Jakka CONTROL KIT 5 User manual

JAKKA CONTROL KIT 5
USER MANUAL

TR
- 3.1” Screen
- 6 Steps control of exhaust and supply fans
- Working of the unit in Automatic/Manual Modes
- Heating/Cooling /Fan Modes
- Room Temperature Sensor
- User Friendly Design
- Minimum ve Maximum Set Temperature Limit
- Constant HVAC-R Images
- Weekly Programming
1. ROOM THERMOSTATE

TR
2. CONTROL PANEL
Control Panel
Control Panel run the heat recovery units by controlling supply and exhaust fans seperately and controlling electrical heater in steps.. It is also possible
to control pre and after heater, fresh air damper, bypass damper, ,heating coil, cooling coil and also EC fans
Main Features:
-Filter Alarm According to Pre-set Time counter (Pre-set Service Time)
-Pre programmed scenario selection via room thermostate
-Adjustable Mode selection (Auto Heating, Auto Cooling, , Manual
Heating , Manual Cooling, Fan Mode)
-Restart with the last paremeters in case of power shortage
-Connection to building management system (Modbus-RTU)
-Weekly Programming

TR
3. SPECIFICATIONS
Environmental Specs
Working and Storage Temperature: 0 ... +50°C
Protection Class: EN 60529 - IP00
Electrical Specs
Control : Room Thermostate/BMS
Relay Current Capacity: Resistive 5A (Heating Contactor)
Power Supply: 230V AC
PhaseShut Down : 10A (6 Steps)
Consumption: Max 5VA, Connection 1,5mm²clips
Functional Specs
On/ Off via BMs
Embedden temperature sensor to room thermostate
Control Of;
- Duct Type Temperature Sensor
-Fresh Air Damper
-Bypass Air Damper
- External Sensor Connection (NTC 10K)
- 6 Steps Manuael or Auto Speed Selection for Exhaust
and Supply Fans seperately
Unit On/Off info
Weekly Programming
Carbondioxide/Air Quality Sensor Control (0-10V)
Proportional Valve Control
EC Fan Control

FEATURES OF ROOM THERMOSTATE:
A. ) HOW TO MAKE WEEKLY PROGRAMMING:
•Press FAN button for two (2) seconds while the unit is on.
•You will see “00” at the upper-right part of the screen, then press Mode / OK button.
•You can select starting and stopping time for each day of the week with UP and DOWN buttons on
the weekly programming screen. Go on by pressing Mode/OK button.
•To go back to previous screen and/ or to exit , use ON/OFF button.
Note1 : Unit will not work if starting time is later than stopping time.
Note2 : Unit will not work if starting time is same with stopping time.
Note3 : There will be a clock symbol on the screen, if unit works in weekly programmed hours.
Note4 : There will be a clock deleting symbol on the screen, if unit works out of weekly programmed hours.
B.) SETTING DATE AND TIME:
•Press Fan button for two (2) seconds while the unit is on.
•You will see “00” at the upper-right part of the screen, then change it to“01” by using UP and DOWN buttons,
then press Mode/OK button.
•Set hour/minute by pressing UP and DOWN buttons then go on by pressing Mode/OK
•Set day/month by pressing UP and DOWN buttons then go on by pressing Mode/OK
•Set year by pressing UP and DOWN buttons then go on by pressing Mode/OK
•Set name of the day by pressing UP and DOWN buttons then go on by pressing Mode/OK
C.) CHANGING UNIT MODE:
•The mode can be selected by pressing Mode/OK button when the unit is on.
•When the unit is at manual heating, manual cooling or fan mode, by pressing Mode/OK button fan
speed and set temperature can be adjusted. You can go to next screen by pressing Mode/OK button
•When the unit is at auto mode, passing to the next mode is possible by pressing Mode/OK button
D.) CHANGING SET TEMPERATURE:
•When unit is on and in auto mode, using UP and DOWN buttons ,set temperature number will start
blinking. Set temperature can be selected by pressing UP and DOWN buttons.
•When unit is on and in manual mode, using UP and DOWN buttons ,set temperature number will start
blinking. Set temperature can be selected by pressing UP and DOWN buttons.

