Isimet RLA Series User manual

ISIMET
RLA Series Style 3
Residential Water Leak Detection
RLA-3
Installation,
Maintenance,
Operations,
and Start-up
Instructions
Read all instructions BEFORE installation and USE of Controller.
KEEP INSTRUCTIONS FOR FUTURE USE.
August 2015
DOC# 18031

Page 2
ISIMET
RLA Series Style 3 Controller
Installation, Maintenance, Operations, and Startup Instructions
Copyright © 2015 ISIMET/MAPA, LLC.
All rights reserved.
Patent 6,757,589 B1
6,990,393 B2
Other Patents Pending
This document is copyrighted. This document may not, in whole or part, be copied, duplicated, reproduced,
translated, electronically stored, or reduced to machine readable form without prior written consent from
ISIMET.
Although the material contained herein has been carefully reviewed, ISIMET does not warrant it to be free of
errors or omissions. ISIMET reserves the right to make corrections, updates, revisions, or changes to the
information contained herein.
ISIMET is a trademark of ISIMET/MAPA, LLC, an affiliate of WCM Industries, Inc.
Warranty:
ISIMET will repair or replace any defective parts or workmanship of this product for a period of one year from date of
installation. The Primary Operating P.C. Board has a two year limited warranty. Damage caused by incorrect installation or
improper usage is not warranted. Failure to follow recommended installation, operation, and/or maintenance procedures listed
in this manual may void product warranty. Recovery rights shall be limited to the total sum of the amounts paid for the
product by the purchaser.
Limits of Liability:
ISIMET's liability shall be limited to costs of repair or replacement parts. The Laboratory Service Panel and Utility Controller
are not intended for usage other than those expressly described in this manual. ISIMET shall not be liable for damage or injury
caused by the improper use of the product.
ISIMET does not warrant against or assume liability for failure of operation or lack of notification to secondary integrated
monitoring systems. The system should be thoroughly tested and adjustments made at time of initial operation. Periodic
testing should be conducted by the user to assure that all components function and operate according to specifications.
Care should be taken in the installation of this product. ISIMET shall not be liable for damage or injury caused from the
improper installation of the product.
Warranty is Subject to Compliance with Specific Installation Requirements.
EXTENDED WARRANTY:
ISIMET will extend the warranty period of the products when installation complies with all start up procedures and that a
factory authorized agent either performs or is in attendance during start-up of the system(s). Controllers, Companion and
Accessory Panels will be extended to a period of five years from date of installation. Except for ISIMET FLA, DLA, RLA and
other Units where automation systems are not common, Control System(s) must be interfaced with a building automation
system or other ISIMET approved time sequencing control for “non-use” system shutdown. All operating components of the
system must be ISIMET provided. Prescribed routine maintenance procedures must be performed per ISIMET
recommendations.
All Start-up and Routine Maintenance Documentation shall be per Factory Recommendation.
Further, required start-up and maintenance procedures must be performed as directed upon all affected systems. This
warranty shall only become enforceable upon issuance of application specific Extended Warranty Document. A copy of this
document should be maintained at all times at the location of the warranted systems.
DISCLAIMER OF IMPLIED WARRANTY:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION HEREIN. SELLER DISCLAIMS ANY
IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE FITNESS OF THE GOODS FOR ANY
PURPOSE, AND BUYER AGREES THAT THE GOODS ARE SOLD “AS IS.”
Printed in the United States

Page 3
Table of Contents:
Page
Warranty ........................................................................................................2
General Product Information .........................................................................4
Assembly, Compliance and Registration Information...................................4
Pre-Installation Information...........................................................................4
Model Number Description ...........................................................................5
Flush Mount Installation................................................................................6
Surface Mount Installation.............................................................................6
Installing the Electrical Conduit ....................................................................7
Wiring the Utility Controller .........................................................................7
Installing the Door Panel ...............................................................................8
Installing the Door Trim ................................................................................8
PLC Overview ...............................................................................................9
Connecting Controlled Services ....................................................................10
Battery Backup...............................................................................................10
Connecting Alarm & Monitoring Wiring......................................................11
Start-Up Checklist .........................................................................................11
Start-Up Test Preliminary Information..........................................................11
Start-Up Test..................................................................................................12
Equipment Operation.....................................................................................13
Troubleshooting.............................................................................................14
Equipment Maintenance ................................................................................15
ISIMET Contact Information.........................................................................16
Table of Figures and Reference Tables:
Page
Figure 1 - Model Numbers.............................................................................5
Figure 2 - Flush Mounted Controller.............................................................6
Figure 3 - Surface Mounted Controller..........................................................6
Figure 4 - Controller Knock-Out Holes.........................................................7
Figure 5 - Junction Box Wiring.....................................................................7
Figure 6 - Door Panel Installation..................................................................8
Figure 7 - Door Trim Installation...................................................................8
Table 1 - PLC Indicator Lights.....................................................................9

