Islandaire 6041228 User manual

Programmable
(7 day, 5-1-1 day or Non-Programmable)
Wired Thermostat
6041228
Installaon and Operaon Manual
6140444 Rev. 04/09/21


Descripon
Gas or Oil Heat Yes
Electric Furnace Yes
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (With Electric Aux.) Yes
Heat Pump (With Gas Aux.) No
Mul-Stage Systems No
Heat Only Systems - Floor or Wall Furnace Yes
Cool Only Systems Yes
High and Low Fan Speed Yes
Millivolt No
Emergency Heat No
Convenonal Single-Stage Furnace Yes
Geothermal Yes
Remote Temperature Sensor Yes
Table of Contents page
Thermostat Applicaon Guide
Installaon Tips 2
Thermostat Quick Reference 6
Wiring 7
Wiring Diagrams 9
Technician Setup 11
Time Seng/Programming 15
Programming 16
Specicaons 20
Hardwire (Common Wire)
Hardwire (Common Wire) with
Baery Backup
A trained, experienced technician
must install this product.
Carefully read these instrucons. You
could damage this product or cause
a hazardous condion if you fail to
follow these instrucons.
Power Type
1
Installaon and Operaon Manual

Wall Locaons
The thermostat should be installed approximately 4 to 5 feet above the oor. Select an area
with average temperature and good air circulaon.
Installaon Tip
Pick an installaon locaon that is easy for
the user to access. The temperature of the
locaon should be representave of the
room.
Do not install
thermostat in locaons:
• Close to hot or cold
air ducts
• That are in direct sunlight
• On an outside wall
• In areas that do not
require condioning
• Where there are dead
spots or dras
(i.e., in corners or behind
doors)
• Where there might be
concealed chimneys
or pipes
2
Installaon Tips

Installaon Manual
Subbase Installaon
Horizontal Mount
Vertical Mount
1
2
For vercal mount, put one screw on the top
and one screw on the boom.
For horizontal mount, put one screw on the le
and one screw on the right.
Electrical Hazard
Failure to disconnect the power before
beginning to install this product can cause
electrical shock or equipment damage.
Mercury Noce
All of our products are mercury free.
However, if the product you are replacing
contains mercury, dispose of it properly.
Your local waste management authority can
give you instrucons on recycling and proper
disposal.
3
Installaon Tips

Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat,
then push gently unl the thermostat snaps in place.
4
Installaon Tips

Baery Installaon
1.5V AAA 1.5V AAA
Important:
Insert two AAA Alkaline baeries
(included). High quality alkaline
baeries are recommended.
R
GL
GH
C
O
B
W
Y
Connect R and C terminals to 24V power.
Note: The C (common wire) does not have to be con-
nected when the thermostat is powered by baeries.
Baery installaon is oponal if thermostat is hardwired.
Note: Installing baeries will enable the thermostat to
remember the program that you have set even if there
has been a power outage.
High quality alkaline baeries are recommended.
Rechargeable baeries or low quality baeries do
not guarantee a 1-year life span.
S1
S2
5
Installaon Tips

Geng to know your thermostat
1
5
4
32
LCD
Fan Switch
System Switch
Setpoint Buons
Menu Buon
Indicates the
current room
temperature
Displays current
day of week
and me
System Operaon
indicators: On will
display when Cool or
Heat mode is selected
Low Baery
indicator:
Replace baeries
when indicator
is shown
1
2
3
4
Press the + or - buttons to select the desired room
temperature.
LCD
1
AUTO will turn the fan on only when the heating
or cooling system is on. Select LOW or HIGH for
the fan to run continuously at the selected speed.
Fan Switch
2
3
4
Selects the operation mode on your HVAC system.
Selecting HEAT turns on the heat mode. Selecting
COOL turns on the cool mode. Selecting OFF turns
both heating and cooling o.
System Switch
Setpoint Buons
5
Time Period indicator:
Indicates current
program me period
(Wake, Leave, Return, Sleep)
Press the Menu Button to create or modify the
thermostat program schedule.
5Menu Buon
Displays the user
selectable setpoint
temperature
6
Thermostat Quick Reference