E.) HOW TO ACTIVATE KEYLOCK:
•Press FAN and DOWN buttons simultaneously when the unit is on.
There will be a lock symbol on screen after 2 seconds.
All of the buttons will be locked when keylock is on.
F.) HOW TO DEACTIVATE KEYLOCK:
•Press FAN and DOWN buttons simultaneously when the unit is on.
•Lock symbol on the screen will be deleted after 2 seconds. Then press any button.
•All buttons will be functional again.
G.) HOW TO RESET ALARM CODE:
•If “Err 0001” alarm (or any other alarm) code blinking on screen
•Press FAN and UP buttons simultaneously
H.) HOW TO RESET FILTER DIRTINESS COUNTER:
•When you got “0001” warning on the screen ,
•You can reset it by pressing FAN and Mode/OK buttons simultaneously.
Note: You can change filter dirtines alarm period on Parameter 177 . You can follow the remaining time from
Parameter 115 .

TR
I.) ENTERING TO SERVICE MENU:
To Enter:
•Press UP and DOWN buttons simultaneously
•Enter service menu password by using UP and DOWN and press Mode/OK.
Note: The Service menu password is“58”
•Then go to Parameter you want to change by using UP and DOWN buttons then press Mode/OK button
•Change the parameter by using UP and DOWN buttons then press Mode/OK button.
•Get out of menu by pressing ON/OFF button
Caution : All the changes on the service menu should be done by authorized personnel.
The damage and problems causing by unauthorized changes on the service menu will be on
user’s responsibility.

TR
J.) SELECTING TEMPERATURE CONTROL POINT
There are 4 options that unit can check the temperature;
-Room thermostate
-Return Air
-Supply Air
-Outside Air
To select one of these;
•Press UP and DOWN buttons simultaneously
•Enter service menu password by using UP and DOWN and press Mode/OK.
•
Note: Service menu password is “58”
•Then go to Parameter ‘’118’’ by using UP and DOWN buttons then press Mode/OK button
•Change the parameter by using UP and DOWN buttons then press Mode/OK button.
Parameter 118 could be one of below numbers
0-Room thermostate
1-Return Air
2-Supply Air
3-Outside Air
•Get out of menu by pressing ON/OFF button
Note: Selected sensor should be connected to the card . If not, there will be “- -“symbol on the screen.

TR
K. SETTING FAN STEP PARAMETERS
STEPKADEME AYARI
Each 6 steps of supply and exhaust fans could be set seperately..
To set step value of the fans
•When the unit is connected to power supply , press UP and DOWN buttons simultaneously
•Enter service menu password by using UP and DOWN and press Mode/OK.
•Go to step needed to be changed by using UP and DOWN and press Mode/OK.
•Change the value according to table below by using UP and DOWN and press Mode/OK.
•Check out from the menu by using ON/OFF button
Fan Step Parameters
130
Exhaust Fan 0. Step Value
0-100
131
Exhaust Fan 1. Step Value
132
Exhaust Fan 2. Step Value
133
Exhaust Fan 3. Step Value
134
Exhaust Fan 4. Step Value
135
Exhaust Fan 5. Step Value
136
Exhaust Fan 6. Step Value
137
Supply Fan 0. Step Value
0-100
138
Supply Fan 1. Step Value
139
Supply Fan 2. Step Value
140
Supply Fan 3. Step Value
141
Supply Fan 4. Step Value
142
Supply Fan 5. Step Value
143
Supply Fan 6. Step Value

