IOTA ICE-80 User manual

IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of
electrical shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and
by disconnecting the unit connector.
3. CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4. The ICE-80 is for use with grounded, UL Listed, damp location rated and enclosed and gasketed fixtures
except in heated air outlets or hazardous locations.
5. The ICE-80 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. Do not mount near gas or electric heaters.
7. The ICE-80 should be mounted in locations and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
8. The ICE-80 is suitable for mounting in the ballast compartment only.
9. The ICE-80 will cold strike and operate
one
28W or 54W T5 or 2´-8´ T8-T12 or
two
2´-4´ T8-T12 instant
start, rapid start, U shape or circline fluorescent lamps, including energy saving and long 4 pin compact
lamps for 90 minutes.
10. The ICE-80 is compatible with most A.C. ballasts (including multiple lamp) as follows:
Magnetic ballasts – either one or two lamp emergency operation.
Electronic ballasts – one lamp emergency operation, consult Customer Service for two lamp emergency
operation wiring diagrams.
11. Suitable for use in damp locations and in enclosed and gasketed fixtures.
12. For use in -18°C minimum, 50°C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility
before final installation.
SAVE THESE INSTRUCTIONS
ICE-80ICE-80
ICE-80ICE-80
ICE-80
COLD-WEATHER SERIES D
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
THIS UNIT CONTAINS A
RECHARGEABLE NICKEL-
CADMIUM BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.

Page 2
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the ICE-80 unit connector is disconnected.
1. LAMPS OPERATED
The ICE-80 can be used with most 2′–8′ lamps. Refer to the chart below for the type of lamp(s) operated and the
number of lamps to be operated in emergency mode.
*The 6″violet leads provide the lamp selection option.The unit is shipped from the factory with the leads
disconnected and capped. When used with particular lamp types, violet leads should be connected to one another.
Refer to chart for lamp selection options.
2. MOUNTING THE ICE-80
Remove the ballast channel cover. Mount the ICE-80 in the ballast channel at least 1/2″away from the A.C. ballast(s).
When battery packs are remote mounted, the remote distance can not exceed ½ of the distance from ballast to
lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no
more than 25′remote distance, then the battery pack should not exceed 12½′. Under no circumstances should
the battery pack exceed a distance of 50′from the lamp.
3. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
4. INSTALLING THE CHARGE INDICATOR
Recessed Troffer Fixture
– Select a convenient location with proper clearance in the ballast cover and drill or
punch a 7/8″hole (½″knockout). Insert the 7/8″bushing into the hole. Push the plastic tube through the bushing.
Disconnect the leads from the LED housing and route the leads down the platic tube. Reconnect the leads to the
housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Push the entire
assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted
so that the Charge Indicator is within ¼″of the fixture lens.The Charge Indicator must be visible after installa-
tion. Refer to
Illustration 1
.
Strip Fixture
– Select a convenient location on the side of the fixture so the Charge Indicator can be seen after
installation. Allow for proper clearance inside the fixture and drill or punch a ½″hole. Disconnect the leads from the
LED housing. Push the LED housing into the 1/2″ hole until it is firmly locked in place. Reconnect the leads,
observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Refer to
Illustration 2
.
OPTION
LAMP TYPE EMERGENCY
OPERATION *VIOLET LEADS WIRING
DIAGRAMS
1
2
3
4
5
2´-4´ T8/T12 Single & Bipin Pin
5´-8´ T8/T12 Single & Bipin Pin
2´-4´ T8/T12 Single & Bipin Pin
2´-4´ 28W-39W T5
2´-4´ 54W T5
One Lamp
One Lamp
Two Lamp
One Lamp
One Lamp
Connected
Disconnected
Disconnected
Connected
Disconnected
1, 2, 3, 4, 5, 6, 7, 8
1, 2, 3, 5, 6
9, 10
1, 2, 3, 4, 5, 6, 7, 8
1, 2, 3, 4, 5, 6, 7, 8
6 18W-55W Long Compact One Lamp Disconnected 1, 2, 3, 4, 5, 6, 7, 8
5. INSTALLING THE TEST SWITCH
The test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip
fixture, preferably adjacent to the charge indicator. Drill or punch a ½″ mounting hole.
7/8" BUSHING
FIXTURE
BALLAST CHANNEL COVER
PLASTIC TUBE
CHARGE INDICATOR
LIGHT
FIXTURE LENS
Illustration 1 Recessed Troffer Fixture
FIXTURE
CHARGE
INDICATOR
LIGHT
(POS LEAD)
RED/BLK OR
RED W/CONNECTOR
WHITE/RED
LEAD
+ RED
Illustration 2 Strip Fixture
ICE-80
OBSERVE PROPER POLARITY
ICE-80

