Mounting of the air ducts and the
siphon (according to DIN 12056)
ART.NR. : 200502195
ODA
EHA ETA
SUPETA
SUP ODA
EHA
Legend:
R Supply and exhaust air on the right-hand side
L Supply and exhaust air on the left-hand side
ODA Outdoor Air
SUP Supply Air
ETA Extract Air
EHA Exhaust Air
Programming air specifications
123
Connect the unit to the mains power.
Select the language and confirm if the siphon
is assembled the correct way.
See above for installation of siphon.
The unit will now carry out an automatic
selftest. This takes about 4 minutes.
45 6
Close all windows and doors.
Fully open all valves connected to the ducting of
the ventilation system.
Set the required total air volume for the
MAX. DURCHFLUSS on the unit's display.
(MENU > LOGIN > PRESETS >
HOHE EINSTELLUNG)
(MENU > LOGIN > BALANCE EINSTELLUNG)
(MENU > LOGIN; Password = 4210)
Go to the installer settings.
The fans will follow the preset setting
automaticly and the unit is now in
commissioning mode for 1 hour.
78
Example of flow meter
Press to switch the commissioning mode
off again directly without saving the value
entered.
Press to save the value entered and switch
off the commissioning mode.
REPEAT THESE STEPS FOR THE MIDDLE AND
LOW PRESET
Measure the air volumes of each opened valve
using a flow meter.
Write them down.
Set each open valve to the desired air volume for
that room.
Measure again the air volumes of each set valve
using a flow meter.
Check whether the flow is in line with the norm
at each valve.
Everything in order:
Press to switch off the commissioning
mode.
Complete an installation/test report. A sample
installation/test report can be found at the back
of the user manual.
Flows not in line with norm:
Return to step 6.
ZGDE-QuickGuide _ODS80494, V0318, DE
3/4
Installation of air ducts and siphon
(according DIN 12056)
Legend:
R Supply and return air on the right-hand side
L Supply and return air on the left-hand side
ODA Fresh air
SUP Supply air
ETA Extract air
EHA Exhaust air
Example of valve
L (Left) R (Right)
L R
Programming air specifications
1 2 3
Close all windows and doors.
Open all valves connected to the ventilation
system via the ducts.
Connect the device to the mains.
Select a language and confirm that the siphon is
mounted correctly. Check the above illustration
for more information about the installation of the
siphon.
Go to the settings for the installer.
(MENU > Login; Login code= 4210
45
The fans will automatically start rotating to
the set position. The unit is in the commis-
sioning mode for one hour.
6Example of a flow meter
Set the required total air flow to the maxi-
mum flow rate. (MENU>Login>VENTILATION
SETTINGS>HIGH SETTING)
= Air flow almost at limit value
= Air flow insufficient
If the limit value is lower than the desired air
flow, a further system test must be carried out.
(MENU>Login>SYSTEM TEST) For more infor-
mation, see the fitter's manual.
Press to switch the commissioning mode off
again directly without saving the value entered.
Press to save the value entered.
REPEAT THESE STEPS FOR THE MEDIUM AND
LOW SETTINGS
Measure the air flow at each opened valve using
a flow meter.
Write down the air flow for these valves.
Adjust the opened valves to the required air flow
per room.
Measure the air flow again at each opened valve
using a flow meter.
Check that the air flow complies with the stand-
ard for each opened valve.
78 9
If the air flow is fine everywhere:
Press to exit the commissioning mode.
Complete an installation/test report. An example
can be found in the back of the user manual.
The unit’s installation height must be specified in
the “ALTITUDE” menu.
(MENU>Login>ALTITUDE>)
In the menu BALANCE SETTING an unbalance
between supply and exhaust air can be set.
(MENU>Login>BALANCE SETTING>BALANCE
FINE TUNE)
BALANCE SETTING selection: ‘+’= more ex-
haust air; ‘-’= less exhaust air.
With the FIREPLACE MODE setting activated,
only less exhaust air (=’-’) is possible.
FROST PROTECTION selection (without pre-
heater):
(BALANCE SETTING>FIREPLACE MODE)
■FIREPLACE MODE active? YES: (Default)
Exhaust and supply air remain in balance at all
times. As a result, the unit switches off faster
in frost mode than in inactive fireplace mode.
■FIREPLACE MODE active? NO: There is more
supply air than exhaust air. So in frost mode,
ventilation is maintained longer.
Malfunctions on the preheater or bypass can only be reset after the system test has been carried out again. 3/4