TR
L. SETTING FRESH AIR DAMPER OPENING TIME
•When the unit is connected to power supply , press UP and DOWN buttons simultaneously
•Enter service menu password “58”by using UP and DOWN and press Mode/OK.
•Go to parameter ‘’199’’ by using UP and DOWN and press Mode/OK.
•Change the value by using UP and DOWN and press Mode/OK.
•Check out from the menu by using ON/OFF button
Note: Parameter 119 values as seconds
Caution;If the fans run before damper opens, fan motors could be broken..
M. ADDING PRE-HEATER
You can add preheater by configuring the below parameters ;
•When the unit is connected to power supply , press UP and DOWN buttons simultaneously
•Enter service menu password “58”by using UP and DOWN and press Mode/OK.
•Go and change to below parameter by using UP and DOWN and press Mode/OK.
•Change the value by using UP and DOWN and press Mode/OK.
•Check out from the menu by using ON/OFF button
PARAMETER
SET VALUE
EXPLANATION
423
1
After Heater Relay Selection
152
10
Hysterisis(1C=10)
154
3
PreHetaer Step Quantity

N. ERROR CODES
TROUBLE SHOOTING
CODE
EXPLANATION
E
0001
Exhaust Fan Error
Check the fan,connection cables and filter.If 11lla re fine,
reset the alarm by pressing FAN and UP buttons
simultaneously If there is a broken component replace it
with a new one.
E
0002
Supply Fan Error
Check the fan,connection cables and filter.If 11lla re fine,
reset the alarm by pressing FAN and UP buttons
simultaneously If there is a broken component replace it
with a new one.
E
0004
Electrical Heater Error
Check the electrical heater and connection cables ..If 11lla
re fine, reset the alarm by pressing FAN and UP buttons
simultaneously If there is a broken component replace it
with a new one.
E
0008
Exhaust Air Flow Error
Check the exhaust fan,connection cables ,filter and
ducting..If 11lla re fine, reset the alarm by pressing FAN
and UP buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
E
0016
Supply Air Flow Error
Check the exhaust fan,connection cables ,filter and
ducting..If 11lla re fine, reset the alarm by pressing FAN
and UP buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
E
0099
Connection Error between
Controller and Card
Check connection cables between controller and the
board
E
0256
Fire Alarm
Check if there is fire or not.. If the alarm is because of a heat
transmitter close to room thermostate , or another factor that
increases the temperature at the room artificially, make sure
that the room thermostate reads the temperature at the normal
conditions. Also check the electrical heater at the duct system.
If everything is controlled then reset the alarm by pressing FAN
and UP buttons simultaneously.

[Buraya yazın]
O.
MODBUS –RTU SETTINGS
SESESETTINGSI
Enter to Sevice Menu as it is described above (I. Entering To Service Menu)
•For Modbus ID’s go to parameter 111 . Go to Modbus ID by using UP and DOWN buttons Set and confirm
by using Mode/Ok
For Modbus Baudrate go to parameter 112 and change Modbus Baudrate by using UP and DOWN buttons . Set and
confirm by using Mode/Ok
0: 1200 Bps
1: 2400 Bps
2: 4800 Bps
3: 9600 Bps
4: 19200 Bps
5: 38400 Bps
6: 57600 Bps
Note1: All Modbus parameters are Holding register.
Note2: All Modbus parameters are Signed Integer16.
P. MODBUS REGISTER LIST
PLC Register
Parameters for Controlling the Unit
4001
0
Unit On/Off
0...1
0: Unit On 1: Unit Off
4002
1
Unit Set Temperature
0...999
280 value means 28 ºC
4003
2
Conditioning Mode
0...4
0: Manual Heating
1: Manual Cooling
2: Auto Heating
3: Auto Cooling
4: Auto
4004
3
Exhaust Fan Manual Speed Value
0...6
4005
4
Supply Fan Manual Speed Value
0...6
Temperature Parameters
4006
5
Unit Ambient Temperature
-400...999
280 value means 28 ºC
4007
6
Panel Ambient Temperature
-400...999
Temperatıre on the propanel
4008
7
Exhaust air temperature
-400...999
Exhaust air temperature
4009
8
Supply air temperarure
-400...999
If there is no temperature value on
the unit, the value will be shown as
"32767
4010
9
Outside air temperature
-400...999
4011
10
Water Coil temperature
-400...999
4012
11
Evaporator Temperature
-400...999
4013
12
Condenser Temperature
-400...999
4014
13
Exchanger Temperature
-400...999
Unit Performance Parameters
4015
14
Bms Entry
0...1
0: Unit On 1: UnitOff
4016
15
Boost Entry
0...1
0: Works as prgrammed
1: Fans work in full speed.
4017
16
Exhaust Fan Air Blowing Info
0...1
Info Exhaust Fan
4018
17
Supply Fan Air Blowing Info
0...1
Info for Supply Fan
4019
18
Filter 1 Dirtiness Info
0...1
4020
19
Filter 2 Dirtiness Info
0...1
4021
20
Electrical Heater Safety Thermostat Info
0...1
Safety Thermostate Info