Page 4
General Product Information
The RLA Style 3 is intended as a control device to guard a residence from flooding due to domestic water leaks that may
occur when the residence is unoccupied. A latching solenoid valve will close, thus turning the water supply OFF.
Available options for the RLA Style 3 allow the controller to guard a part time or vacation residence from flooding due to
domestic water leakage that may occur due to freezing temperatures and also against seismic activity that may break piping
for gas and water service.
Construction
All electrical components are pre-assembled, wired, and mounted. The Electronic Controller is assembled within the
Utility Controller compartment.
The RLA Style 3 Controller has a powder coat finish. All panels and enclosures are constructed of welded 14-gauge sheet
metal.
Caution: Do not drop this assembly or expose it to the environment.
Assembly, Compliance and Registration Information
All Controllers are assembled to permit limited field configurations of the operating system. Options requiring additional
instructions and/or assembly parts are shipped within the component package. Refer to Equipment Specifications to verify
that ALL components conform to these requirements.
The output circuits of the Controller provide control signals to solenoids and relays to activate and engage the various
utilities. ISIMET provides a full line of Companion Enclosures and fittings. It is recommended that these items be included
in the system design, but when the installer elects to provide these fittings from other sources, compliance with product
specifications must be confirmed prior to installation.
Enclosed with this Manual is a separate registration form. The front of the form is for equipment warranty registration.
The back is a copy of the equipment start-up checklist. To ensure proper warranty of the product, it is important that you
complete both sides of the form and either mail or fax to ISIMET within 30 days of installation and start-up.
Locating and Positioning the Controller
Where applicable, verify ADA (Americans with Disabilities Act) dimensions and compliance requirements. For best
results: Install the Controller in the room where the utility services are controlled, at or near an exit, and accessible to
occupants of the room. Mount the vertical center of the service switches on the door panel to the ADA-required maximum
height.
The Door Panel and Trim Kit
The Trim Kits are packaged separately from the RLA Controller enclosure and have a protective wrapping. (Trim Kit not
provided with surface mounted units.) Verify installation requirements prior to installation of the unit.
Store the Door Panel and Trim Kit in a protected location, out of the weather, until installation.
Install the Door Panel onto the RLA Controller after ALL other wiring connections within the controller have been made.
Upon Receipt of Product
Each RLA Controller is assembled specifically for an individual application.
All primary components have the same code number.
Check components for damage. Notify ISIMET immediately of any damaged components.
Check package and product name plates to determine if all components were shipped correctly.
Store uninstalled components in a protected environment, out of the weather.
Note: Only qualified craftsmen licensed within the governing jurisdiction to perform the work associated with this
installation should install and/or service this equipment.

Page 5

Page 6
Installing the Enclosure
There are two options for mounting the RLA Controller:
Flush Mounted and Surface Mounted.
CAUTION: Provided mounting hardware must be used.
Flush Mounted
Prior to installation:
The Enclosure mounts between two standard
spaced wall studs within a minimum 4” wall cavity.
(Enclosure Dimension –16”x14”x4”)
If stud spacing is greater than that required for the
mounting of the controller, add studs to ensure a secured mounting.
The studs should be facing to facilitate securing the Enclosure.
Predetermine wall finish so that the face lip of the enclosure
aligns flush with the finished wall surface.
To install:
1. Using the self-starting screws (13), mount the flanges at
each side and at the top and bottom of the enclosure.
2. Attach the enclosure to the wall studs with field-provided
sheet metal screws per the drawing.
3. Level the enclosure.
Notes:
When the Door Panel is mounted onto the Enclosure,
it should protrude beyond the wall surface about ¼”.
Care should be taken at installation time to ensure that this
occurs.
A Flush Mounting Trim Flange is provided with each flush mounted unit.
Separate installation instructions and hardware are included with this flange.
Semi and Flush Trim add 3.5 inches to both Height and Width wall surface
dimensions.
It is the responsibility of the installer to verify finish wall dimensions.
Clearance around Enclosure:
Care should be taken to allow ½” clearance
from wall framing and sheet-rock or other wall
surface material around the outer surface of the
unit to permit the trim to be properly installed.
Surface Mounted
Prior to installation:
Wall finishes should be complete.
The wall cavity must have sufficient backing or support to
ensure a firm mounting of the enclosure to the wall surface.
To install:
1. Secure the surface mount flanges to the back of the
enclosure with the self-starting screws (13).
2. Use the field-provided screws to attach the enclosure by the
flanges to the wall surface.
3. Level the enclosure.
Figure 2
For best Flush Mounting
results, recess face of
enclosure’s lip
½ ” behind wall finish
Semi-Recess Enclosure Placement Note:
For Semi-Recess Units, the face of the
enclosure’s lip should be positioned
¼ ” beyond wall finish.
Figure 3