Page 3
BLACK
A.C. BALLAST
HOT A.C. LINE
WHT
WHITE
(120V) BLK
(277V) ORG
TEST SWITCH
COMMON
➀
Select proper voltage lead. Cap unused lead.
➀
WHT/BLK
WALL SWITCH
BLK/ORG
➁
For 120V installation, connect BLK/ORG to BLK.
For 277V installation, cap BLK/ORG.
➁
6. WIRING THE A.C. INPUT
A. The ICE-80 and A.C. ballast
must
be on the same branch circuit.
B. The ICE-80 requires an
unswitched
A.C. power source of either 120 or 277 volts. Select the proper voltage
lead and cap the unused lead.
C. When the ICE-80 is used with a switched fixture, the A.C. input to the ICE-80 must be connected ahead of the
fixture switch. Refer to
Illustration 3
for switched and unswitched fixture wiring diagrams.
NOTE: The ICE-80 will require a maximum power input of 100 watts when the internal heating element is active.
BLACK
A.C. BALLAST
HOT A.C. LINE
WHT
WHITE
(120V) BLK
(277V) ORG
TEST SWITCH
COMMON
➀Select proper voltage lead. Cap unused lead.
➀
WHT/BLK
BLK/ORG
➁
➁
For 120V installation, connect BLK/ORG to BLK.
For 277V installation, cap BLK/ORG.
Illustration 3 Switched Fixture Unswitched Fixture
ICE-80
ICE-80
7. LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for
lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to
anyone attempting to service the fixture.
8. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the ICE-80 unit connector.
OPERATION
Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended.The ICE-80 is in the
standby charging mode.The Charge Indicator will be lit providing a visual indication that the battery is being charged.
Emergency Mode – The A.C. power fails. The ICE-80 senses the A.C. power failure and automatically switches to the
Emergency Mode
. One or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C.
power is restored, the ICE-80 switches the system back to the
Normal Mode
and resumes battery charging. See page 1
of the Instruction Manual.
TESTING & MAINTENANCE
Pressing the Test Switch turns off the light on the Charge Indicator and forces the unit into emergency mode, interrupt-
ing power to the designated A.C. ballast. The emergency lamp is now being lit by the ICE-80 unit. After releasing the
Test Switch, the fixture returns to normal operation after a momentary delay.To simulate a “BLACK OUT” use the circuit
breaker to turn off A.C. power.
Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour
charge before conducting a one hour test.
The ICE-80 is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,
outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. One lamp should operate at reduced output.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 11/2hour discharge test. The unit should
operate as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.