[Buraya yazın]
4022
21
Exhaust Fan Thermal Error Info
0...1
Exhaust Fan Error Info
4023
22
Supply Fan Thermal Error Info
0...1
Supply Fan Error Info
4024
23
Emergency Stop Button Info
0...1
Emergency Stop Button Info
4025
24
Low Pressure Info
0...1
Low Pressure Info
4026
25
Hıgh Pressure Info
0...1
Hıgh Pressure Info
4027
26
Fire Info
0...1
Fire Info Entry
4028
27
Frost Thermostate Info
0...1
Frost Thermostate Info (Valves are open
and fans are closed during water coil
application)
4029
28
Compressor Thermal Error Info
0...1
Compressor Thermal Info (If there is an
error on the compressor, it will be
stopped.)
4030
29
Phase Error Info
0...1
Phase error Info (Unit will be stopped.)
4031
30
Exchanger Frost Info
0...1
4032
31
VRF Error
0...1
4033
32
VRF Defrost
0...1
Unit Analog Entry Registers
4034
33
Humidity Value
0...1000
The value should be between
321 to 340 .
4035
34
Air Quality Value
0...1000
4036
35
CO2 Value
0...1000
4037
36
Return Pressure Value
0...1000
4038
37
Blowing Pressure value
0...1000
4039
38
Anolog 1 Set Value
4040
39
Analog 2 Set Value
4041
40
Analog 3 Set Value
Mixing Damper Registers
4042
41
Mixing Damper Mode
0...1
4043
42
Mixing Damper Manual Value
Digital Putput Online Registers
4044
43
Fresh Air/Suction Damper Motor
0...1
0:Off 1:On
4045
44
ByPass Damper Motor
0...1
0:Off 1:On
4046
45
Heating/Cooling Coil Valve Exit
0...1
0:Off 1:On
4047
46
Heating Coil On/Off Exit
0...1
0:Off 1:On
4048
47
Cooling Coil On/Off Exit
0...1
0:Off 1:On
4049
48
Compressor Exit
0...1
0:Off 1:On
4050
49
Compressor 4 way Valve Exit
0...1
0:Off 1:On
4051
50
Unit Working Info Exit
0...1
0:Off 1:On
4052
51
Unit Error Info Exit
0...1
0:Off 1:On
4053
52
Unit Warning Info Exit
0...1
0:Off 1:On
4054
53
Exhaust Fan Run Exit
0...1
0:Off 1:On
4055
54
Supply Fan Run Exit
0...1
0:Off 1:On
4056
55
VRF On Off EXit
0...1
0:Off 1:On
4057
56
VRF Heating EXit
0...1
0:Off 1:On
4058
57
VRF Soğutma Çıkışı
0...1
0:Off 1:On
4059
58
Rotary Exchanger Exit
0...1
0:Off 1:On
4060
59
Humidifier Exit
0...1
0:Off 1:On
4061
60
Exhaust Fan Instant Exit Value
0...6
Shows instant values of fan and
electrical heater
4062
61
Supply Fan Instant Exit Value
0...6
4063
62
Last-Electrical Heater Instant Exit Value
0...3
4064
63
Pre-Electrical Heater Instant Exit Value
0...3
Instant Accessories Registers
4065
64
Exhaust Fan Analog Exit Value
0...100
Shows proportional exit values.
4066
65
Supply Fan Analog Exit Value
0...100
4067
66
Proportional Heating Valve Exit Value
0...100
4068
67
Proportional Cooling Valve Exit Value
0...100
4069
68
Proportional Heating/Cooling Valve Exit Value
0...100