Page 7
Figure 3
Figure 5 - Junction Box
Installing the Electrical Conduit
Only one Knock-Out is provided from the factory on the top left corner of the RLA Controller.
Connect rigid conduit for the required 120 VAC electrical service at the top left as indicated in
Figure 4.
Conduit holes for wiring to Terminals 1 & 2 may be made on the top, bottom, or right side of the enclosure.
Important!
All local codes must be followed when connecting the conduit to the service panel.
Figure 4 –Controller
Knock-out
holes
Wiring the RLA Controller
Important!
Verify that the electrical supply is disconnected prior to
connecting wiring to the RLA Controller.
To wire the RLA Controller:
1. Remove the junction box cover from the panel
surface.
2. Make final connections to the 120 VAC electrical
service to wiring within the junction box. Verify that
line wiring (Black), neutral (White), and ground wire
(Green) are correctly connected. Minimum
recommended wire size is 14 AWG.
3. Replace the junction box cover before activating or
testing the unit.

Page 8
Installing the Door Panel
Figure 6
To install the Door Panel on the Enclosure:
1. Position the door at 90° –100° of enclosure. (STEP 1)
2. Slide top hinge pin onto fixed hinge post at top of door. (STEP 2)
3. Slide lower hinge pin toward lower spring hinge mechanism with hinge pin lever in retract position. (STEP 3)
4. With lower hinge pin in position, turn hinge pin lever outward and down, then turn inward to the extend lock position.
(STEP 4)
Installing Flush Door Trim
Figure 7
Prior to installing Door Trim, ensure that wall finishes are
complete and that the door panel has been installed.
To install the Flush Door Trim:
1. With the door in the open position, slide flush door
trim over enclosure. See Figure 7.
2. Align holes on enclosure with upper and lower holes
in door trim.
3. Insert four (4) 12-24 (provided) screws through
enclosure panel and tighten into door trim.
Notes: Holes in enclosure are slotted to allow installer to
adjust trim to wall finish.
Flush Trim adds 3 ½” to both Height and Width
of Wall Surface dimensions.

Page 9
PLC Overview:
Each RLA Style 3 Controller is equipped with a
Micro-PLC to control all of its functions.
The PLC comes programmed and wired from the
factory and should not be altered in any way.
Note: All units will be shipped with the PLC
Mode switch in the STOP position. It should
remain in this position until Start-Up testing is
going to be performed. Once ready to test the
system, the switch must be set to the RUN
position for the controller to function.
Indicator Light
Description of Status When Light is On
PWR
PLC has 24VDC from Power Supply
RUN
PLC is set to RUN Mode and is operational
ERR
PLC Processor has incurred an error
X1
Door Panic Button is being pressed
X2
Alarm signal being received (Dry-Contact)
X3
Leak Sensor signal being received (Dry-Contact)
X4
Leak Sensor signal being received (Dry-Contact)
X5
Freeze Sensor signal being received (Dry-Contact)
X6
Seismic Sensor signal being received (Dry-Contact)
X7
Not Used
X8
Not Used
Y1
Circuit 1 active (Water - Supply)
Y2
Circuit 2 active (Water - Drain Down)
Y3
Circuit 3 active (Gas Supply)
Y4
Circuit 4 active (Electrical Shunt)
Y5
Beacon Output (ON with service)
Y6
Beacon Output (OFF with service)
Table 1

