
6
THE GAS SAFETY (INSTALLATION AND
USE) REGULATIONS 1996.
It is the law that all gas appliances
are installed by a registered person, in
accordance with the above regulations.
Failure to install appliances correctly
could lead to prosecution. It is in your
own interest, and that of safety, to ensure
that the law is complied with.
Read these instructions carefully before
attempting to operate the appliance.
The family
is a fully automatic, wall mounted, room
sealed, fan assisted range of combination
boilers. When operating in winter mode,
the appliance provides central heating
as required and produces instantaneous
hot water upon demand. When operating
in summer mode, the central heating is
not operational however the appliance
continues to supply hot water whenever
it is required.
The
family is a fully automatic, wall mounted,
room sealed, fan assisted range of
system boilers. The boiler is fitted with
a divertor valve which enables the boiler
to be directly connected to a hot water
cylinder.
- a
demand of hot water will be sensed
by the appliance detecting water flow
(providing that the flow rate is above 2
l/m - 0.5 gal/min).
The fan will start and the burner will
light at full output. If the draw off rate is
near the maximum design flow rate the
appliance will run continuously at full
output until a tap is either turned off or
the flow rate is reduced in which case
the heat output will reduce accordingly
to maintain a steady temperature.
Hot water is made available almost
immediately at the appliance outlet, but
the final temperature and time taken
for the hot water to reach a tap depends
upon the potentiometer setting, the rate
at which water is drawn off, and the
length of the pipe between the boiler and
the tap.
When the tap is turned off, the appliance
will revert to C.H. mode (if set on winter
position) otherwise the burner will be
extinguished pending the next demand
for hot water.
- a demand for heating will be
sensed by the boiler, The pump will
start, and provide sufficient circulation
is detected, the fan will start and the
burner will light.
The heat output will be controlled by the
heating sensor and the user interface
control.
The first ignition of the boiler must
be carried out by qualified technical
personnel. Successively, if it is necessary
to start up the boiler again, adhere strictly
to the following instructions: open the
gas tap to allow the flow of the fuel.
Move the main switch of the system
to “ON”. When fuel is fed to the boiler,
a sequence of checks will be carried
out and the display shows the normal
condition of the functioning, always
indicating the pressure of the system. If
the blue luminous bar is on, this indicates
the presence of voltage.
Press the key
of the controls (pos. 2)
to activate the winter mode functioning
(heating and D.H.W.). The display will be
as shown in the figure.
Press the key
of the controls (pos. 2)
to activate the summer mode functioning
(only the production D.H.W.). The display
will be as shown in the figure.
Fig. 24
APRE
22
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
APRE
22
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
APRE
22
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
APRE
22
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)