[Buraya yazın]
4070
69
Proportional ByPass Damper Exit Value
0...100
4071
70
Mixing Damper Exit Value
0...100
4072
71
VRF Exit Value
0...100
Weekly Programming Parameter Registers
4073
72
Sunday Starting Time Hour/Minute
0...2359
Unit works between starting and stopping
time.
If starting and stopping times are same,
unit will work all day.
If starting time is later than stopping time ,
unit will not work.
4074
73
Sunday Stopping Time Hour/Minute
0...2359
4075
74
Monday Starting Time Hour/Minute
0...2359
4076
75
Monday Stopping Time Hour/Minute
0...2359
4077
76
Tuesday Starting Time Hour/Minute
0...2359
4078
77
Tuesday Stopping Time Hour/Minute
0...2359
4079
78
Wednesday Starting Time Hour/Minute
0...2359
4080
79
Wednesday Stopping Time Hour/Minute
0...2359
4081
80
Thursday Starting Time Hour/Minute
0...2359
4082
81
Thursday Stopping Time Hour/Minute
0...2359
The setting should be done as
➔Hour:Minute
4083
82
Friday Starting Time Hour/Minute
0...2359
4084
83
Friday Stopping Time Hour/Minute
0...2359
4085
84
Saturday Starting Time Hour/Minute
0...2359
4086
85
Saturday Starting Time Hour/Minute
0...2359
4087
86
Day Setting
1...31
4088
87
Month Setting
1...12
4089
88
Year Setting
0...99
4090
89
Hour setting
0...23
4091
90
Minute Setting
0...59
4092
91
Seconds setting
0...59
4093
92
Setting day of the week
1...7
1:Sunday 2:Monday 3:Tuesday
4:Wednesday 5:Thursday 6:Friday
7:Saturday
4094
93
Instant Weekly Programming Check
0...2
0:No weekly Programming
4095
94
RTC Module
0...1
1:Unit Works and it has a weekly
programming
4096
95
Error Value
0...99
4097
96
Warning Value
0...99
Menu Setting Parameters
4098
97
Show Fan Mod Menu
0...1
The menus needs to be shown when the
unit is on should be selected as 1
4099
98
Show Manual Heating Menu
0...1
4100
99
Show Manual Cooling Menu
0...1
4101
100
Show Auto Heating Menu
0...1
4102
101
Show Auto Cooling Menu
0...1
4103
102
Show Full Auto Menu
0...1
KeyLock
4104
103
KeyLock
0...1
0: Key Lock Active
1: Key Lock de-Active
Error Parameters
4105
104
Critical Error Info
0...1
0:No Error
1: An Error resulting complete shut down
of the unit.
4106
105
Compressor Error Info
0...1
0:No Error at compressor
1: An Error resulting complete shut
down of the compressor.
Set Temperature Parameters
4107
106
Set Temoerature Min Value
0...999
Value of 280 means 28 ºC
4108
107
Set Temperature Max Value
0...999
Value of 280 means 28 ºC
Fan Setting Parameters
4109
108
Fan Quantity
1...2
1Single
2Double
4110
109
Fan Step Value
1...6
Password Parameters

