INSBUD IB-Therm 203S User manual

Electronic room thermostat
for ventilation support, recuperators
or four-pipes fan coils

InsBud company supports policy of development. The right to making changes and
improvements in products and manuals without prior notice reserved!
The contents of this manual - the text and graphics are owned by InsBud company
or its subcontractors. It is legally protected.
PRODUCT IS CE MARKED
AND WAS PRODUCED IN ACCORDANCE WITH ISO 9001 STANDARD
v2.2
„INSBUD”
ul. Niepodległości 16a
32-300 Olkusz
Poland
sale department: +48 (32) 626 18 00
sale department: +48 (32) 626 18 18
technical department: +48 (32) 626 18 07
technical department: +48 (32) 626 18 08
fax: +48 (32) 626 18 19
e-mail: insbud@insbud.net

www.insbud.net 3
E
NGLISH
IB-THERM 203S
General Information________________ 4
Features _________________________ 4
Principle of Operation ______________ 4
Technical Data ____________________ 4
Scope of Delivery __________________ 5
Structure _________________________ 5
Structure of Outputs _______________ 6
Exemplary Connection______________ 7
Warranty _________________________ 8

www.insbud.net
4
E
NGLISH
GENERAL INFORMATION
IB-Therm 203S room thermostat is desi-
gned to control valves, air dampers and he-
aters, fan coils and other heating appliances
after usign relay. IB-Therm 203S thermostat
allows to control process of heating, cooling
and ventilation comfortably in the each type
of buildings. It allows to save energy costs,
contributing to protect our environment.
øEnergy consumption: < 2 W
øSetting range: 10÷ 30 ºC
øHysteresis: 1 ºC
øAccuracy: 1 ºC
øMaximum load: 400 W
øCasing: ABS
øProtection rating: IP20
øStorage temperature: -20÷ 60 ºC
øOperating temperature: 0 ÷ 60 ºC
øControl: electronic
øPower supply: 230V AC or
24V AC/DC
Thermostat measures the temperature by
built-in sensor. The knob is used to set the
desired temperature (switching threshold).
In the heating mode heating device is turned
on when the real temperature is lower than
the desired temperature, and cooling device
is always turned o.
In the cooling mode cooling device is turned
on when the real temperature is higher than
the desired temperature, and heating device
is always turned o.
Ventilation speed switch allows to set venti-
lation’s eciency (fan coil gear, fan gear).
Thanks to independent outputs for heating
and cooling, both devices can be connec-
ted to the thermostat at the same time (for
example: heater and air conditioner). It me-
ans that selection of the currently working
device is only made by heating/cooling
switch (the logical requirement is reversed
simultaneously).
PRINCIPLE OF OPERATION
TECHNICAL DATA
FEATURES
øEsthetic and traditional design
øEasy and intuitive operating
øSensor with a negative temperature co-
ecient (NTC)
øAvailable modes:
» heating
» cooling
øFan speed:
» low
» medium
» high
øON/OFF switch
øAbility to precise room temperature set-
ting, according to needs
øIndependent outputs for heating and
cooling devices - dedicated for four-pi-
pes fan-coils.
øStandard mounting dimensions
øSurface mounting

www.insbud.net 5
E
NGLISH
STRUCTURE
SCOPE OF DELIVERY SCOPE OF DELIVERY
ø1x IB-Therm 203S thermostat
ø1x Operating manual
temperature
setting knob
low/medium/high
ON/OFF
heating/cooling
55 mm
130 mm
40 mm
Thermostats powered from 230V mains vol-
tage are delivered implicitly. Also thermo-
stats powered from 24V voltage source can
be delivered (the same model for AC and DC
voltage) if ordered. If you want to buy 24V
thermostat, please indicate it in the order.

www.insbud.net
6
E
NGLISH
ø1, 2- power (depending on the model:
230V AC or 24V AC/DC);
ø3- this output is short to the input no. 1
when following requirements are simul-
taneously met: the thermostat is turned
on (ON), it works in heating mode and
the real temperature is lower than the
desired temperature;
ø4- this output is short to the input no. 1
when following requirements are simul-
taneously met: the thermostat is turned
on (ON), it works in cooling mode and
the real temperature is higher than the
desired temperature;
ø5- not used;
ø6- output of gear 3. It is short to the in-
put no. 1 when both requirements are
simultaneously met: the thermostat is
STRUCTURE OF OUTPUTS
turned on (ON) and ‘FAN’ switch is in the
position ‘3’;
ø7- output of gear 2. It is short to the in-
put no. 1 when both requirements are
simultaneously met: the thermostat is
turned on (ON) and ‘FAN’ switch is in the
position ‘2’;
ø8- output of gear 1. It is short to the in-
put no. 1 when both requirements are
simultaneously met: the thermostat is
turned on (ON) and ‘FAN’ switch is in the
position ‘1’;
IOnly one output is active at the same
time (depending on selected operatio-
nal mode: output no. 3 or output no. 4),
or both outputs are inactive.
Simplied diagram of outputs:
T
2
31
45678
FAN
1
2
3OFF ON
IB-Therm 203S HEAT
/COOL

