J.E. Adams 8670-5WB User manual


8670-5WB Manual – 10/2006 2
TABLE OF CONTENTS
•Product Information…………………………………… 3
•Specifications…………………………………………… 4
•Installation……………………………………………… 5-10
oRequirements…….…………………………… 5
oInstallation Directions..………………………. 6
oFigure 1: Hose Reel Base Footprint.…………. 7
oFigure 2: Mounting and Routing Detail………..8
oFigure 3: Electrical Installation Detail…………9
oFigure 4: Cabinet and Base Dimensions……….10
•Timer setup……………………………………………… 11-15
oSSAC Setup…………………………………... 11
oIDX Setup…………………………………….. 12
oInfitec Setup………………………………….. 13
oTimer Settings Chart…………………………. 14
oTypical Timer Settings………………………. . 15
•Programming the Remote Start System…………………16
•Maintenance……………………………………………... 17
•Parts Breakdown………………………………………... 18-20
o8670-5WB…………………….……………… 18
o8778A-1………………………..……………... 19
o22002-51A……………………………………. 20
•Schematics……………………………………………….. 21
oS8670-5WB………………………...…………. 21
•Troubleshooting…………………………………………. 22

8670-5WB Manual – 10/2006 3
PRODUCT INFORMATION
Please take a moment to fill out the information below in order to aid us with any future sales or service inquiries. Model
number and serial number information can be found on the serial tag located inside the control box and/or on the lower
exterior of the can. Key number can be found on the tag that comes attached to the keys. There may be more than one key
number depending on unit.
Please keep this information with your records.
MODEL#:_________________________________________
SERIAL#:_________________________________________
KEY NUMBER(S):_________________________________
DATE PURCHASED:_______________________________
DISTRIBUTOR:___________________________________
J.E. Adams Industries
1025 63rd Ave. S.W.
Cedar Rapids, IA 52404
1-800-553-8861
www.jeadams.com

8670-5WB Manual – 10/2006 4
SPECIFICATIONS
DeVILBISS COMPRESSOR
•20 AMP SERVICE REQUIRED
•120 VAC, 60Hz, 14 AMPS
•1.5 HORSEPOWER
•ONE CYLINDER
•ONE STAGE OIL-LESS
SCFM @ PSI :
6 @ 0
5 @ 20
4.1 @ 40
3.1 @ 90
2.9 @ 100
2.1 @ 125 (MAX PSI)
TEMPERATURE RANGE:
-10 DEGREES F TO 100 DEGREES F.
MOTOR:
•1.5 HP, 1725 RPM
•CAPACITOR START
•NEMA 56 FRAME
•AUTOMATIC THERMAL
OVERLOAD.
NO LUBRICATION REQUIRED ON MOTOR OR COMPRESSOR.

8670-5WB Manual – 10/2006 5
INSTALLATION REQUIREMENTS
!IMPORTANT!
TO ENSURE PROPER FUNCTIONALITY AND ADHERANCE TO BOTH LOCAL AND NATIONAL ELECTRIC
CODES, IT IS RECOMMENDED THAT SERVICE BE INSTALLED BY A LICENCED ELECTRICIAN EXPERIENCED
IN COMMERCIAL APPLICATIONS. INADEQUATE POWER AND WIRING MAY CAUSE THE UNIT TO PERFORM
ERRATICALLY, BLOW FUSES AND TIME INCORRECTLY.
GENERAL MECHANICAL:
•ALL DIMENSIONS IN DRAWINGS ARE IN INCHES.
•MOUNTING STUD SIZE 3/8” X 16 UNC X 1”.
•4” MINIMUM CONCRETE REQUIRED AROUND MOUNTING STUD.
•18” MINIMUM PAD RECOMMENDED FOR BUMPER CLEARANCE.
FOR GASOLINE DISPENSING LOCATIONS:
•A MINIMUM 18” HIGH PAD ABOVE THE DRIVEWAY.
•20 FOOT HORIZONTAL CLEARANCE FROM THE EXTERIOR ENCLOSURE OF ANY
GASOLINE DISPENSING PUMP.
ELECTRICAL SERVICE:
•Dedicated service required
o120V single phase
o20 amp service
o60Hz cycle
•Minimum service wire size:
oLess than 100ft run: 12Ga
o100ft – 200ft run: 10Ga

