IONPURE IP-VNX28EP-2 Manual

IONPURE®
VNX CEDI
Modules
Operation
&
Maintenance
Manual
IP-MAN-VNX-1019-EN
Rev 1
October 2019
This manual covers
model numbers:
·IP-VNX28EP-2
·IP-VNX55EP-2
·IP-VNX55E-2
·IP-VNX55EX-2
·IP-VNX55HH-2
·IP-VNX15CDIT-2
·IP-VNX30CDIT-2
·IP-VNX-MAX-1
·IP-VNX-MINI-1
Evoqua Water Technologies, LLC
558 Clark Road
Tewksbury, Massachusetts 01876, USA
ionpure@evoqua.com (email)
www.ionpure.com (web)
Visit web site to find local Ionpure contact

IONPURE ®VNX CEDI Modules
Page 2 IP-MAN-VNX-1019-EN.pdf
TABLE OF CONTENTS
DISCLAIMER STATEMENT 5
PROPRIETARY RIGHTS STATEMENT 5
OPERATING MANUAL REVISION HISTORY 6
1. INTRODUCTION 7
1.1. VNX55 product family overview 7
1.2. Using this manual 8
1.3. Installation Precautions 8
1.4. Operating Precautions 9
1.5. Shutdown Precautions 9
2. PRE-INSTALLATION: PREPARATION & REQUIREMENTS 10
2.1. Tools Required 10
2.2. Unpacking and Moving VNX Modules 10
2.3. Electrical and Plumbing Connection Requirements 11
2.4. Operating Requirements 11
2.4.1. Operating Environment 11
2.4.2. Space Requirements 11
2.4.3. Module Orientation 12
2.4.4. Electrical Requirements 12
2.4.5. Feed Water Requirements 12
2.4.6. Drain Requirements 13
2.5. Flow Rates and pressure drops 13
3. VNX MODULE INSTALLATION 14
3.1. Preparation 14
3.2. Water Connection Configuration and Fittings 14

IONPURE ®VNX CEDI Modules
Page 3 IP-MAN-VNX-1019-EN.pdf
3.2.1. VNX Piping Adapter Sealing Mechanism 15
3.2.2. VNX Piping Configurations 17
3.3. Electrical Connections 18
3.3.1. Electrical Precautions 18
3.4. RO/CEDI System Design Considerations 18
4. PREPARATION FOR STARTUP 20
4.1. Verify Feed Water Meets VNX Quality Requirements 20
4.2. Estimate DC Current Required 20
5. START-UP PROCEDURE 21
5.1. Test Interlocks 21
5.2. Startup of VNX Modules 21
5.3. Minimum Reject Flow Rate 21
5.4. Water Recovery 22
5.4.1. Example calculation of recovery 22
5.4.2. Example calculation of reject flow 22
6. MAINTENANCE AND TROUBLESHOOTING 23
6.1. General Maintenance Guidelines 23
6.2. Approved Cleaning Procedures 23
6.3. Cleaning and Sanitization Prompts 24
6.4. Clean-In-Place (CIP) System Construction 24
6.5. Chemical Cleaning and Sanitization Precautions 26
6.6. Typical Procedure for Cleaning or Sanitization 26
6.7. Cleaning Solution Recipes 28
7. TROUBLESHOOTING 31

IONPURE ®VNX CEDI Modules
Page 4 IP-MAN-VNX-1019-EN.pdf
8. SHUTDOWN AND STORAGE 38
8.1. System Shutdown 38
8.2. Startup After Shutdown 38
8.3. Rebuild or Repair 38
8.4. Disposal 38
APPENDIX A: VNX MODULE SPECIFICATIONS 39
APPENDIX B: VNX55 LAYOUT & ELEVATION DRAWING B-1 42
APPENDIX B: VNX ELECTRICAL CONNECTIONS DRAWING B-2 43
APPENDIX C: VNX PORT PVC ADAPTER DRAWING C-1 44
APPENDIX C: VNX PORT PVC PLUG DRAWING C-2 45
APPENDIX C: VNX PORT PP ADAPTER DRAWING C-3 46
APPENDIX C: VNX PORT PP PLUG DRAWING C-4 47