Wiring
This thermostat is shipped from the factory to operate a convenonal heang and cooling
system. This thermostat will also operate a heat pump system. See the “heat pump”
conguraon step on page 10 of this manual to congure the thermostat for heat pump
applicaons.
If you are replacing a thermostat, make note of the terminal connecons on the thermostat
being replaced. In some cases the wiring connecons will not be color coded. For example,
the red wire may not be connected to the R terminal.
Terminal 1 Heat 1 Cool
Convenonal System
1 Heat 1 Cool
Heat Pump System
2 Heat 1 Cool
Heat Pump System
R Transformer power Transformer power Transformer power
CTransformer common Transformer common Transformer common
O Energized in cooling Energized in cooling Energized in cooling
BEnergized in heang Energized in heang Energized in heang
GL Fan Relay, Low Fan Relay, Low Fan Relay, Low
GH Fan Relay, High Fan Relay, High Fan Relay, High
W Convenonal heat N/A Emergency heat
YEnergized in cooling Energized in heat & cool Energized in heat & cool
S1 Indoor Remote Sensor Indoor Remote Sensor Indoor Remote Sensor
S2 Indoor Remote Sensor Indoor Remote Sensor Indoor Remote Sensor
7
Wiring

Wiring Tips
Power Connecons
The thermostat can be either baery
powered, or hard-wired to power by
connecng supply voltage wire (red) and
common wire to the RH and C terminals,
respecvely, on the base.
Note: Installing baeries will enable the
thermostat to remember the program
that you have set even if there has been a
power outage.
Installaon Tip
Electrical Hazard
Failure to disconnect the power
before beginning to install this
product can cause electrical shock or
equipment damage.
Note:
When connecng the 6041228
thermostat to a PTAC, refer to the
PTAC unit’s instrucons to enable
remote thermostat operaon.
Wire Specicaons
Use shielded or non-shielded
18-22 gauge thermostat wire.
Remote Temperature Sensor
Connecons
Use the S1 and S2 screw terminals to
connect the oponal indoor remote
temperature sensor (Islandaire part no.
6040912). Indoor remote sensor wires
must be separated from the thermostat
wires.
Warning:
All components of the control
system and the thermostat
installaon must conform to
Class ll circuits per the NEC Code.
THERMOSTAT
REMOTE TEMPERATURE
SENSOR
P/N 6040912
S1 S2
8
Wiring

R
Y
W
C
GL
GH
C
R
L1
L2
COMPRESSOR
RELAY
HEAT RELAY
FAN LOW RELAY
FAN HIGH RELAY
1
C
R
L1
L2
COMPRESSOR
RELAY
HEAT RELAY
FAN RELAY
1
2
R
Y
W
C
GL
GH
O/B
3
3
O/B
Typical 1H/1C Convenonal System: 2 Speed Fan
1
2
3
Power supply
Splice together GL and GH wires.
O and B terminals not used.
Typical 1H/1C Convenonal System: 1 Speed Fan
9
Wiring Diagrams

C
R
L1
L2
COMPRESSOR
RELAY
CHANGEOVER VALVE
FAN LOW RELAY
FAN HIGH RELAY
1
3
C
R
L1
L2
COMPRESSOR
RELAY
CHANGEOVER VALVE
FAN LOW RELAY
FAN HIGH RELAY
1
B
3
EMERGENCY
HEAT RELAY
R
Y
W
C
GL
GH
B
R
Y
W
C
GL
GH
CHANGEOVER VALVE
OO
CHANGEOVER VALVE
Typical 1H/1C Heat Pump System: 2 Speed Fan Typical 2H/1C Heat Pump System: 2 Speed Fan
1
2
3
Power supply
Cap off W
Terminal B or O is used on Heat Pump Systems;
B is energized in heang, O is energized in cooling.
2
Note:
Most PTAC systems support two speed fan operaon. In a single speed
fan PTAC system or convenonal single speed fan system, the GL and GH
wires should both be ed to the Fan Wire (green).
10
Wiring Diagrams

Technician Setup Menu
This thermostat has a technician setup menu for easy installer conguraon. To set up the
thermostat for your parcular applicaon:
1. Press the Menu buon.
2. Press and hold the Tech Set buon for three seconds. This three second delay is
designed so that homeowners do not accidentally access the installer sengs.
3. Congure the installer opons as desired using the table below. Use the “+” and “-” keys
to change sengs and to move from one step to another. Note: Press the Done key to
exit Tech Setup Menu.
Tech Setup Steps LCD Will Show Adjustment Opons Default
Filter Change
Reminder
This feature will ash
a reminder aer the
elapsed run me to
remind the user to
change the lter. A
seng of “OFF” will
disable this funcon.
You can adjust the
lter change reminder
from “OFF” to 2000
hours of fan runme
in 50 hour increments.
Room
Temperature
Calibraon
This feature allows the
installer to change the
calibraon of the room
temperature display.
For example, if the
thermostat reads 70°
and you would like it to
read 72°, then select 2.
°F
You can adjust the
room temperature
display to read up to
3˚ above or below
the factory calibrated
reading.
°F
Minimum
Compressor
On Time
This feature allows the
installer to select the
minimum run me
for the compressor.
For example, a seng
of 4 will force the
compressor to run for
at least 4 minutes every
me the compressor
turns on, regardless of
the room temperature.
MinCom On
You can set the
minimum compressor
run me to “OFF”, “3”,
“4”, or “5” minutes. If
3, 4, or 5 is selected,
the compressor will
run for at least the
selected me before
turning o.
MinCom On
11
Technician Setup