8670-5WB Manual – 10/2006 6
INSTALLATION
IT IS HIGHLY RECOMMENDED THAT THIS UNIT BE INSTALLED BY A LICENSED
ELECTRICIAN to ensure all local and national electrical codes are adhered to.
1. This unit is designed to be used with the J.E. Adams 6025 hose reel base.
2. Using the 6025 footprint dimensions shown in Figure 1, locate and install mounting studs.
3. Secure hose reel base to mounting studs securely. DO NOT install the cover at this time.
4. Mount cabinet to base securely as shown in Figure 2, using only the four 5/16-18 X ½” bolts.
DO NOT install the ¼-20 X ½” bolts at this time.
5. Using Figures 2 & 3, install electrical and water services to the unit and run air and water lines to
the inputs of their respective hose reels. Air line should run between the output of the unloader
valve and the input of the air reel.
6. Set timer to desired time and coin settings (pages 11-15).
7. Apply power to the unit and verify proper operation.
8. Install hose reel cover using ¼-20 X ½” bolts to secure in place as shown in Figure 2.

8670-5WB Manual – 10/2006 7
Figure 1: Installation footprint for 6025 hose reel base

8670-5WB Manual – 10/2006 8
Figure 2: Mounting and routing detail

8670-5WB Manual – 10/2006 9
Figure 3: Electrical installation detail

8670-5WB Manual – 10/2006 10
Figure 4: Cabinet and hose reel base dimensions

8670-5WB Manual – 10/2006 11
Figure 5: SSAC timer setup
Figure 5 shows an SSAC timer set for 1 coin to start and 3.8 minutes per
coin for a total run time of 3.8 minutes (3 minutes and 48 seconds).
TIMER SETUP – SSAC TIMERS
Note: “AE” and “AN” model SSAC timers are accumulating timers.
During use, timing can be extended proportionately by adding more
coins.
The SSAC timer has two adjustable settings: Time per coin (in minutes)
and number of coins to start.
Time per coin:
Time per coin is the amount of time the unit will run per coin inserted
and can be set from 0.1 minutes (6 seconds) to 12.7 minutes (12 minutes
and 42 seconds) in increments of 6 seconds by turning on the correct
switches until their values equal the desired time.Refer to Tables 1 and 2
(pages 14-15) for standard timer and coin settings. For custom settings,
follow the steps below:
1. Figure the total time your vac will run (in minutes) and divide that
number by the number of coins to start. This is your time per coin.
Round up or down to the nearest tenth of a minute.
2. Subtract the largest value switch (initially 6.4) from your time per
coin.
a. If the resulting number is zero, move the switch to the “on”
position and set all remaining un-set switches in the “off”
position. Your timer is now set.
b. If the resulting number is positive, move the switch into the
“on” position. Using the resulting number as your new time
per coin, repeat step 2 with the next largest switch value.
c. If the resulting number is negative, set the switch in the
“off” position and repeat step 2 using the next largest switch
value.
Coins to start:
Coins to start is the amount of coins needed to activate the timer and can
be set from one to seven coins in increments of one coin. Refer to Table
1 (page 14) for switch settings.

