
3 407753 407753 407753 407753 HEATSINK
21 104583 104583 104583 104583 POWER MODULE (SCR)
3 13319 13319 13319 13319 THERMAL SENSOR
6 104607 104607 104607 104607 FUSIBLE LINK
3 110939 110939 110939 110939 DIODE
3 103759 103759 103759 103759 BLOWER MOTOR

160K(i) 60 Hz Power Conditioner | Owners Manual 20
WARRANTY
WARRANTY VALIDATION
WARRANTY VOID UNLESS THIS FORM IS COMPLETE AND
RETURNED TO TRANSTECTOR SYSTEMS
Transtector Systems, Inc. warrants that the Series 700 AV/T-S Power Conditioner and its components will remain free
from defects in material and workmanship for the period of two (2) years from the date of shipment and agrees to replace
F.O.B. its factory, any part or parts which fail through defect in material or workmanship during such period.
▪The Warranty shall be effective only if and so long as the system is installed and operated in the manner specied
in the manual which accompanied the Power Conditioner and operated within the ratings on the nameplate of the
system.
▪The Warranty shall be void if any alteration is made to the system or any of its components are altered by anyone
other than authorized personnel.
▪The cost of transporting a questionable component and/or a replacement component to and from the factory is the
responsibility of the customer. The expense of installation of the replacement component is the responsibility of the
purchaser, unless covered by the GOLD PLAN or GOLD PLUS PLAN. Factory servicemen are not included in this
warranty.
▪This Warranty is in lieu of all other warranties, expressed or implied. The giving of, or failure to adhere to any advice
or recommendations by Transtector Systems shall not constitute any warranty by, or impose any liability upon the
company. Transtector Systems Inc. neither assumes nor authorizes any person to assume for it, any liability other
than that specically set forth in this Warranty. Except for its obligations, Transtector Systems, Inc. assumes no
responsibility for consequential or other damages resulting from defects in workmanship or failure of the system or
any components.
▪This warranty does not apply if the cause of the failure to properly perform is re, ood, windstorm, earthquake,
misuse, or abuse or any other reason other than those described above, i.e. defects in manufacture. If the component
fault has been caused by misuse or abnormal conditions in the judgment of factory personnel after inspection at our
plant, the customer will be charged for repairs based on parts and labor required.
Model #
Date
Title
Start up Organization
Serial #
Company
Address
City/State/Zip
Contact
Phone
Complete and return form to:
Attn: Rick Ribbeck
Transtector Systems, Inc.
10701 Airport Dr.
Hayden Lake ID 83835
Phone 208-635-6400 Ext. 5867
Fax 208-762-6133
Table of contents
Popular Industrial Electrical manuals by other brands

Siemens
Siemens 3TM operating instructions

HSP
HSP STARIS Sia+ Installation, operating and maintenance instructions

Nova Technology International, LLC
Nova Technology International, LLC Lock-Up installation manual

Murata
Murata GRM0335C1H6R4CA01 Series Reference sheet

PCB Piezotronics
PCB Piezotronics 352B10 Installation and operating manual

UCL SWIFT
UCL SWIFT ILSINTECH K33A Owner's manual & user guide

Murata
Murata GRM0335C1H3R7CA01 Reference sheet

Murata
Murata GRM1555C1H3R9WA01 Series Reference sheet

Furukawa electric
Furukawa electric FITELNINJA NJ001 Quick reference guide

Intelitek
Intelitek Scorbot-ER 9 Pro installation guide

Murata
Murata GCM1885C1H201JA16 Series Reference sheet

Murata
Murata GRM188R60J475ME19 Series Reference sheet