Page 10
Connecting Controlled Utility Services
The RLA Controller is not provided with electrical solenoids, contactors, or relays. ISIMET provides a
full line of Companion Enclosures and fittings. It is recommended that these items be included in the
system design, but when the installer elects to provide these fittings from other sources, compliance with
product specifications must be confirmed prior to installation. Connect wiring for these devices to
Terminal 2 at designated posts.
NOTE: Place relays and solenoids in areas that are easily accessible for future maintenance.
Touch Panel Switch to Terminal 2 Configuration: (typical)
Typical Usage Operated By Standard Application
Terminal
2
Water - Supply
Leak, Freeze & Seismic Sensor
Circuit 1
Post 1
Water - Supply
Leak, Freeze & Seismic Sensor
Circuit 1
Post 2
Water - Drain Down
Freeze & Seismic Sensor
Circuit 2
Post 3
Water - Drain Down
Freeze & Seismic Sensor
Circuit 2
Post 4
Gas - Supply
Seismic Sensor
Circuit 3
Post 5
Gas - Supply
Seismic Sensor
Circuit 3
Post 6
Electrical Shunt
Seismic Sensor
Circuit 4
Post 7
Electrical Shunt
Seismic Sensor
Circuit 4
Post 8
NOTE: Use of primary outputs may be changed to accommodate specific project requirements.
Water Solenoids used with the RLA Controller should be ISIMET S-220 Series General Service Brass
Valves with 12-vdc coils. These coils are polarized and must be connected correctly to the Output
Terminal in order to function as intended.
Connect Supply Solenoid to the ‘ON w/Latch Terminals.
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are
similarly color coded. Piping and wiring for solenoids should follow details provided with the solenoids.
Gas Solenoids used with the RLA Controller should be ISIMET S-300 Series Gas Service Valves with
12-vdc coils. These coils are polarized and must be connected correctly to the Output Terminal in order
to function as intended.
Connect Supply Solenoid to the ‘ON w/Latch Terminals.
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are
similarly color coded.
Piping and wiring for solenoids should follow details provided with the solenoids.
If optional shunt electrical is utilized, make connections at output circuit terminal on 7 and 8. Must use
single pole relay with N/O and N/C contacts to shunt electrical.
NOTE: Internet connection with remote access available. Refer to User’s Guide
BATTERY BACK UP CONNECTION: (Recommended)
This unit has been shipped with the battery disconnected to
prevent discharge during shipment. Connect the RED
battery backup wire to the positive (+) terminal, and the
BLACK backup wire to the negative (-) terminal. If power
is lost for an extended period, it is normal for the battery to
need recharging. This is done by the ISIMET system, but as
the battery is a sealed type, it MUST be trickle-charged.
This charging may take as long as eight hours. The system
may be used as normal during this time.

Page 11
Connecting Alarm Wiring
Alarm Input
The unit will not operate properly without an “Alarm” input signal.
Providing an input signal from the Alarm System at Terminal 1 will notify the RLA Controller if the
residence is occupied or not.
Start-Up Checklist:
A separate Start-Up Test Sheet is provided with the installation CD. The tests described herein
and in those procedures should be followed prior to placing the unit into operation. If you do not
have on hand this CD and/or Start-up sheet, you may retrieve a copy from your local factory
representative.
Caution!
Verify that ALL installation procedures and Line Voltage, Solenoids, and/or Remote Relays
conform to Equipment Specifications.
□Examine electrical wiring at junction box to verify that ALL wiring is correctly connected.
□Examine Terminal 1 and Terminal 2 to assure that wiring has been properly connected.
Test Output circuits at Terminal 2 to verify that field wiring or connected devices are wired
correctly. A direct short or input voltage at the output circuit will cause damage to the PLC and
Controller.
□Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected.
□Examine Door Panel factory wiring to ensure that it was not damaged or loosened during shipping
or installation.
□For Building Alarm System, verify that wiring connections, voltage requirements and alarm system
conform to unit specifications.
□Remove all dust and construction debris prior to proceeding.
Start Up Test Preliminary Information
Caution!
Do not proceed with equipment start-up until the Start-Up Checklist has been completed.
Before commencing these Start-Up tests, turn the control switch to the OFF position.
This unit was factory tested, but the manufacturer recommends that the installer perform these tests to
ensure that the unit did not sustain damage during shipment or installation.
Perform Start-Up Tests with the Door Panel open.
With the control switch ON, “PWR” LED on the PLC should illuminate. If not, check circuitry
for 24VDC power at Power Supply.
If after performing these tests and verifying operation, if the Unit fails to function contact an
ISIMET factory representative.