IONPURE ®VNX CEDI Modules
Page 5 IP-MAN-VNX-1019-EN.pdf
DISCLAIMER STATEMENT
The operation and maintenance manual should provide complete and accurate
information to meet your operating and/or service requirements based on the information
available at the time of publication. The information in this manual may not cover all
operating details or variations or provide for all conditions in connection with installation,
operation and maintenance. Should questions arise which are not answered specifically
in this manual, contact your water system supplier.
IONPURE reserves the right to make engineering refinements that may not be reflected
in these manuals. The material in these manuals is for informational purposes and is
subject to change without notice.
PROPRIETARY RIGHTS STATEMENT
This manual discloses information in which IONPURE has proprietary rights. Neither
receipt nor possession of this manual confers or transfers any right to the client, and by
its retention hereof, the client acknowledges that it will not reproduce or cause to be
reproduced, in whole or in part, any such information except by written permission from
IONPURE. The client shall have the right to use and disclose to its employees the
information contained herein for the purpose of operating and maintaining the IONPURE
equipment, and for no other purpose.
In the event the content of this manual is altered or section/items are omitted during a
reproduction, in whole or in part, and instructions or definitions within the reproduction
result in personal injury to those who follow the altered instructions, the burden of
responsibility for personal injury falls solely on the party who effects the reproduction.
MANUAL USER'S GUIDE
This manual describes the procedures necessary to install, operate, and maintain your
IONPURE Continuous Electrodeionization modules. Please read this manual carefully
before installing and operating your modules. The module warranty may be voided if
installation or operation instructions are not followed correctly.
Notes, Warnings, Cautions are used to attract attention to essential or critical information
in a manual. Warnings and Cautions will appear before the text associated with them,
and notes can appear either before or after the associated text.
NOTE: Notes are used to add information, state exceptions, and point out areas
that may be of greater interest or importance.

IONPURE ®VNX CEDI Modules
Page 6 IP-MAN-VNX-1019-EN.pdf
Cautions indicate a situation that may cause damage or
destruction of equipment or may pose a long-term health hazard.
Warnings indicate condition, practices, or procedures which
must be observed to avoid personal injury or fatalities.
IONPURE continually strives to provide safe, efficient, trouble-free equipment using the
optimum technology for your application. If problems should develop, IONPURE's
worldwide network of technical support will be available to provide assistance. For
service, sales, parts, or additional manual copies, please visit the website:
www.ionpure.com.
OPERATING MANUAL REVISION HISTORY
Event Date Description
First publication 03-2018 VNX Family Operation & Maintenance Manual
Revision 1 10-2019
2.2 Added lifting statement for vertical installations
3.3 Added torque specification for terminal strip
Corrected flows in Table 6-1a for 55E and 55EX
Updated Section 4.2 DC Current Required

IONPURE ®VNX CEDI Modules
Page 7 IP-MAN-VNX-1019-EN.pdf
1. INTRODUCTION
1.1.VNX55 Product Family Overview
Ionpure VNX modules are the highest flow rate CEDI devices available. Their compact
state-of-the-art design assures ease of installation, maintenance, and service. VNX
modules are available in the following sizes:
Model Number Nominal Flow Description
IP-VNX-MINI-1 52.8 gpm (12 m3/h) Small footprint, enhanced performance
IP-VNX-MAX-1 66 gpm (15 m3/h) High flow, enhanced performance
IP-VNX28EP-2 27.5 gpm (6.25 m3/h) Enhanced performance
IP-VNX55EP-2 55 gpm (12.5 m3/h) Enhanced performance
IP-VNX55E-2 55 gpm (12.5 m3/h) Microelectronics, polishing loop
IP-VNX55EX-2 55 gpm (12.5 m3/h) Microelectronics, makeup
IP-VNX55HH-2 55 gpm (12.5 m3/h) High hardness
IP-VNX15CDIT-2 15 gpm (3.4 m3/h) Thin cell
IP-VNX30CDIT-2 30 gpm (6.8 m3/h) Thin cell
For more information on the VNX module specifications and flow rates, see Section 2.4
and Appendix A of this Manual.
Figure 1-1: Angle and Side views of VNX Modules

