ISYGLT BW-03 User manual

1
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
Technical Data / Instruction Manual
BW-03
Article no. 80087170
BW-03-UP
Article no. 80087171
BW-03-LP
Article no. 80087173
Motion Sensor

2
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
1. Notes on documentation
These instructions are intended for qualified personnel who are
familiar with the assembly, installation and operation of the ISYGLT
system. It is essential that you read these operating instructions
through before commissioning and keep them accessible for further
use.
SEEBACHER cannot accept any liability for damage or malfunctions
resulting from failure to observe these instructions.
1.1. Retention of documents
These instructions and all other applicable documents are part
of the product. They must be handed over to the device operator.
The operator will store the documents so that they can be made
available if necessary.
1.2. Symbols used
Observe the following safety and other instructions in the manual:
Handling instruction
The hand indicates that you should carry out an act.
Danger!
Immediate danger to life!
Attention!
General notes, useful information and special features
Directory of Content
1. Notes on documentation
1.1. Retention of documents
1.2. Symbols used
2. Safety instructions
2.1. Intended usage
2.2. Predictable mishandling
2.3. Safe handling
2.4. Qualification of staff
2.5. Changes to the product
2.6. Use of spare parts and additional equipment
2.7. Liability notes
3. Warranty
4. Declaration of Conformity
5. Service address
6. Maintenance / Care / Disposal
7. Storage
8. Assembly
9. Product description
10. Technical Data
10.1. Pin assignment
11. Wiring diagram

3
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
ves of the country in which the device is installed and operated,
and the applicable safety and accident prevention regulations.
The device is intended for wall or ceiling mounting. It can be
installed as a luminaire mounting, in a flush-mounted combina-
tion panel and as a surface-mounted variant in a junction box.
Extreme environmental conditions impair the function of the pro-
duct.
• Protect module from shocks
• Use module indoors only
• Protect module from humidity
In addition to these safety instructions, you must also observe
the special safety instructions listed in the individual chapters for
the individual acts.
2.4. Qualification of staff
Assembly, commissioning, operation, maintenance, decommis-
sioning and disposal may only be carried out by qualified staff.
Work on electrical parts may only be carried out by a trained
electrician in accordance with the applicable regulations and
directives. Other activities in connection with the ISYGLT module,
such as assembly and installation of system components with
tested standard plug connections, as well as operation and con-
figuration of the ISYGLT module may only be carried out by trai-
ned staff.
2.5. Changes to the product
Unauthorized modifications to the ISYGLT module which are not
described in this or the other applicable instructions can lead to
malfunctions and are prohibited for safety reasons.
2.6. Use of spare parts and additional equipment
The module may be damaged if unsuitable spare parts and addi-
tional equipment are used. Only use original spare parts and
additional equipment from the manufacturer.
2.7. Liability notes
SEEBACHER accepts no liability or warranty whatsoever for
damage and consequential damage caused by non-compliance
with the technical regulations, instructions and recommendati-
ons. SEEBACHER shall not be liable for any costs or damage
incurred by the user or third parties as a result of the use of this
equipment, in particular improper use of the equipment, misuse
or malfunction of the connection, malfunction of the equipment
or connected devices.
SEEBACHER accepts no liability for printing errors.
2. Safety instructions
Observe the following general safety instructions when installing
and commissioning the device:
Assembly and installation of the ISYGLT module may only be carried
out by a qualified electrician. Other activities in connection with the
ISYGLT module, such as assembly and installation of system com-
ponents with tested standard plug connections, as well as operation
and configuration of the ISYGLT module may only be carried out by
trained staff.
Observe the electrical installation regulations of the country in which
the device is installed and operated as well as its national accident
prevention regulations. In addition, observe internal company regu-
lations (work, operating and safety regulations).
Before working on the ISYGLT module system, it must be
disconnected from the power supply and secured against
being switched on again. After completion of the assembly,
installation and maintenance work, an electrical check must
be carried out! Check all protective conductor connections
and the voltages at all connection plugs as well as at each
individual module slot.
2.1. Intended usage
The sensor is used to switch and control lighting and/or HVAC
systems depending on movement. The device is not suitable
as a burglary or robbery detector. The sensor is designed for
indoor use in buildings only and is intended for operation accor-
ding to the listed technical data. Any other use is not intended.
The limit values stated in the technical data must not be excee-
ded under any circumstances. This applies in particular to the
permissible ambient temperature range and the permissible IP
protection type. For applications with a higher required IP protec-
tion type, the ISYGLT module must be installed in a housing or a
cabinet with a higher IP protection type.
2.2. Predictable mishandling
The module must not be used in the following cases in particular:
•explosive area
When operating in explosive areas, sparking can lead to defla-
gration, fire or explosions.
2.3. Safe handling
This module corresponds to the state of the art and the recog-
nised safety regulations. Each device is tested for function and
safety before delivery.
Only operate this module in perfect condition in accordance with
the operating instructions, the applicable regulations and directi-