Page 12
Start-Up Tests
A. Testing the Control Wiring and Service Switches
1. Turn the control switch to the ON position. Voltage should read 120 VAC. If it does not, consult an
electrician before continuing this testing.
2. From the System Enable Screen (Refer to Users Guide) turn the first service button to the ON Position.
3. The button will turn green and the corresponding LED on the PLC will illuminate.
Using testing probes, verify that the corresponding terminal posts at Terminal 2 are energized.
4. Repeat steps 2 and 3 for the remainder of the service switches.
5. Turn all service switches ON. All services should be ON. All green indicating lights should be
illuminated. Verify ALL power loads with test probe.
6. Turn service switches OFF.
B. Testing the Panic Button
1. If the unit is integrated with a monitoring system:
a. Press and release the red Panic Button.
b. Verify that all Solenoids have been deactivated.
2. Press the Reset System button on the screen.
NOTE: Electrical Service will not shut down with Panic Button. Electrical Service will only shut down
with seismic activity.
C. Testing the Building Alarm Input signal
The unit has been factory tested to assure that the “Alarm” Input perform correctly. Field verify that
wiring to Terminal 1 is connected to the proper posts.
D. Testing the Building’s Utility Systems
1. Turn ALL control switches ON.
2. Field-test ALL utility and appliance outlets to confirm that services have become active.
3. Turn the switch for each utility to OFF. Verify that the specific utility outlets are not active or “ON”.
E. Test Completion
The unit should now be fully operable. If it is not, contact an ISIMET Service Representative.
1. Turn the Control Switch OFF.
2. Reconnect ALL integrated services.
3. Replace ALL panels and covers.
4. Turn the Control Switch ON.
5. Close and lock the Door Panel.

Page 13
Equipment Operation
A dry-contact Input from a Building Alarm Signal connected to Terminal 1 will turn ON the Unit, placing
it in the OPERATE Mode. Removal of this signal will turn OFF the OPERATE Mode and turn ON the
SERVICE ON Mode.
The Unit may also incorporate freeze protection devices. A device similar to a thermometer with dry-
contact outputs that close upon a set low temperature will turn the Unit OFF. Additional latching
solenoid(s) could be incorporated into the system that opens upon the un-latch sequence, thus partially
draining the piping system.
The Unit may also incorporate a seismic sensor that will transmit a signal to turn OFF services to a
facility that if left on after a seismic event with potential breakage in piping or circuits may cause damage
to the facility. Integral time delay programming insures that brief seismic or similar activity will not affect
services.
To Activate One or More of the Services Controlled by the Unit:
(Refer to Users Guide)
1. From the Home Screen press Start System button.
2. Turn ON corresponding switch for the service you wish to activate.
To Turn a Service OFF:
Turn the appropriate switch to OFF.
Note:
A service left ON remains ON until its switch is turned OFF unless the Panic button is depressed
(Excluding Electrical Service), System Shutdown is pressed, or line voltage is removed from the
controller (When used with Battery Backup).
In Case of an Emergency:
Press the red panic button on the door panel. This will disable the panel and ALL services. Once the panic
button is pressed the Passcode must be re-entered to reset from panic. Also, the Panic Screen will remain
on until reset is accomplished.

Page 14
Troubleshooting Guide
If the Utility Controller fails to energize, follow these procedures:
Verify that the Controller has correct line voltage connected. With the control switch in the ON
position, the PLC “PWR” light should be illuminated. If it is not, check the wiring connections.
Remove the wiring junction-box cover and examine wiring connections.
Verify that Touchscreen turns on and initializes.
Touchscreen should start-up on the Home Screen.(Refer to Users Guide)
Verify that PLC Mode switch is set to “RUN” position.
Verify that the Door Panel plug is securely connected to the door terminal.
Check the wiring terminals on the door panel to verify that none has become damaged or disconnected
during installation. Reconnect, if necessary.
If services do not turn on with switches:
1. Verify that PLC Mode switch is set to “RUN” position.
2. Verify proper voltage at corresponding posts on Terminal 2.
3. If you do not read the correct voltage at the terminal posts, contact an ISIMET Service
Representative.
4. If you read the correct voltage, test the remote relay and/or solenoids to verify that they are
operational.
In many cases, failure of the system is the result of improper connection of a remote service or device such
as a remote relay, solenoid or building alarm system. Refer to Equipment Specifications to confirm that
correct connections to these services and devices have been made.
Notes:
Damage to the Electronic Controller and other components can occur from improperly connecting the
services, overloading the output circuits, or failing to follow all start-up tests and checklists.
In ALL cases, if the system fails or you have questions about the equipment, contact an ISIMET
Service Representative.
If the results of all test procedures are positive but utilities will not activate, ISIMET recommends that
you examine and test the various utility services controlled by the unit to verify that they are
operational and active.
If utilities or controlled devices remain operational after the service switch is disengaged, check for the
following before placing the unit into full operation:
A defect in the remote relay or solenoid
Tampering
The remote relay unit has a control switch with a manual operation position and the switch is in the
manual position.
If utilities or devices continue to be active or if you have a question about the operation of the unit,
contact an ISIMET Service Representative immediately.

