IXL Tactic Neo 34101 User manual

C
D
F
E
All appliances must be mounted so that the lowest
point is at least 2.3 m above the floor. The Vent body
and ducted blower is designed to fit a ceiling cavity or
between – floor space with a minimum height of 245
mm. The modules may be installed between joists
using the spring clips (Fig. 2c). Ensure that the outlet of
the Vent unit is directed towards the outer wall. If the
desired orientation of the Vent unit directs the ducting
across ceiling joists ensure that the closest ceiling joist
is not within 150 mm of the Vent outlet.
Note: Neo Heat Modules (models 36111 & 36112)
must be located at least 1m away from the nearest
wall.
Sufficient air inlet into room
Steam will only be removed if there is sufficient flow of
air through the room. Ensure generous inlets exist
through windows, vents or under the door. Air flow
path from inlet to fan should ideally pass over the
steam sources (see Fig.1).
Bathrooms which have high ceilings, are larger than
average, or have an open shower may all require
additional ventilation. We recommend that you visit our
website for further details and suggestions on
effectively ventilating your bathroom.
Ventilation Requirements
Clearances
Figure 2a
A: 215 mm B: 15 mm min. clearance above unit
Figure 2b
C: Models: 34101, 34102, 35101 & 35102 - 50 mm
Models: 36111 & 36112 - 75 mm
D: Models: 34101, 34102, 35101 & 35102 - 195 mm
Models: 36111 & 36112 - 151 mm
E: Models: 34101, 34102, 35101 & 35102 - 35 mm to
structural member
Models: 36111 & 36112 - 50mm to structural members.
F: Models: 34101, 34102, 35101 & 35102 - 150 mm.
Figure 2c
Models: 34101, 34102, 35101 & 35102 - 35 mm min.
clearance is required near all joists
Models: 36111 & 36112 - 50 mm min. clearance is
required near all joists.
For maximum efficiency and fan performance there
a few key points to keep in mind when installing your
Tastic.
are
Fig. 1: Ideal placement of Ventilation units.
Sufficient air inlets into room are required
Fig. 2b: Minimum clearances for installation
Fig. 2a: Minimum blower clearances
Fig. 2c: Minimum clearances for installation
Overview
Electrical Requirements
Fig. 6: Wiring diagram for models 34101 and 34102, Neo Vent n Lite.
See the wiring diagrams on the following pages for supply requirements and maximum loadings for each
model. Modules may be connected to a lighting or power circuit if loading permits. These models are for
wired-in installation and wiring must be carried out by a registered electrician. Switches and a wall plate
are not provided with the hardwired Neo modules. Do not use this product with any solid state speed
control or commercial dimming device.
Neo modules are fitted with LED centre lamps. To ensure
operation and to prolong the life of the LEDs please wire as per
the following wiring diagrams for the appropriate model.
correct
Wiring Diagrams
Fig. 8: Wiring diagram for model 36111 and 36112, Neo Heat.
Wiring – Aust & NZ
In all versions a local isolating switch (not supplied)
must be incorporated in the fixed wiring to the
appliance to allow disconnection of supply during
maintenance. This isolating switch, and the wall
switch, must be located in accordance with Wiring
Rules AS/NZS 3000. They must not be installed where
it can be reached from the bath or shower recess or
enclosure (see AS/NZS 3000 Section 7).
Vent & Vent n Lite models 34101, 34102, 35101 &
35102: Switch the power outlet for the Inline Blower
with a wall switch (not supplied) as per the Wiring
Diagrams. Do not mount the power outlet for the Inline
Blower more than 200 mm from the Inline Blower.
Wiring – UK & Eire
In all versions a local isolating switch (not supplied)
must be incorporated in the fixed wiring to the
appliance to allow disconnection of supply during
maintenance. This isolating switch, and the wall
switch, must be located in accordance with the
applicable Wiring Rules and it must not be installed
where it can be reached from the bath or shower
recess or enclosure.
Vent and Vent n Lite models 34101, 34102, 35101
& 35102: Supply should be connected to the Inline
Blower 2-core power lead as per the Wiring Diagrams.
The plug fitted to the power cord is to be cut off and
the wires stripped to allow connection.
The colours of the wires in the Inline Blower 2-core
lead may not correspond to those in the fixed wiring.
The designation of poles for the Tastic power leads are
as follows:
Tastic Wire
Colour
Connect to
Supply Pole
Brown Live
Blue Neutral
Fig. 7: Wiring diagram for model 35101 and 35102, Neo Vent.
E
34101 & 34102: 0.4A 50Hz
FASCIA
BODY
M
ACTIVE
NEUTRAL
DUCTED FAN
TERMINAL BLOCK
3 X DOWNLIGHTS
ACTIVE
NEUTRAL
FOR SWITCH
CONNECTION
REFER TO FIGS
9 & 11
FOR SWITCH
CONNECTION
REFER TO FIG
10 & 12
35101 & 35102: 0.3A 50Hz
M
DUCTED FAN
ACTIVE
NEUTRAL
FOR SWITCH
CONNECTION
REFER TO FIGS
10 & 12
36111 & 36112: 3.3A 50Hz
FASCIA
BODY
ACTIVE
NEUTRAL
TERMINAL BLOCK
THERMAL SWITCH 65°C
HEAT LAMP
FOR SWITCH
CONNECTION
REFER TO FIGS
9 & 11
Wiring Diagrams
* This switch must be double-pole
with minimum 3 mm contact gap.
type
A
B
Fig. 3: Layout of Neo Vent and Vent n Lite.
Neo Models: 34101, 34102, 35101 & 35102
Wall switch (not supplied)
Inline Ducted Blower
Ducting
Air outlet grille
positioned in eaves lining
Exterior
of home
Eaves
lining
Vent unit
Flexible support
Cable not on 35101 & 35102
Fig. 9
Fig. 10: Inline Ducted Blower
Fig. 11
Fig. 12: Inline Ducted Blower
A
N
E
Wall Switch (not supplied)
A
N
Wall Switch (not supplied)
A
N
E
Wall Switch (not supplied)
A
N
BROWN
BLUE
Wall Switch (not supplied)