Tech Setup Steps LCD Will Show Adjustment Opons Default
Compressor
Short Cycle
Delay
The compressor short
cycle delay protects the
compressor from short
cycling. This feature
will not allow the
compressor to be turned
on for 5 minutes aer it
was last turned o.
ComDelay
Selecng ON will not
allow the compressor
to be turned on for 5
minutes aer the last
me the compressor
was switched o.
Select OFF to remove
this delay.
ComDelay
Heat Pump When turned on the
thermostat will operate
a heat pump. Y will be
the rst stage of heat
& cool, W will be the
second stage of heat.
OFF congures the
thermostat for non
heat pump systems.
ON congures the
thermostat for heat
pump systems.
Cooling
Swing
The swing seng,
oen called “cycle rate”,
“dierenal” or “anci-
paon”, is adjustable. A
smaller swing seng
will cause more frequent
cycles and a larger swing
seng will cause fewer
cycles.
CoolSwing
The cooling swing
seng is adjustable
from 0.2° to 2°. For ex-
ample: A swing seng
of 0.5° will turn the
cooling on at approxi-
mately 0.5° above the
setpoint and turn the
cooling o at approxi-
mately 0.5° below the
setpoint.
CoolSwing
12
Technician Setup Menu

Tech Setup Steps LCD Will Show Adjustment Opons Default
Heang
Swing*
The swing seng,
oen called “cycle rate”,
“dierenal” or “anci-
paon”, is adjustable. A
smaller swing seng
will cause more frequent
cycles and a larger swing
seng will cause fewer
cycles.
Heat
Swing
The heang swing
seng is adjustable
from 0.2° to 2°. For
example: A swing
seng of 0.4° will
turn the heang on at
approximately 0.4° be-
low the setpoint and
turn the heang o
at approximately 0.4°
above the setpoint.
Heat
Swing
Heang
Temperature
Setpoint
Limit
This feature allows you
to set a maximum heat
setpoint value. The
setpoint temperature
cannot be raised above
this value.
Use the “+” or “-” key
to set the maximum
temperature setpoint:
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
Cooling
Temperature
Setpoint
Limit
This feature allows you
to set a maximum cool
setpoint value. The
setpoint temperature
cannot be raised above
this value.
Use the “+” or “-” key
to set the maximum
temperature setpoint:
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
F or C Select F for Fahrenheit
temperature read out.
Select C for Celsius tem-
perature read out.
Use the “+” or “-”
key to select F for
Fahrenheit or C for
Celsius.
* The second stage of heat will turn on at 2x the swing seng. The second stage will turn o when
1x the swing is reached. For example, if the swing seng is 0.8° for heang and the thermostat is
set at 70 °F, the rst stage will turn on at approximately 69.2 °F. The second stage will turn on at
68.4 °F and the rst will turn o at 70.8 °F.
13
Technician Setup Menu

Tech Setup Steps LCD Will Show Adjustment Opons Default
12 or 24
Hour Clock
You can select either a
12 or 24 hour clock.
Use the “+” or “-” key
to select 12 or 24 hour
clock.
Electric/Gas This seng allows the
thermostat to operate
the fan during a call for
heat. For systems that
control the fan during
a call for heat, put
the switch in the GAS
posion.
Most PTAC systems
will require ELEC Fan
Operaon Setup. The
thermostat operaon
switch should be put
in the ELEC posion.
Program
Opons
You can congure this
thermostat to have a 7
day program, a 5+1+1
program, or as non-
programmable.
Use the “+” or “-” key
to select 7d for 7 days,
5d for 5+1+1, or 0d for
non-programmable.
14
Technician Setup Menu