Page 15
Equipment Maintenance
The Utility Controller should have semi-annual inspections.
ISIMET recommends opening the service panel and turning OFF the control switch prior to long
periods of inactivity in the building.
Prior to anticipated activity within the building, ISIMET recommends that you conduct a brief test
of the control system by performing Start-Up Test Procedure A and Step 1 of ProcedureB.
If examination of the unit indicates tampering, ISIMET recommends that you first review the Start-
Up Checklist, then conduct ALL Start-Up tests.
ISIMET recommends that the door panel key be kept in a secured location. The door panel key
should be available only to those needing access to the interior of the unit for the purposes of
maintenance or service. ISIMET recommends that the door panel remain locked unless service is
performed.
If you have any questions regarding the operation and maintenance of the RLA Controller, please
contact an ISIMET Service Representative.
The enclosure has a NEMA 1 rating. It is not intended for use in wet areas. Exercise caution to prevent
exposure of the interior compartment of the enclosure to moisture. If moisture is present within the
enclosure, ISIMET recommends that the control switch be turned OFF, power be disconnected from
the unit until the source of the moisture is determined, and all moisture is removed from the
compartment.
The electronic controller (PLC) is sensitive to moisture, dust, debris and other air-borne particles. Do
not expose the interior compartment of the enclosure. During the semi-annual inspection, if dust or
other material is present, ISIMET recommends that you remove all foreign matter before operating the
unit.
If the Unit fails to operate, we recommend that you check the power supply to the unit. With the
control switch in the ON position, the PLC “PWR” light should be illuminated if power is on to the
unit. If not, check the service breaker.
If the unit still fails to operate, we recommend that you contact your local Service Representative.
Removing the Door Panel
Before removing the Door Panel, turn power OFF at the control switch, then disconnect the plug from
the terminal within the enclosure.
Follow steps 1 –4 in reverse as shown in Figure 6.
Instructions for Re-coating the Enclosure
If the finish surface of the enclosure or door panel becomes scratched, follow this procedure to repair
the surface.
Most standard, good quality paints can be used to re-coat the polyester powder finish.
For best results, correct surface preparation before re-coating is essential. Follow instructions
provided by your paint manufacturer.
Wipe surfaces to be painted with either xylene or lacquer thinner solvent.
Allow surface to flash dry prior to painting.
Follow paint manufacturer’s instructions for applying paint.
Allow paint to cure adequately. Consult the paint manufacturer for proper cure time and hardness.

Page 16
ISIMET believes that sole and local authority means that the primary operator or the
instructors should have the sole authority to start and stop the utility services within
the immediate area of use during normal usage. This should distinguish this type of
operating environment from that where a single emergency shut-down device is
located remotely from the areas of use. As an example, the ISIMET system is not
specifically intended for use in applications where a master shut-down and re-instate
device is located away from areas of normal use. ISIMET’s opinion is that in such
cases there is risk that the operator of the system during re-start may inadvertently
activate utilities in an unoccupied area that is remote from the present occupancy,
thus creating the risk of injury and/or fire where the utility is fuel gas.
ISIMET/MAPA, LLC
103 W. CJ Wise Parkway
PO Box 129
Naples, TX 75568
(903) 897-0737
Toll Free (866) 897-0737
Fax (903) 897-0740
www.ISIMET.com
Innovative Systems
Integrating
Mechanical and Electrical
Technology
This manual suits for next models
1
Table of contents