
1700 SERIES INSTALLATION INSTRUCTIONS
1. Before beginning the installation, verify that the system temperature, pressure and flow
rate do not exceed the ratings indicated on the meter.
2. The meter is designed to operate at a sustained flow of ½ the Maximum Flow Rating
(indicated as the Continuous Flow Rating). The meter should not be operated at the
Maximum Flow Rating for more than one hour per day as excessive wear and/or failure
will result.
3. Flush the pipeline thoroughly after any plumbing changes to eliminate the possibility of
foreign materials reaching the meter.
4. The ½”, ¾” and 2” meters may be installed in horizontal or vertical pipelines (either up or
down flow). To achieve the rated accuracy, there should be at least five (5) diameters of
straight pipe (same size as meter) before and after the meter. Meters 1” through 1-1/2”
must be installed on horizontal pipelines only. There is no straight pipe requirement
before or after these meters. In horizontal installations, the flow counter should be facing
straight upward.
5. Pay careful attention to the flow direction as indicated by the arrow cast into the meter
body.
6. It is highly recommended that a strainer be installed upstream of the meter inlet. It is also
recommended that a shutoff valve be located before and after the meter to facilitate
service.
7. Care should be taken to protect the meter from water hammer as well as freezing
temperatures.
8. The counter is calibrated in U.S. gallons and can not be reset. It will roll around to zero
after reaching its maximum reading. See page 2 for additional information on the
counter.
9. Meters with a pulse output contain a magnetically driven “dry contact type” reed switch.
Each contact closure is equal to one (1) or ten (10) gallons of water as indicated on the
meter. The electrical rating of the switch is 100mA at 42 volts AC/DC.
Sparta, NJ 07871