8670-5WB Manual – 10/2006 12
Figure 6: IDX timer setup
Figure 6 shows an IDX timer set for 3 coins to start and 60 seconds per coin
for a total run time of 3 minutes.
TIMER SETUP – IDX TIMERS
Note: IDX timers are accumulating timers. During use, timing can be
extended proportionately by adding more coins.
The IDX timer has two adjustable settings: Time per coin (in seconds)
and number of coins to start.
Time per coin:
Time per coin is the amount of time the unit will run per coin inserted
and can be set from 2 seconds to 510 seconds (8.5 minutes) in increments
of 2 seconds by turning on the correct switches until their values equal the
desired time.Refer to Tables 1 and 2 (pages 14-15) for standard timer
and coin settings (Note: IDX timers do not have 1 second or 512 second
switches. When configuring timer using Table 1, ignore settings for
switches 1 and 512). For custom settings, follow the steps below:
1. Figure the total time your vac will run (in seconds) and divide that
number by the number of coins to start. This is your time per coin.
Round up or down to the nearest even number.
2. Subtract the largest value switch (initially 256) from your time per
coin.
a. If the resulting number is zero, move the switch to the “on”
position and set all remaining un-set switches in the “off”
position. Your timer is now set.
b. If the resulting number is positive, move the switch into the
“on” position. Using the resulting number as your new time
per coin, repeat step 2 with the next largest switch value.
c. If the resulting number is negative, set the switch in the “off”
position and repeat step 2 using the next largest switch value.
Coins to start:
Coins to start is the amount of coins needed to activate the timer and can
be set from one to seven coins in increments of one coin. Refer to Table
1 (page 14) for switch settings.

8670-5WB Manual – 10/2006 13
Figure 7: Infitec timer setup
Figure 7 shows an Infitec timer set for 2 coins to start and a total run time of
240 seconds (4 minutes).
TIMER SETUP – INFITEC TIMERS
The Infitec timer has two adjustable settings: Total run time (in seconds)
and number of coins to start.
Total run time:
Total run time is the amount of time the unit will run once activated and
can be set from 1 second to 1023 seconds (17 minutes and 3 seconds) in
increments of 1 second by turning on the correct switches until their
values equal the desired time.Refer to Tables 1 and 2 (pages 14-15) for
standard timer and coin settings. For custom settings, follow the steps
below:
1. Figure the total time your vac will run (in seconds). This is your
total run time. Round up or down as desired.
2. Subtract the largest value switch (initially 512) from your total run
time.
a. If the resulting number is zero, move the switch to the “on”
position and set all remaining un-set switches in the “off”
position. Your timer is now set.
b. If the resulting number is positive, move the switch into the
“on” position. Using the resulting number as your new time
per coin, repeat step 2 with the next largest switch value.
c. If the resulting number is negative, set the switch in the
“off” position and repeat step 2 using the next largest switch
value.
Coins to start:
Coins to start is the amount of coins needed to activate the timer and
can be set from one to 15 coins in increments of one coin. Refer to Table
1 (page 14) for switch settings.

8670-5WB Manual – 10/2006 14
5
10
15
20
25
30
35
40
45
50
55
60 (1 min)
70
80
90
100
110
120 (2 min)
130
140
150
160
170
180 (3 min)
190
200
210
220
230
240 (4 min)
250
260
270
280
290
300 (5 min)
1xxxxxx
2xx xx xxxxxxxxxxxxxx
4x xx x x xxx xx xx xx xx xx x
8xx xx xx x x xx x x xx x x xx x
16 xxx xxx xx x x xx xx xx x
32 xxxxxx xxx xxxx xxx xx
64 xxxxxx xxxxxx
128 xxxxxxxxxxxxx
256 xxxxx
512
0.1 (6sec)
0.2 (12 sec)
0.3 (18 sec)
0.4 (24 sec)
0.5 (30 sec)
0.6 (36 sec)
0.7 (42 sec)
0.8 (48 sec)
0.9 (54 sec)
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
0.1 xxxxxxxxxxxxxxxxxx
0.2 xx xx xx xx xx xx xx xx xx
0.4 xxxx xxxx x x x xx x x xx
0.8 xxxxxxxx xx xx x x xx
1.6 xxxxxxx xxx xxxx
3.2 xxxxxx x
6.4 xxxxxxxx
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1xxxxxxxx
2xx xx xx xx
4xxxx xxxx
8xxxxxxxx
All Timers
Coin Switches
Coins to Start
SSAC Timers
Timer Switches
Time Per Coin (In minutes)
Infitec Timers: Total Run Time (In Seconds)
Infitec and IDX Timers
Timer Switches
IDX Timers: Time Per Coin (In Seconds)
Table 1: Timer Settings Chart
Note: “X” indicates a switch in the “on” position