Page 4
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
VIOLET
VIOLET
➂➂
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
RED OR
RED/BLK (+)
➃
➃
BLK/ORG
➄
➄
➁
➀
TYPICAL WIRING DIAGRAMS
For wiring diagrams of ballasts not shown, consult our Customer Service.
Rev. 021208
68180-041
1. ONE LAMP RAPID START BALLAST
2. TWO LAMP RAPID START BALLAST
3. TWO LAMP RAPID START BALLAST
4. THREE LAMP RAPID START BALLAST
7. ONE LAMP INSTANT START BALLAST
8. TWO LAMP INSTANT START BALLAST
9. THREE LAMP INSTANT START BALLAST
10. FOUR LAMP INSTANT START BALLAST
VIOLET
VIOLET
➂
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➀
➂
RED OR
RED/BLK (+)
➃
BLK/ORG
➃
➄
➄
➁
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
VIOLET
VIOLET
➂➂
TBTS / CHARGE
INDICATOR
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE/WHT
BLUE/WHT
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
COMMON
➁
➀
A.C.
Ballast
BLUE
BLUE
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
RED OR
RED/BLK (+)
➃
➃
BLK/ORG
➄
➄
➁
➀
VIOLET
VIOLET
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION IS
COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT WIRES TOGETHER.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➃
➂
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
RED
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
➃
RED OR
RED/BLK (+)
BLK/ORG
➄
➄
➅
➅
➂
➁
RED OR
RED/BLK (+)
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE
BLUE
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
➃
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
VIOLET
VIOLET
➂
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT WIRES TOGETHER.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➃
➄
BLK/ORG
➄
➅
➅
➂
➁
VIOLET
VIOLET
➂
➀SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT WIRES TOGETHER.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➃
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BLUE
BLUE
BLUE
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
➃
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
RED OR
RED/BLK (+)
➄
BLK/ORG
➄
➅
➅
➂
➁
VIOLET
VIOLET
➂
➀
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT WIRES TOGETHER.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➃
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
RED
RED
BLUE
BLUE
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast
➃
EMERGENCY
BALLAST
WHT/BLK
WHT/RED
RED OR
RED/BLK (+)
➄
BLK/ORG
➄
➅
➅
➂
➁
5. THREE LAMP RAPID START BALLAST
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
WHITE
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE RED
RED
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
COMMON
A.C.
Ballast
BLUE
BLUE
UNIT
CONNECTOR
TBTS/CHARGE
INDICATOR
VIOLET
VIOLET
EMERGENCY
BALLAST
BLACK (120V)
BLK/ORG
WHT/RED
RED OR
RED/BLK (+)
➂
ORANGE
ORANGE
YELLOW
YELLOW
ORG (277V)
WHT/BLK
➀
➁
➃
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➂
➃
➄
➁
➀
➄
ICE-80
ICE-80
ICE-80
ICE-80
ICE-80 ICE-80
ICE-80
ICE-80
CHARGE
INDICATOR
CHARGE
INDICATOR
CHARGE
INDICATOR
CHARGE
INDICATOR CHARGE
INDICATOR
CHARGE
INDICATOR
CHARGE
INDICATOR
CHARGE
INDICATOR
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
VIOLET
VIOLET
➂➂
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
COMMON
ORG (277V)
BLK (120V)
WHITE
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE BLUE
BLUE
RED
RED
YELLOW
YELLOW
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
UNIT
CONNECTOR
TBTS / CHARGE
INDICATOR
COMMON
➁
➀
A.C.
Ballast EMERGENCY
BALLAST
WHT/BLK
WHT/RED
RED OR
RED/BLK (+)
➃
➃
BLK/ORG
➄
➄
➁
➀
ICE-80
CHARGE
INDICATOR
6. FOUR LAMP RAPID START BALLAST
UNSWITCHED
COMMON
WHITE
BLACK (120V)
BLK/ORG
ORG (277V)
WHT/BLK
➀
LAMP
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLACK
WHITE
BROWN
BROWN
RED
RED
BLU/WHT
BLU/WHT
BLUE
BLUE/WHT
RED
YELLOW
COMMON
A.C.
Ballast
UNIT
CONNECTOR
TBTS/CHARGE
INDICATOR
VIOLET
VIOLET
EMERGENCY
BALLAST
WHT/RED
RED OR
RED/BLK (+)
RED/WHT
BLUE
BLUE
ORANGE
ORANGE
➂
YELLOW
YELLOW
SWITCHED
OR
UNSWITCHED
LINE
➁
➃
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER TO INSTALLATION
INSTRUCTIONS, LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS.
FOR 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR 277V INSTALLATION, CAP BLK/ORG.
TEST ACCESSORY LEADS-REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POLARITY WIRING.
➂
➃
➄
➁
➀
➄
ICE-80
CHARGE
INDICATOR
Table of contents
Other IOTA Security Sensor manuals
Popular Security Sensor manuals by other brands

Bacharach
Bacharach MGS-150 Installation and operation manual

jablotron
jablotron JA-181M manual

Panlux
Panlux SL2700 instructions

SMC Networks
SMC Networks PSE541 instruction manual

Endress+Hauser
Endress+Hauser SOP300 Brief operating instructions

urmet domus
urmet domus 1051 Installation, programming and functions manual