Fig. 22
Power
cable
Fig. 16
Template Guide
Part number 611028_A
Approved by the appropriate
electrical supply authorities.
I N H O M E
WARR ANTY
For comments,
questions or warranty matters:
Sampford IXL Pty Ltd
Service Department
Phone: 1300 727 421
Fax:
1300 727 425
aftersalesser
www.ixlappliances.com.au
Fig. 13: Use template to mark position of module
Installation
The Neo modules may be installed between joists
using the spring clips, clearances must be maintained
as per Fig. 2b, 2c & 2d.
IMPORTANT:
cut or notched to install the appliance.
Joists, beams and rafters shall not be
Depending on your model, the modules have a weight
of 1.0 – 2.6 kg (see below). If adequate support is not
available for the modules, it may be necessary to
provide extra strengthening.
If ceiling battens have been cut to install this
then ensure that the cut ceiling battens are
adequately secured to rafters.
product
NOTE: This product must be installed by a qualified
installer. Ensure power is off to location of Tastic.
Cut out hole for Neo module
After determining the location of the Neo module,
mark out and cut aperture in ceiling using the
appropriate template. Trim the template to the outside
of the black outline.
Vent and Vent n Lite modules (models
34101, 34102, 35101 & 35102)
1.
mm dia. ducting. Determine the length of ducting
required ensuring that the length is as short as
possible. Refer to Fig’s 19-21 to attain optimum
performance.
2. Tape a length of ducting 1 m long (max) to the
blower inlet. Tape remaining length of ducting to
exit of blower.
3. Feed ducting and blower through hole in ceiling.
While feeding ducting into ceiling direct it towards
the installation position of the outlet grille. Position
blower so that the short length of ducting and
stripped wire (models 34101 & 34102) is sitting
next to the hole as per Fig. 22.
4. Make the necessary electrical connections. Refit
terminal cover.
5. Tape short length of ducting, from blower inlet, to
transition.
6. Push unit into ceiling aperture, allowing metal
springs to snap open. As the unit is raised into the
ceiling, ensure electric cable do not rest on the
unit.
7. To secure the unit in position, push lower ends of
springs apart (Fig 16.). Ceiling board thickness
should be adjusted to enable springs to be fitted
without excessive force.
8. Bring fascia up to unit and connect the earthing
wire (models 34101 & 34102). Clip fascia into the
unit. Fig 17.
9. Remove downlight mounts and fit down lights.
Connect lamp holders to downights and refit
downlight mounts (models 34101 & 34102).
10. Turn on the power at the isolating switch and
check operation of the unit.
These products have been designed to suit 150
Fig. 19: Straight ducting
Performance
Fig. 20: Gradual bends,
ducting stretched straight.
100%
Performance
Neo Light small – approx 1.0 kg
Neo Light large – approx 1.3 kg
Neo Vent n Lite - approx 1.9 kg
Neo Vent - approx 1.5 kg
Neo Heat - approx 2.6 kg
Installation Installation
Fig. 23
Fig. 21: Tightly compressed bends
Performance
100%
Fig. 17
Modules - Heat • Vent • Light
Model: 33132 Neo Light Small Silver - Hardwired
Model: 33141 Neo Light Large White - Hardwired
Model: 33142 Neo Light Large Silver - Hardwired
Model: 34101 Neo Vent n Lite White - Hardwired
Model: 34102 Neo Vent n Lite Silver - Hardwired
Model: 33131 Neo Light Small White - Hardwired