8670-5WB Manual – 10/2006 15
Amount to
Start Total Run
Time Switches in "On"
Position Amount to
Start Total Run
Time Switches in "On"
Position Amount to
Start Total Run
Time Switches in "On"
Position
25¢ 2 MIN 8, 16, 32, 64 25¢ 2 MIN 0.4, 1.6 25¢ 2 MIN 8, 16, 32, 64
25¢ 2-1/2 MIN 2, 4, 16, 128 25¢ 2-1/2 MIN 0.1, 0.8, 1.6 25¢ 2-1/2 MIN 2, 4, 16, 128
25¢ 3 MIN 4, 16, 32, 128 25¢ 3 MIN 0.2, 0.4, 0.8, 1.6 25¢ 3 MIN 4, 16, 32, 128
25¢ 3-1/2 MIN 2, 16, 64, 128 25¢ 3-1/2 MIN 0.1, 0.2, 3.2 25¢ 3-1/2 MIN 2, 16, 64, 128
25¢ 4 MIN 16, 32, 64, 128 25¢ 4 MIN 0.8, 3.2 25¢ 4 MIN 16, 32, 64, 128
25¢ 4-1/2 MIN 2, 4, 8 , 256 25¢ 4-1/2 MIN 0.1, 0.4, 0.8, 3.2 25¢ 4-1/2 MIN 2, 4, 8, 256
25¢ 5 MIN 4, 8, 32, 256 25¢ 5 MIN 0.2, 1.6, 3.2 25¢ 5 MIN 4, 8, 32, 256
25¢ 5-1/2 MIN 2, 8, 64, 256 25¢ 5-1/2 MIN 0.1, 0.2, 0.4, 1.6, 3.2 25¢ 5-1/2 MIN 2, 8, 64, 256
50¢ 2 MIN 4, 8, 16, 32 50¢ 2 MIN 0.2, 0.8 50¢ 2 MIN 8, 16, 32, 64
50¢ 2-1/2 MIN 4, 8, 64 50¢ 2-1/2 MIN *50¢ 2-1/2 MIN 2, 4, 16, 128
50¢ 3 MIN 2, 8, 16, 64 50¢ 3 MIN 0.1, 0.2, 0.4, 0.8 50¢ 3 MIN 4, 16, 32, 128
50¢ 3-1/2 MIN 2, 8, 32, 64 50¢ 3-1/2 MIN *50¢ 3-1/2 MIN 2, 16, 64, 128
50¢ 4 MIN 8, 16, 32, 64 50¢ 4 MIN 0.4, 1.6 50¢ 4 MIN 16, 32, 64, 128
50¢ 4-1/2 MIN 8, 128 50¢ 4-1/2 MIN *50¢ 4-1/2 MIN 2, 4, 8, 256
50¢ 5 MIN 2, 4, 16, 128 50¢ 5 MIN 0.1, 0.8, 1.6 50¢ 5 MIN 4, 8, 32, 256
50¢ 5-1/2 MIN 2, 4, 32, 128 50¢ 5-1/2 MIN *50¢ 5-1/2 MIN 2, 8, 64, 256
75¢ 2 MIN 8, 32 75¢ 2 MIN *75¢ 2 MIN 8, 16, 32, 64
75¢ 2-1/2 MIN 2, 16, 32 75¢ 2-1/2 MIN *75¢ 2-1/2 MIN 2, 4, 16, 128
75¢ 3 MIN 4, 8, 16, 32 75¢ 3 MIN 0.2, 0.8 75¢ 3 MIN 4, 16, 32, 128
75¢ 3-1/2 MIN 2, 4, 64 75¢ 3-1/2 MIN *75¢ 3-1/2 MIN 2, 16, 64, 128
75¢ 4 MIN 16, 64 75¢ 4 MIN *75¢ 4 MIN 16, 32, 64, 128
75¢ 4-1/2 MIN 2, 8, 16, 64 75¢ 4-1/2 MIN *75¢ 4-1/2 MIN 2, 4, 8, 256
75¢ 5 MIN 4, 32, 64 75¢ 5 MIN *75¢ 5 MIN 4, 8, 32, 256
75¢ 5-1/2 MIN 2, 4, 8, 32, 64 75¢ 5-1/2 MIN *75¢ 5-1/2 MIN 2, 8, 64, 256
$1.00 2 MIN 2, 4, 8, 16 $1.00 2 MIN 0.1, 0.4 $1.00 2 MIN 8, 16, 32, 64
$1.00 2-1/2 MIN 2, 4, 32 $1.00 2-1/2 MIN *$1.00 2-1/2 MIN 2, 4, 16, 128
$1.00 3 MIN 4, 8, 32 $1.00 3 MIN *$1.00 3 MIN 4, 16, 32, 128
$1.00 3-1/2 MIN 2, 4, 16, 32 $1.00 3-1/2 MIN *$1.00 3-1/2 MIN 2, 16, 64, 128
$1.00 4 MIN 4, 8, 16, 32 $1.00 4 MIN 0.2, 0.8 $1.00 4 MIN 16, 32, 64, 128
$1.00 4-1/2 MIN 4, 64 $1.00 4-1/2 MIN *$1.00 4-1/2 MIN 2, 4, 8, 256
$1.00 5 MIN 4, 8, 64 $1.00 5 MIN *$1.00 5 MIN 4, 8, 32, 256
$1.00 5-1/2 MIN 4, 16, 64 $1.00 5-1/2 MIN *$1.00 5-1/2 MIN 2, 8, 64, 256
IDX TIMER SETTINGS SSAC TIMER SETTINGS INFITEC TIMER SETTINGS
Table 2: Typical Timer Settings
Note: “*” denotes a configuration that is not possible with this timer. See Table 2 for the closest approximation to this time.