Set Time
Follow the steps below to set the day of the week and current me:
1. Press the Menu buon.
2. Press Set Time buon.
3. The day of the week will be ashing. Use the “+” or “-” key to select the current day of
the week.
4. Press the Next Step buon.
5. The current hour will be ashing. Use the “+” or “-” key to select the current hour. When
using the 12 hour me seng, ensure “AM” or “PM” is appropriately selected.
6. Press the Next Step buon.
7. The current minutes will be ashing. Use the “+” or “-” key to select the current minutes.
8. Press the Done buon.
Programming
The 6041228 Thermostat is shipped with an energy saving default program. The thermostat
can be re-programmed as described in the paragraph entled “Set Program Schedule”.
There are two program schedule opons:
• 7 days - Each day of the week programmed individually
• 5+1+1 - All weekdays have the same program, separate programs for Saturday and Sunday
Alternavely, the thermostat can be set to non-programmable (manual temperature
control). Refer to the Technician Setup Menu secon under the “Program Opons” step and
set to “0d”.
For the 7 day and 5+1+1 programming opons, there are four me periods:
• Wake
• Leave
• Return
• Sleep
15
Time Seng/Programming

Default Programming
Factory Default Program
Day of
Week Time Period Time
Setpoint
Temperature
(Heat)
Setpoint
Temperature
(Cool)
Weekday
Wake 6 AM 70°F (21°C) 75°F (24°C)
Leave 8 AM 62°F (17°C) 83°F (28°C)
Return 6 PM 70°F (21°C) 75°F (24°C)
Sleep 10 PM 62°F (17°C) 78°F (26°C)
Saturday
Wake 6 AM 70°F (21°C) 75°F (24°C)
Leave 8 AM 62°F (17°C) 83°F (28°C)
Return 6 PM 70°F (21°C) 75°F (24°C)
Sleep 10 PM 62°F (17°C) 78°F (26°C)
Sunday
Wake 6 AM 70°F (21°C) 75°F (24°C)
Leave 8 AM 62°F (17°C) 83°F (28°C)
Return 6 PM 70°F (21°C) 75°F (24°C)
Sleep 10 PM 62°F (17°C) 78°F (26°C)
16
Programming

Set Program Schedule (7 Day Schedule)
To customize your 7 day program schedule, proceed as follows:
1. Set the System Switch to either Heat or Cool. Note: You have to program heat and cool
separately.
2. Press the Menu buon.
3. Press Set Schedule buon.
4. Monday (Mon) is displayed and the me seng will be ashing; the “Wake” me period
icon is displayed at the boom of the screen. Use the “+” or “-” key to set the desired
Wake me. When using the 12 hour me seng, ensure “AM” or “PM” is appropriately
selected.
5. Press the Next Step buon.
6. The “Set At” temperature will be ashing. Use the “+” or “-” key to select the desired
temperature seng for the Wake me period.
7. Press the Next Step buon.
8. Repeat steps 4 through 7 for that day’s Leave, Return and Sleep me periods.
9. Press the Next Step buon.
10. Repeat steps 4 through 9 for the remaining days of the week.
11. Press the Done buon.
Note: Repeat this process for heat and cool separately.
17
Programming

Set Program Schedule (5+1+1 Schedule)
To customize your 5+1+1 day program schedule (weekday, Saturday, Sunday), proceed as
follows:
1. Set the System Switch to either Heat or Cool.
Note: You have to program heat and cool separately.
2. Press the Menu buon.
3. Press Set Schedule buon.
4. “Mon Tue Wed Thu Fri” is displayed and the me seng will be ashing; the “Wake”
me period icon is displayed at the boom of the screen. Use the “+” or “-” key to set
the desired Wake me. When using the 12 hour me seng, ensure “AM” or “PM” is
appropriately selected.
5. Press the Next Step buon.
6. The “Set At” temperature will be ashing. Use the “+” or “-” key to select the desired
temperature seng for the Wake me period.
7. Press the Next Step buon.
8. Repeat steps 4 through 7 for that day’s Leave, Return and Sleep me periods.
9. Press the Next Step buon.
10. Saturday (Sat) is displayed and the me seng will be ashing; the “Wake” me period
icon is displayed at the boom of the screen. Repeat steps 4 through 9 for Saturday’s
Leave, Return and Sleep me periods.
11. Press the Next Step buon.
12. Sunday (Sun) is displayed and the me seng will be ashing; the “Wake” me period
icon is displayed at the boom of the screen. Repeat steps 4 through 9 for Sunday’s
Leave, Return and Sleep me periods.
13. Press the Next Step buon.
14. Press the Done buon.
Note: Repeat this process for heat and cool separately.
18
Programming
Table of contents
Other Islandaire Thermostat manuals