www.insbud.net 7
E
NGLISH
1
2
2
3
1
4
5
6
7
8
-HEAT
-COOL ON OFF
-1-
FAN -2-
-3-
sn Bud
10
20
30
15
25
M
1
2
LN
EXEMPLARY CONNECTION
In this example, IB-Therm 203S thermostat
controls the four-pipes fan coil. Heating or
cooling mode is enabled and it can be chan-
ged by ‘HEAT/COOL’ switch at any time.
In the heating mode:
When the thermostat is turned on and the
real temperature is lower than the desired
temperature, circulation valve of hot water
is open (230V phase is on the output no. 3
of the thermostat) and fan works at chosen
speed.
When the thermostat is turned o or the real
temperature is higher than the desired tem-
perature, both valves are closed (there is no
phase either on output no. 3 or no. 4) and fan
is turned o.
In the cooling mode:
When the thermostat is turned on and the
real temperature is higher than the desired
temperature, circulation valve of cold water
is open (230V phase is on the output no. 4
of the thermostat) and fan works at chosen
speed.
When the thermostat is turned o or the real
temperature is lower than the desired tem-
perature, both valves are closed (there is no
phase either on output no. 3 or no. 4) and fan
is turned o.
IB-Therm 203S
Room thermostat
230V AC mains
IB-73xx valve
hot water
IB-73xx valve
cold water
3-gear fan
Following picture shows the exemplary wiring of „230V” model:

www.insbud.net
8
E
NGLISH
WARRANTY
øWarranty repair refusal is equivalent to
loss your warranty.
øIf it is not possible to test product be-
fore its purchase (distance selling), it is
possible to return goods within 10 days.
Returned goods cannot bear signs of
exploitation, it must contain all ele-
ments with which it was delivered.
øIn the case of return of purchased go-
ods all shipping costs are on buyer’s
side. For shipment please enclose pur-
chase document and give precise de-
tails of the buyer with account number
on which will be refunded an amount
equal to the value of the returned go-
ods, no later than 21 days from the date
of delivery of the goods. This amount is
reduced by shipping costs if these costs
were incurred by the seller. Delivery of
copy of document correction is neces-
sary to a refund. Before return of goods
please contact with seller.
øWarranty terms may be changed by lo-
cal InsBud company partner.
„INSBUD”
ul. Niepodległości 16a
32-300 Olkusz
Poland
sale department: +48 (32) 626 18 00
sale department: +48 (32) 626 18 18
technical department: +48 (32) 626 18 07
technical department: +48 (32) 626 18 08
fax: +48 (32) 626 18 19
e-mail: insbud@insbud.net
WARUNKI GWARANCJIWARRANTY
øWarranty is granted on 24 months from
the date of purchase of goods.
øAny defect disclosed during the war-
ranty period will be removed within 21
working days, from the date of adoption
of goods for service.
øIn case of necessity of import goods or
components from abroad, repair time is
extended by the time needed to bring
them.
øCustomer provides product to service at
his own cost. If the product is shipped at
the expense of the service, it will not be
received.
øAt time repair service has no obligation
to provide substitute product.
øWarranty repair will be made upon pre-
sentation of properly and legibly lled
your warranty card, signed by guarantor
and with sales document.
øWarranty covers only defects arising
from causes inherent in goods. Dama-
ge resulting from external causes such
as: mechanical damade, pollution, o-
oding, weather, improper installation or
improper wiring and operations. War-
ranty does not apply in case unautho-
rized repair by customer, changes in so-
ftware (rmware) and device formatting.
øDue to the natural consumption of con-
sumables, some of them are not covered
by warranty (for example: cables, batte-
ry, loader, micro contacts, buttons).
øIn the event of unjustied claim for war-
ranty repair, all additional cost are on
customer’s side.
øService has right to refuse to perform
warranty repairs for following: dieren-
ces between documents and goods
marks, make repairs on their own by
customer, changes in product construc-
tion without authorization.
Table of contents