8670-5WB Manual – 10/2006 16
PROGRAMMING THE REMOTE START SYSTEM
Note: The remote start system will need to be re-programmed each time the unit is powered up.
1. Remove cover from signal receiver by pressing in at the center of each of the two lengthwise
sides.
2. Locate the covered Learn Code Button and LED indicator at the top of the circuit board. They
will be located directly beneath the upper tab holding the circuit board in place.
3. Press and release the Learn Code Button. LED indicator will blink at a rate of two times per
second.
4. Press the Transmitter Button once. The indicator light should now be on continuously.
5. Press the same Transmitter Button again. The indicator light should now turn off. The remote
start system should now be programmed. Note: You must perform steps 3-5 within 30 seconds.
If the LED indicator begins to blink rapidly (about 4 times per second) you must repeat steps
3-5.
6. Test the system to verify proper operation.
7. Replace cover, making sure antenna is hanging straight down outside the cover.

8670-5WB Manual – 10/2006 17
MAINTENANCE
•Check air and water hoses and attachments periodically for signs of wear or
damage and replace them as needed.
•Check door gaskets periodically for signs of wear or damage and replace them as
needed.
•Water solenoid may need to be disassembled and cleaned periodically to prevent
sticking. To disassemble, remove nut on top of valve and remove coil cover and
coil. Then using a flat head screwdriver, remove the piston housing. Clean out any
debris on the piston and in the piston housing and reassemble the valve.
•Clean the outside portion of the cabinet with a stainless steel polish. DO NOT use
any abrasive cleaners, steel wool or any kind of brush to clean the exterior. Doing
so could possibly scratch or damage the finish of the cabinet.
•Mild soap and water may be used to clean the decals. DO NOT use any harsh or
abrasive cleaners or the decal surface may be damaged.

8670-5WB Manual – 10/2006 18

8670-5WB Manual – 10/2006 19

8670-5WB Manual – 10/2006 20
Table of contents
Popular Compressor manuals by other brands

Drawmer
Drawmer DL241 Operator's manual

Emerson
Emerson Copeland Scroll UltraTech CoreSense Application Engineering Bulletin

Hamron
Hamron 604-000 operating instructions

Gardner Denver
Gardner Denver ELECTRA-SAVER OPERATING & SERVICE MANUAL

JBM
JBM 52227 instruction manual

Hitachi
Hitachi NEXT Series Service manual