IONPURE ®VNX CEDI Modules
Page 8 IP-MAN-VNX-1019-EN.pdf
1.2.Using This Manual
Service technicians should review this manual prior to going to the installation site. It lists
tools and materials needed to install the modules. It also outlines the site information
required to prepare for installation.
NOTE: The warranty may be void if installation or operation instructions contained in this
manual are not followed exactly.
This manual describes the installation, operation, and routine maintenance of the VNX
modules. It also contains information on basic troubleshooting (See Section 7).
IONPURE strongly recommends all users read the entire contents of the manual. If the
VNX module is not operating properly after going through the basic troubleshooting
exercises, contact your Local Service Provider.
1.3.Installation Precautions
·During operation, the electrode wiring inside the module junction
boxes are at high voltage and present a shock hazard.
THEREFORE, BEFORE TOUCHING THE INSIDE OF THE
JUNCTION BOX, CONFIRM THAT AC POWER TO THE DC
POWER SUPPLY HAS FIRST BEEN DISCONNECTED AND
LOCKED OUT ACCORDING TO STANDARD LOCKOUT/
TAGOUT PROCEDURES.
·To minimize the possibility of electric shock, confirm that all ground
wires are properly connected.
·Do not open the VNX module. Opening the module will void the
warranty and cause irreversible damage.
·The module must be operated according to the design
specifications for temperature and humidity.
·Metal piping should never be connected directly to the module.
Non-metallic piping adapters are required at the module inlets and
outlets. It is then allowable to transition to metallic piping.
·Pipe sections prepared for installation must be inspected, and be
free of debris from storage or cutting tool particles. This must be
done before installation.
·Because VNX modules have narrow flow distribution channels,
plugging by particles can cause permanent damage. Always
install pressure gauges, sampling ports, sensors, etc. in tee
fittings. Do not drill or tap into piping.

IONPURE ®VNX CEDI Modules
Page 9 IP-MAN-VNX-1019-EN.pdf
·Always flush out the piping to remove any debris before operating
the VNX module.
·Installation of the VNX module must be completed in accordance
with the procedures outlined in this manual. If deviations from the
prescribed procedures are deemed necessary to achieve the
desired performance, consult your local Service Provider.
1.4.Operating Precautions
·DO NOT APPLY POWER TO THE VNX MODULE UNTIL
PROPER FLOW AND PRESSURE HAVE FIRST BEEN
CHECKED AND VERIFIED.
·Never block off (dead-head) the VNX outlets. Dead-heading the
outlets can result in over-pressurization, leading to permanent
damage.
·Do not operate the module under conditions other than those
stated in the module manual. The prescribed feed water
requirements, electrical requirements, and flow configurations
must be followed at all times. If the feed water quality or the
product water requirements change, contact the IONPURE
Technical Support Department for assistance.
·Once every six months:
oMake sure all wiring connections are tight.
oTest safety interlocks such as flow switches or connections to upstream
equipment.
1.5.Shutdown Precautions
·Confirm that the pressure in the unit is relieved until all pressures inside the unit are
atmospheric (i.e., all pressure gauges should read zero).
·Drain standing water and valve off or plug all inlets and outlets. This is to minimize
bacteria growth and prevent drying of ion exchange resins during shutdown.

IONPURE ®VNX CEDI Modules
Page 10 IP-MAN-VNX-1019-EN.pdf
2. PRE-INSTALLATION: PREPARATION & REQUIREMENTS
2.1.Tools Required
·Lifting straps and forklift or block and tackle to move the module into place
·Slip joint pliers, for tightening of plumbing connectors
·Wire cutters/strippers, for wiring connections
·Phillips head screwdriver, to connect wire at terminal strip
2.2.Unpacking and Moving VNX Modules
·After uncrating the module, inspect it for any signs of damage. If damage is apparent,
immediately notify the carrier and your CEDI System Provider.
·The VNX modules can weigh 300-600 lbs. (136-273 kg) dry, depending on size, and
will require mechanical assistance for lifting and moving into position. See Figure 2-1
for one example of how to lift a VNX module.
·For vertical installations the module can be lifted from one end (not shown).
·Ensure that lifting apparatus has appropriate load rating.
Figure 2-1 Lifting VNX module via housing FlexMounts