4
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
6. Maintenance / Care / Disposal
The product is maintenance-free. The device has highly sensitive
sensors and lens systems. Soiled devices can be cleaned with a
dry wipe. If this is not sufficient, a wipe slightly moistened with soap-
water mixture can be used. Do not clean the lens system with
abrasive or aggressive cleaning products.
Disposal (European Union)
Do not dispose of product in household waste! Products with this
symbol
7. Storage
The product must be stored in a dry place, protected from dirt and
mechanical stress. After damp or dirty storage, the product may only
be operated after a condition check by an authorised electrician.
8. Assembly
(Only by certified electrician!)
Mount the product only when it is in a power-free state!
Switch off the power supply, check that there is no voltage, secure
against being switched on again!
The device may only be operated at voltages according to the tech-
nical data and loaded with the currents defined therein. Only use
suitable equipment (system modules).
Check that there are no loose parts in the product. If this is the case
and the presence of such parts is not explicitly described, do not
install or commission the product.
Only use suitable cables and fixing screws.
Assembly site
• The product can be installed in any position in a casing to be deter-
mined by the electrician (junction box). Observe maximum ambient
temperature!
Assembly steps
(Read completely before assembly!)
The device is designed for wall or ceiling mounting. The full functio-
nality of the device depends, among other things, on the mounting
height (see chapter „Detection range“).
• Mount the device in a suitable casing.
• Make the electrical connections according to the wiring diagram.
• Only after a complete connection and a visual test by a qualied
electrician, the system may be put under voltage.
Seebacher GmbH
Marktstrasse 57
83646 Bad Tölz
GERMANY
Phone: +49 (0) 80 41 / 77 77 6
Fax: +49 (0) 80 41 / 77 77 2
www.seebacher.de
info@seebacher.de
5. Service address
4. Declaration of Conformity
The valid declaration of conformity for the module can be requested
from us free of charge by stating type and article no. as follows:
By phone: +49(0)8041/77776
By fax: +49(0)8041/77772
By mail: info@seebacher.de
3. Warranty
We provide warranty within the framework of the statutory provisi-
ons. These are limited to the intended use of the module and refer
to the repair or replacement of the ISYGLT module. Please send the
device with an attached error description to our company address
given below.
must be disposed of according to the EU directive WEEE 2012/19/
EU on waste electrical and electronic equipment at the local collec-
tion points for waste electrical and electronic equipment!

5
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
9. Product description
The ISYGLT BW-03 motion sensor is based on passive infrared
monitoring technology. Via the very small round lens, 80 zones are
monitored in a radial manner. The detection range is guaranteed
with 10m in radius according to the data sheet. Due to the integrated
line amplifier the length of the control line up to the I/O module or
24V power component can be up to 100m. Due to its small design
the motion sensor can be easily integrated into devices or lights.
As variants we also offer a version for mounting on standard switch
boxes (type BW-03-UP) and a version in a light spot housing for
installation in ceilings or hollow walls (type BW-03-LP). If required,
please ask for the possibilities for corresponding switch programs of
the different manufacturers.
Outputs
• 1 transistor output led to line amplier with 3-pole terminal
Function displays
• none
Connections
• 3 spring-loaded terminals
Design
• BW-03: White plastic lens for gluing into devices or luminaires
• BW-03-UP: Flush-mounted combination plate matching the respective switch range with white plastic lens
• BW-03-LP: In light spot housing for installation in ceilings or hollow walls
• BW-03-LP-K4M: same as BW-03-LP, but with 4m long connection cable
Type designation BW-03 BW-03-UP BW-03-LP
Article no. 80087170 80087171 80087173
Operating voltage 12V to 30V DC
Current consumption max. 10mA without load
Output Vin -1.5V, 200mA short-circuit proof PNP, length max. 100m to the input module
Dimensions DxH 17.4x23mm + 125mm cable
Weight 11g without flush-mounted cover plate
Connection 3-pole spring-loaded terminal
Operating temperature -10°C to +50°C
Storage temperature -20°C to +70°C
Humidity 0-85% r. h. non condensing
Protection class IP20
CE mark yes
10. Technical data

6
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
10.1. Pin assignment
View
+Ub Operating voltage
0V Operating voltage
OUT Switching output
approx. 125.0mm
23.0mm17.4mm
BW-03
80.0mm
68.0mm
BW-03-UP
30.0mm 22.0mm12.0mm approx. 125.0mm
BW-03-LP
Diameter of cut-out:
optimum 26mm, maximum 28mm

7
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
+24V
0V=
BUS-A
BUS-B
12345678
Address
Art.no.:
ISYGLT I/O module
8002*****
Ub
0V
BUS A
BUS B
CE
E1
E2
E3
E4
A1
C1
A2
C2
A3
C3
A4
C4
Cable length max. 100m
Ub
0V
OUT
11. Wiring diagram

8
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
Misprints and technical changes reserved.
Top view
55¡
5m
10m
5m
10m X
Side view
46,5¡
Y
5m
10m
5m
10m
6 4 4
Y
X
6m
6m
(Max. 15.9m)
4
4
2
2
810m 6810m
22
(Max. 12.3m)
Detection range
This manual suits for next models
5
Table of contents