
C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER MANUAL
INTEGRATED RECTIFIER TECHNOLOGIES, INC.
Doc #: APC0010
Rev. 3.0, November, 2004
Page 18 of 22
REGULAR MAINTENANCE & ADJUSTMENT
The basis for any effective CP system is routine documentation & maintenance. Despite the
rectifier maintaining the DC output “automatically”, it is recommended that the rectifier be
checked and adjusted if necessary at least twice per year. Some local regulatory bodies
require a monthly or semi-monthly check to ensure proper protection levels are being
maintained. These checks also allow you to ensure that the rectifier has not been damaged.
When completing this maintenance and adjustment check, it is recommended that all readings
and observations be recorded in the site file. With regular maintenance checks and by
maintaining good records, future troubleshooting and repair costs can be reduced.
Prior to arriving at the site for the rectifier maintenance check, it is recommended that the
technician review the existing rectifier site file to gain familiarization with the subject rectifier
and site conditions. Upon arriving at the rectifier site, a visual check should be completed to
determine if any changes have occurred. Things to look for are signs of new underground
construction, buildings, pipeline tie-ins, bonds, etc. Prior to adjustment of the rectifier, it is
recommended that structure potential readings be taken, to determine the adjustment level
required. Even if the potential levels are within the required range, the rectifier should still be
checked for proper operation.
When approaching the rectifier, ensure that no items have been placed near the rectifier
enclosure in such a manner as to block the venting, either on the bottom or sides. As the vent
openings on the rectifier enclosure are screened, there should be no refuse inside from birds
or larger insects. However, after opening the door of the enclosure, ensure that there has been
no significant accumulation of dirt, snow, or other small debris at the bottom of the enclosure,
which may adversely affect proper venting.
DO NOT INSTALL, REMOVE, or REWIRE
THIS EQUIPMENT WITH POWER APPLIED!!
Prior to any adjustment of the rectifier, measure and record the “As Found” readings of the
rectifier (DC voltage, DC amperage, etc.). Next, set the rectifier circuit breaker and the utility
disconnect to the “OFF” position to allow for a detailed rectifier inspection.
At least once a year the rectifier should be inspected for loose electrical connections that could
eventually cause damage to the electrical panel, wiring, or rectifier components. If an electrical
connection becomes loose, the resistance of the connection increases and causes it to heat
up. This additional heat will cause the connection to oxidize and become even higher resistant
until a failure occurs. The best way to check for a heated connection is with a temperature
probe, however, as these are not typically standard issue for Cathodic field maintenance, the
visual inspection method will suffice. First, visually inspect all of the main electrical
connections within the rectifier for signs of discoloration on the connection terminal, the
electrical panel, or the wire attached to the terminal. Key points to check are the DC output lug
terminal connections and the fuse holder connections. If you see a suspect connection, use a
wrench or other suitable tools to see if the connection is indeed loose. (Note: Be careful when
touching these types of connections with your hand as the temperature of loose high current
connections can cause a significant burn.) If you do find a loose connection, it should be
secured with suitable tools (make sure to secure both the front and rear of the double-nutted
panel connections). If a loose connection has already caused damage to the electrical panel,
the panel should be repaired or replaced, as re-tightening a connection on a degraded panel
will most likely still lead to a future failure.