IONPURE ®VNX CEDI Modules
Page 11 IP-MAN-VNX-1019-EN.pdf
2.3.Electrical and Plumbing Connection Requirements
·An electrical junction box is included with all VNX modules, mounted on one of the
VNX endblocks. A single conduit connection is required through a 7/8” (22 mm)
through-hole to provide power to the CEDI module.
·Connection of the DC power supply to the VNX module requires 12 AWG (3.31 mm2)
wire. All wiring should be done in accordance with local electrical codes.
·Ionpure VNX modules have cast metal end blocks with four (4) custom, ACME-thread
FEMALE connection points. These require special plumbing adapters or plugs,
constructed to the drawings provided in Appendix B. The 4 connections are:
oProduct (Dilute) Inlet
oProduct (Dilute) Outlet
oReject (Concentrate) Inlet
oReject (Concentrate)Outlet
·The VNX modules are shipped with PVC piping adapters with 1-1/2” SOC connections
oKit model number IP-VNX-CK-PVC-2, part number W3T17350
·Optional polypropylene adapters with 50 mm butt weld connections are available
oKit model number IP-VNX-CK-PP-2, part number W3T17348
·To avoid the risk of electrical shock, some form of grounding must
be used on any stream where the plumbing is stainless steel or if there
are samples points or instrumentation near the module.
oFor sanitary applications, a grounding cap can be used, Ionpure part number
W3T83436, which is actually a ¾” TC cap with a welded stud to be wired to
ground.
oFor non-sanitary applications, a ¼” SS threaded grounding rod can be used,
Ionpure part number W2T211647.
2.4.Operating Requirements
In order to operate to specification, the VNX module must have the following conditions
present. If any of these conditions are unmet, do not attempt to install the VNX module
without specific instructions from your Local Service Provider’s Technical Support.
2.4.1. Operating Environment
The VNX module requires indoorinstallation out of direct sunlight. The maximum ambient
temperature should not exceed 113 °F (45° C). The module can tolerate humidity of up
to 90%, as long as condensation does not occur.
2.4.2. Space Requirements
The physical dimensions of the VNX modules are given in appendix A.1. In addition to
the size of the module itself, the arrangement of the piping and the electrical connections

IONPURE ®VNX CEDI Modules
Page 12 IP-MAN-VNX-1019-EN.pdf
will determine the amount of space the module needs to operate. This arrangement
varies from site to site. Space should be allowed for module servicing/replacement.
2.4.3. Module Orientation
The VNX modules can be installed vertically or horizontally. If orientated in the vertical
position, the junction box end should be facing down. This is done to remove the
possibility of the junction box flooding. When mounting in the horizontal position, the
modules should be stacked no higher than four (4) modules high.
2.4.4. Electrical Requirements
The VNX module power requirements are listed in Table 2-2. In all cases the cathodes
must be at ground potential. Connections are shown in section 3-3.
Table 2-2. Electrical Requirements for the VNX Modules
NOTE: The 600V DC3 power supply can be used even if required DC Voltage is lower.
This may help protect against upsets due to feed water changes, scaling or fouling.
2.4.5. Feed Water Requirements
Feed water for the VNX module must always meet the specifications outlined in Table 2-
3. In most cases, pre-treating VNX module feed water with reverse osmosis (RO) will
bring it within these specifications. Depending on the conditions, however, some sites
may require additional pretreatment. To determine if additional pretreatment is required,
compare the VNX feed water on site with the feed water requirements listed below.
NOTE: Recycling the VNX reject to the RO feed will cause the CO2load on the VNX to
increase, and may have an impact on the VNX product water quality. Please refer to
VNX Model Nominal Flow Rate DC Volts DC Amps
IP-VNX-MINI 52.8 gpm (12 m3/h) 480 1 - 7
IP-VNX-MAX 66 gpm (15 m3/h) 600 1 - 7
IP-VNX28EP-2 27.5 gpm (6.25 m3/h) 300 1 - 6.6
IP-VNX55EP-2 55 gpm (12.5 m3/h) 300 2 - 13.2
IP-VNX55E-2 55 gpm (12.5 m3/h) 300 10 - 13.2
IP-VNX55EX-2 55 gpm (12.5 m3/h) 300 10 - 13.2
IP-VNX55HH-2 55 gpm (12.5 m3/h) 600 2 – 8.0
IP-VNX15CDIT-2 15 gpm (12.5 m3/h) 600 1 - 6.6
IP-VNX30CDIT-2 30 gpm (12.5 m3/h) 600 2 – 13.2

