
Switch Description Position
1I²C Service Port pull-up
resistor
ON/OFF
2Modbus 120 ohm termination
resistor
ON/OFF
b) Connect the IMM Service Port to the heat pump
Service Port. Use the supplied communication cable
for this.
c) Using the 4-pin connector, connect the RS485
Modbus side of the IMM to the Modbus. The
connector can be removed from the IMM for
assembly. Connect the cables as shown in the table
below.
Symbol Connection
VIN 12–24 V DC
WGround/GND
BCommunication control
signal
A
d) Mount the IMM in a dry place with the adhesive strips
on the back of the IMM.
When the power supply is connected correctly, the green
LED will light up.
6. Settings
äCaution!
Required settings
6.1. Avoiding thermostat error messages
If the heat pump is controlled by the IMM, an error
message may appear on the thermostat. If you indicate
that the control is running via the IMM, this error
message will no longer be displayed on the thermostat.
Refer to the register table below to ascribe the
appropriate value to the register.
Register Value Description
1020 0 (default) No IMM
1020 1 IMM
6.2. Communication settings
The IMM supports multiple Modbus configurations to
adjust the baud rate, parity and stop bit options. The
communication settings are adjusted in the IMM
registers. This needs to be done once in order to establish
communication. This depends on the system
requirements.
Baud rate Parity Stop bits Address
Register
1015
Register
1011
Register
1013
Register
1000
2400 None 1 (default) 1 - 247
4800 Odd 2 10 (default)
9600 (default) Even (default)
14400
19200
28800
38400
57600
115200
230400
The communication settings are stored in the IMM’s
internal memory and are retained even if the voltage is
lost. If the default settings are not suitable, the IMM can
be configured in a few steps.
●Determine the appropriate setting and only change
the register that needs to be modified.
a) Adjust baud rate: register 1015
b) Adjust parity: register 1011
c) Adjust stop bits: register 1013
d) Adjust Modbus address: register 1000
If one or more settings have been changed, write the
value 1 in register 1100 to reset the IMM. This will cause a
reset after a few seconds. After the reset, the IMM will
restart with the new setting. This will also happen if
power to the IMM is lost after the settings have been
changed.
7. Monitoring
For all data registers, the data in the registers is
refreshed every 5 seconds with current operating data
from the heat pump.
7.1. Operating data and error codes
In order to read the actual heat pump data, it must first
be known to the IMM. The operating data is stored in
registers. The actual data in these registers consists of
3