Electrical Rating: 230~240 V. 50 Hz.
Model: 35101 Neo Vent White - Hardwired
Model: 35102 Neo Vent Silver - Hardwired
Model: 36111 Neo Heat White - Hardwired
Model: 36112 Neo Heat Silver - Hardwired
Heat module (models 36111 & 36112)
IMPORTANT: Under no circumstances shall this
appliance be covered with insulating material or
similar material.
1. Unscrew terminal cover and make necessary
electrical connections. Refit terminal cover. Do
not turn on power to unit.
2. Push unit into ceiling aperture, allowing metal
springs to snap open. As the unit is raised into the
ceiling, ensure electric cable does not rest on the
unit.
3. To secure the unit in position, push lower ends of
springs apart (Fig 16.). Ceiling board thickness
should be adjusted to enable springs to be fitted
without excessive force.
4. Bring fascia up to unit and connect the earthing
wire. Clip fascia into the unit. Fig 17.
5. Using care, fit the tubular heat lamps into the
lamp holders. Be careful not to touch the glass
surface as oils from skin can shorten the life of
the glass lamp. A clean soft cloth or tissue is
recommended. Ensure that the white reflective
layer on the tubular heat lamp is on the upper side
of the lamp, ie lamp is pointing downwards.
6. Fit the glass sheets to the heat lamp reflector
bodies Fig. 18.
7. Turn on the power at the isolating switch and
check operation of the unit.
Installing the Grille
1.
wall. Feed ducting out through this hole and tape
to the Grille baseplate.
2. Feed the ducting back through the hole so that the
Grille base is against the eaves or outer wall.
3. Fix Grille base with four 6 G screws and snap ft
the Grille louvres over the Grille base as shown in
Fig. 23.
Note: A piece of fly screen can be fitted to the Grille
base prior to fitting the Grille louvre.
Cut a hole 160 mm in diameter in eaves or outer
13
2
Fig. 18
TEMPLATE MODELS: 36111 & 36112 TEMPLATE MODELS: 34101, 34102, 35101 & 35102
Cut-out size: 292mm x 332mm Cut-out size: 214mm x 332mm
Model: 33131, 33132, Neo Light Small Model: 33141, 33142, Neo Light Large
Model: 36111, 36112, Neo Heat Model: 34101, 34102, Neo Vent n Lite Model: 35101, 35102, Neo Vent
T
rim to outside of black line.
T
rim to outside of black line.
IXL Pty Ltd
Service Department
Model: 34101 Neo Vent n Lite White - Hardwired
Model: 34102 Neo Vent n Lite Silver - Hardwired
Model: 35101 Neo Vent White - Hardwired
Model: 35102 Neo Vent Silver - Hardwired
Model: 36111 Neo Heat White - Hardwired
Model: 36112 Neo Heat Silver - Hardwired
Electrical Rating 230 ˜ 240 V. 50 Hz
This manual suits for next models
5
Other IXL Fan manuals
Popular Fan manuals by other brands

Monte Carlo Fan Company
Monte Carlo Fan Company 3TSR52XXD Series installation instructions

WT Knowles & Sons
WT Knowles & Sons KSFM1 Fitting instructions

Oceanic
Oceanic OCEAVT40CM2 user manual

NuTone
NuTone QTREN080C instructions

Flex-a-Lite
Flex-a-Lite Flex Fan installation instructions

SmartVent
SmartVent Synergy2 SYN190E2 user manual

Tate
Tate poweraire quad installation guide

Zehnder Rittling
Zehnder Rittling ComfoAir E 350 quick guide

LUCCI
LUCCI AIRFUSION RESORT installation instructions

Vents
Vents Quiet-dMEV 100 DC user manual

Emerson
Emerson PRIMA CF901BS00 owner's manual

Greenheck
Greenheck MSCF Installation, operation and maintenance manual