IONPURE ®VNX CEDI Modules
Page 13 IP-MAN-VNX-1019-EN.pdf
Ionpure.com for additional reject stream system design guidance including the following
paper: “Process and System Design for Reliable Operation of RO/CEDI Systems”,
Jonathan Wood and Joe Gifford, International Water Conference, 2004 (Paper 47).
Table 2-3. Feed Water Requirements (except hardness, silica), also see A.3
Parameter EP, Max, Mini, HH E, EX CDIT
Feed water source RO permeate
or DI water 2-pass RO
or DI water RO permeate
FCE (µS/cm) ≤40 µS/cm ≤10 µS/cm ≤100 µS/cm
Iron, manganese, sulfide ≤0.01 ppm ≤0.01 ppm ≤0.01 ppm
Total chlorine (as Cl2)≤0.02 ppm ≤0.02 ppm ≤0.02 ppm
TOC (ppm as C) ≤0.5 ppm ≤0.5 ppm ≤0.5 ppm
Operating pH range 4 – 11 4-11 4 – 11
Feed water temperature
(10°C minimum for VNX-Max) 41 - 113 °F
(5 – 45 °C) 68 – 113 F
(20-45C) 41 - 113 °F
(5 – 45 °C)
Inlet pressure ≤100 psig
(6.9 bar)
≤100 psig
(6.9 bar)
≤100 psig
(6.9 bar)
Table 2-4. Module-Specific Feed Water Hardness and Silica Requirements
VNX Model Silica (as SiO2) Hardness (as CaCO3)
IP-VNX-MINI ≤1.0 ppm ≤1.0 ppm
IP-VNX-MAX ≤1.0 ppm ≤1.0 ppm
IP-VNX28EP-2 ≤1.0 ppm ≤1.0 ppm
IP-VNX55EP-2 ≤1.0 ppm ≤1.0 ppm
IP-VNX55E-2 ≤0.2 ppm ≤0.1 ppm
IP-VNX55EX-2 ≤0.5 ppm ≤0.1 ppm
IP-VNX55HH-2 ≤1.0 ppm ≤2.0 ppm
IP-VNX15CDIT-2 ≤2.0 ppm ≤4.0 ppm
IP-VNX30CDIT-2 ≤2.0 ppm ≤4.0 ppm
2.4.6. Drain Requirements
Place the VNX module near a drain that can accommodate 100% of the total feed flow.
2.5.Flow Rates and Pressure Drops
See Appendix A

IONPURE ® VNX CEDI Modules
Page 14 IP-MAN-VNX-1019-EN.pdf
3. VNX MODULE INSTALLATION
3.1.Preparation
Confirm that the pre-installation requirements outlined in Section 2 are met and the
system is ready for VNX Module installation.
·Remove any packaging materials and move the module to its
operating location. Use safe lifting practices when moving the module
(see Section 2.2).
·To avoid corrosion, the piping adapters and plugs must be non-metallic.
·Modules are shipped with PVC connection adapters and plugs installed.
·Optional polypropylene PP adapters and plugs are available
·If other adapter types are required, the module end must be made to the dimensions
provided in drawings C-1 through C-4 in Appendix C. This is essential to ensure
proper sealing of the adapter in the endblock.
·Remove the yellow dust plugs that seal the inlet and outlet ports on
the module (see Figure 3-1). Failure to remove yellow dust plugs can
cause permanent damage to the modules.
Figure 3-1 VNX PVC adapter with yellow shipping plug
3.2.Water Connection Configuration and Fittings
·Make sure all upstream pretreatment equipment and piping have
been thoroughly flushed with particle-free water before connecting
them to the VNX Module. Flushing removes any particles left in the
piping fromcutting and assembly. If particles remain, they could plug the passages inside
the VNX Module.
NOTE: Failure to properly flush the pretreatment water system of installation debris to
drain prior to flowing water to the CEDI can result in particulate fouling that may be
irreversible.
Remove this
yellow dust plug