[Buraya yazın]
4111
110
Service Setting Password
0...9999
Main card password is "58"
Building Management Modbus-RTU Parameters
4112
111
Modbus ID
1...254
4113
112
Modbus Baudrate
0...7
Screen Value Registers
4114
113
Show Temperature Value
0...3
0:Do Not Show
1:OutsideTemperature
2:Supplied Air Temperature
3:Show both temperatures
4115
114
Show Analog Inlet
0...3
0:Do not show
1:CO2
2:Air Quality
3:Humidity
Filter Time Counter Parameters
4116
115
Filter Dirtiness Counter
0-9999hour
Counter increases due to working hour
of supply fan
4117
116
Unit Mode Info
0-100
0:Unit Off
1:Damper is opening
2:Fan Starts Working
3:Main Function
4:Valve Closing
5:Fan Stops
6:Frost
7:Defrost
99:Error Mode (Waiting for Reset)
Boost Mode Setting Registers
4118
117
Activate Boost
0-1
0:Deaktive
1:Aktive
Parameters for Temperature Check Point
4119
118
Temperature Check Point
0-3
0:Controller
1:Return Air Temperature
2:Supply Air Teperature
3:Outside Air Temperature
4120
119
Exhaust/Fresh Air Damper Opening Period
0-999sec.
Opens damper and start fans and
other components after waiting for
the period defined here
Auto Mode Fan Setting Parameters
4121
120
Auto Mod Fan Min. Speed
0-6
The minimum speed for fans at
auto mod
4122
121
Full Auto Mod Fan Working Stage
0-1
0: Normal
1: Working Continously
4123
122
Full Auto Mod Exhaust Fan Value
0-100
Working value for Exhaust Fan
4124
123
Full Auto Mod Supply Fan Value
0-100
Working value for Supply Fan
4125
124
Full Performance of the Fans at the start
0-1
Full Performance for the fans or not at
the start
4126
125
Passage time between fan steps
0—999sec.
Passage time between fan steps
4127
126
Fan Hysteresis Value
0-999
If fans work thermostatically, the
hysteresis value between step
changing..
4128
127
The difference value between the fans
0-999
4129
128
Fan delay time at the start
0-999sec.
Waiting time for the fan to start
4130
129
Fan working time after stop command
0-999sec.
Waiting time for fans to stop after stop
command (Cools electrical heater and
other components after they stop
during the delay time.)
4131
130
Exhaust Fan 0. Step Value
0-100
It is recommended not to work motor ,
at a value of exit voltage under 120 V.
4132
131
Exhaust Fan 1. Step Value
4133
132
Exhaust Fan 2. Step Value
4134
133
Exhaust Fan 3. Step Value
4135
134
Exhaust Fan 4. Step Value