IONPURE ®VNX CEDI Modules
Page 15 IP-MAN-VNX-1019-EN.pdf
Ionpure VNX modules have a cast aluminum endplate with female ACME thread
connections. There are four (4) connection points:
·Product (Dilute) Inlet
·Product (Dilute) Outlet
·Reject (Concentrate) Inlet
·Reject (Concentrate) Outlet
Product and reject port locations are identified with color coded labels affixed near the
appropriate endblock connection points. Product port inlets (I) and outlets (O) are
identified with BLUE labels, and reject port inlets (I) and outlets (O) are identified with
RED labels. Figure 3-2 (below) shows what the labels look like.
Figure 3-2 VNX Port Labels
Detailed dimensions of the VNX module port locations are given in the layout and
elevation drawing in Appendix B, Drawing B-1.
3.2.1. VNX Piping Adapter Sealing Mechanism
The female threads in the VNX endplate are ACME threads. They are NOT TAPERED
pipe threads and the threads DO NOT CREATE the seal, they allow the sealing surfaces
to move towards each other and they hold the piping adapter in place. The seal comes
from the silicone through-port gasket that isolates the endblock and creates a sealing
surface directly to the internal VNX spacer. See Figure 3-3, below.
NOTE: Do NOT use Teflon®tape or any other pipe sealant (such as pipe dope) on the
ACME thread adapters or plugs. The use of these products on the ACME threads will
prevent proper sealing of the adapters or plugs.

IONPURE ®VNX CEDI Modules
Page 16 IP-MAN-VNX-1019-EN.pdf
Figure 3-3 VNX Piping Adapter Sealing Mechanism
Do not install O-rings on the circumference of the VNX ACME-thread piping adapters or
plugs. The O-rings make it more difficult to properly tighten these parts.
Tighten the adapter or plug until the gap between the endblock and the “shoulder” on the
piping adapter or plug is between 0.03” (0.76 mm) and 0.06” (1.52 mm). This is shown
in Figure 3-4, below. It should be possible to accomplish this by hand but if necessary a
wrench can be used. You should only need 10-30 ft-lbs (13.6 – 40.7 N-m) of torque.
Figure 3-4 Proper Tightening of VNX Piping Adapter

IONPURE ® VNX CEDI Modules
Page 17 IP-MAN-VNX-1019-EN.pdf
3.2.2. VNX Piping Configurations
Because the internal piping of a VNX module can vary depending on model, external
connections can vary as well. Consult the table below for the correct configuration for
your specific VNX module.
Table 3-1 VNX Module Piping Connections
Model Recommended Configuration Comments
IP-VNX28EP-2
IP-VNX55EP-2
IP-VNX55HH-2
IP-VNX15CDIT-2
IP-VNX30CDIT-2
IP-VNX-MAX
IP-VNX-MINI
Product:
Inlet & outlet on same side OR
Inlet & outlet on opposite sides
Reject:
Inlet & outlet on same side OR
Inlet & outlet on opposite sides
IP-VNX55E-2 Product:
Inlet & outlet on same side OR
Inlet & outlet on opposite sides
Reject:
Inlet & outlet on opposite sides
(Top inlet, bottom outlet)
IP-VNX55EX-2 Product:
Inlet & outlet on same side OR
Inlet & outlet on opposite sides
Reject:
Inlet & outlet on opposite sides
(Top inlet, top outlet)
Product connection (blue, solid)
Reject connection (red, dashed)

IONPURE ®VNX CEDI Modules
Page 18 IP-MAN-VNX-1019-EN.pdf
3.3.Electrical Connections
All VNX modules have an on-board electrical junction box to allow convenient connection
of the module to the DC power supply that provides the driving force for the
electrodeionization process. Only one electrical connection is required per module.
Power connections to the terminal strip inside the module junction box (see Figure 3-5)
should be made with 12 or 10 AWG (4.0 or 6.0 mm2) wire and conduit connections should
be supplied via the 7/8” (22 mm) junction box through-hole. Wire stripping length is 0.35”
(9 mm) and terminal strips screws should be tightened to 1.6 N-m (14 lbf-in).
The DC wire color conventions used on the VNX modules are as follows:
·Red (+) to DC positive terminal of power controller
·Black (–) to DC negative terminal of power controller
·Green/Yellow to earth ground
Figure 3-5 Inside the VNX Junction Box (2-stack module)
3.3.1. Electrical Precautions
·Disconnect power before opening any enclosure and follow
accepted Lockout/Tagout procedures when working on the
system.
·Do not run AC and DC wiring within the same conduit. This may
cause interference and lead to malfunctions.
◄Return from stack
◄Return from stack
◄Out to stacks

IONPURE ®VNX CEDI Modules
Page 19 IP-MAN-VNX-1019-EN.pdf
·Ensure that polarity of DC connections is correct before applying
DC power. Operation with polarity reversed will permanently
damage the cathode. It is critical that the red and black wires are
correctly oriented on the positive (+) and negative (-) terminal
blocks.
·Junction box terminal strips screws should be tightened to 1.6 N-
m (14 lbf-in) to avoid wire loosening, arcing and overheating.
·The ground in the junction box must be connected to earth ground.
·All wiring done in the field must conform to local electrical codes. Consult your Local
Service Provider if there is a conflict between the instructions in this manual and the
local codes.
·Power connections for the modules must be connected to a suitable DC power supply
capable of meeting the DC power requirements of the module (see Table 2-2).
3.4.RO/CEDI System Design Considerations
·Direct feed of an RO system to the CEDI system requires use of a pressure relief valve
or rupture disk between the RO and CEDI to prevent accidental overpressure of the
CEDI.
·If the CEDI system is fed from a tank instead of directly from an RO system, there are
two requirements:
oThe CEDI feed pump must be sized so that its dead-head pressure does not
exceed the 100 psig (6.9 bar) pressure limit of the CEDI modules.
oThere must be prefiltration directly upstream of the CEDI system (5 micron
suggested) as experience has shown tanks and repumping to be a common
source of particulate contamination.
·The CEDI DC power supply must be interlocked with the RO feed pump or the CEDI
feed pump (whichever is appropriate) to ensure that the power supply can’t be
energized if the pump is not running.
·In addition, the EDI system must have low flow protection for both the product and
reject.
·Piping to the CEDI modules should be designed to minimize mechanical stress on the
CEDI piping connectors.
·Start/stop systems should have provisions to automatically divert RO permeate to
drain upon startup from standby condition. This is necessary because the initial RO
permeate is usually worse quality than the ROfeed water! It is better to flush for a set
time period (3-5 minutes) rather than to a conductivity endpoint.
·Systems that reclaim CEDI reject and send it back to the RO inlet should have
provisions for venting the electrode gases.
·Automatic valves downstream of the CEDI should be designed to close slowly (>3
seconds) and must avoid momentary dead-heading of the CEDI module.

IONPURE ®VNX CEDI Modules
Page 20 IP-MAN-VNX-1019-EN.pdf
4. PREPARATION FOR STARTUP
4.1.Verify Feed Water Meets VNX Quality Requirements
Check the VNX feed water quality by running the RO system to drain and testing to make
sure the feed water quality meets all the feed water requirements given in Tables 2-3 and
2-4. Below are some of the test kits or devices that may be useful:
Table 4-1 Useful Equipment for Feed Water Testing
Analyte Model Minimum Increment
Conductivity Myron L Ultrameter II 4P 0.1 µS/cm
CO2Hach CA-23 (#143601) 1.25 mg/l
Cl2Hach CN-70 (#1454200) 0.02 mg/l
Hardness Hach HA-71A (#145201) 1.0 mg/l
Silica Hach SI-7 (#2255000) 0.05 ppm
4.2.Estimate DC Current Required
An important part of the startup process for the VNX module is setting the operating
current correctly for each particular application. The amount of DC current required
depends on the following site-specific conditions:
·Product flow rate per stack, number of cells per stack
·Number of stacks (electrode pairs) per module
·CEDI feed water conductivity equivalent (FCE)
·Measured feed water conductivity (may require a portable conductivity meter)
·Feed water carbon dioxide concentration (requires test kit such as above)
·Feed water silica concentration (usually low enough to be neglected)
·Product water quality required
The best way to determine the amount of DC current required is to use the Ionpure
projection tool, IP-PRO: https://ippro.evoqua.com/
Alternatively, it can be estimated using the equation below (based on Faraday’s Law).
NOTE: Contact local Ionpure Technical support for assistance.
DC amps/stack = (1.31)(product flow, L/min/cell)(FCE, µS/cm)/current efficiency, %
Where FCE = measured µS/cm + (ppm CO2)(2.79) + (ppm SiO2)(2.04)
NOTE: VNX55E and VNX55EX are normally operated at 10 amps DC per module, to
maximize silica removal and boron removal.
This manual suits for next models
8
Table of contents
Popular Control Unit manuals by other brands

Staubli
Staubli CombiTac direqt Assembly instructions

Telcoma Automations
Telcoma Automations T10 FM400 Operation and Programming Instructions

Belden
Belden lumberg automation LioN-P 0980 ESL 300... manual

Pentair
Pentair FLECK 5000 Service manual

Lite-Puter
Lite-Puter LPTC801 quick start guide

Beninca
Beninca THINK operating instructions