[Buraya yazın]
4136
135
Exhaust Fan 5. Step Value
4137
136
Exhaust Fan 6. Step Value
4138
137
Supply Fan 0. Step Value
0-100
It is recommended not to work motor , at
a value of exit voltage under 120 V.
4139
138
Supply Fan 1. Step Value
4140
139
Supply Fan 2. Step Value
4141
140
Supply Fan 3. Step Value
4142
141
Supply Fan 4. Step Value
4143
142
Supply Fan 5. Step Value
4144
143
Supply Fan 6. Step Value
4145
144
Fire Scenario Selection
0-3
0: Shut down both fans
1: Exh. Fan Full Supp. Fan.Off
2: Exh. Fan Off Supp. Fan.Full
3: Both fans are working
4146
145
Cooling and Heating Hysteresis Value
0-999
Pressure Error Parameters
4147
146
Pressure Error Quantity
0-10 each
For instance, if the value is 5 and
there happens 5 pressure error
,unit shuts down. F the values is 0
then unit will shut down with the
first pressure error.
4148
147
Pressure Error Period
1-30min.
Boost ve Heater Limiting Parameters
4149
148
Maximum working time for boost
0-999min
Boost will close at the end of this period
4150
149
Heater Limiting according to Fan
0-1
Pre Heater Setting Parameters
4151
150
Pre Heater Delay time at Start
1-999 Sec.
4152
151
Pre Heater Delay time at Stop
1-999 Sec.
4153
152
Pre Heater Hysteresis Value
1…100
100 value means 10.0ºC
4154
153
Pre Heater Steps as Temperature
4155
154
Pre Heater Step Quantity
0-3
Last Heater Setting Parameters
4156
155
After Heater Opening Delay Time
1-999 Sn
4157
156
After Heater Stopping Delay Time
1-999 Sn
4158
157
After Heater Hysteresis Value
1…100
100 value means 10.0ºC
4159
158
After Heater Steps as Temperature
4160
159
After Heater Step Quantity
Accessories Setting Parameters
4161
160
Pre Heater Set Temperature
-400…999
4162
161
ByPass Histeresis Value
1…999
4163
162
Rotary Exchanger Histerezsis Value
1…999
PID Setting Parameters
4164
163
Valve P Value
4165
164
Valve I Value
Compressor Setting Parameters
4166
165
Compressor Starting Time
1…999
Starting and Stopping Time of
Compressor can be set.
4167
166
Compressor Stopping Time
1…999
4168
167
Compressor Histeresis Value
1…100
Compresor Defrost Setting Parameters
4169
168
Fan Step in case of defrost
0...6
4170
169
Min. Temperature Value for defrost
-400...999

[Buraya yazın]
4171
170
Max. Temperature Value for defrost
-400...999
4172
171
Max.Defrost Period
1...100
4173
172
Waiting Time between two defrosts
1…100
Frost Protection Setting Parameters
4174
173
Heating Coil min Temp. Value in case of Frost
-400...999
4175
174
Heating Coil max. Temp. Value in case of Frost
-400...999
4176
175
Exchanger min Temp. Value in case of Frost
-400...999
4177
176
Exchanger max. Temp. Value in case of Frost
-400...999
4178
177
Dirty Filter Warning Time
1...9999
After working for 1200 hours,,this alarm
will appear on screen.
4179
178
Exhaust Fan Air Blowing Control Period
1...9999
4180
179
Supply Fan Air Blowing Control Period
1...9999
Universal Input Check Parameeters
4182
181
Number 1 Universal Inlet
-400...999
4183
182
Number 2 Universal Input
-400...999
4184
183
Number 3 Universal Input
-400...999
4185
184
Number 4 Universal Input
-400...999
4186
185
Number 5 Universal Input
-400...999
4187
186
Number 6 Universal Input
-400...999
4188
187
Number 7 Universal Input
-400...999
4189
188
Number 8 Universal Input
-400...999
4190
189
Number 9 Universal Input
-400...999
4191
190
Number10 Universal Input
-400...999
4192
191
Number 11 Universal Input
-400...999
4193
192
Number 12 Universal Input
-400...999
4194
193
Number 13 Universal Input
-400...999
4195
194
Number 14 Universal Input
-400...999
4196
195
Number 15 Universal Input
-400...999
4197
196
Number 16 Universal Input
-400...999
4198
197
Number 17 Universal Input
-400...999
4199
198
Number 18 Universal Input
-400...999
4200
199
Number 19 Universal Input
-400...999

Digital OutputCheck Parameters
4202
201
Number 1 Digital Output
0...1
4203
202
Number 2 Digital Output
0...1
4204
203
Number 3 Digital Output
0...1
4205
204
Number 4 Digital Output
0...1
4206
205
Number 5 Digital Output
0...1
4207
206
Number 6 Digital Output
0...1
4208
207
Number 7 Digital Output
0...1
4209
208
Number 8 Digital Output
0...1
4210
209
Number 9 Digital Output
0...1
4211
210
Number 10 Digital Output
0...1
4212
211
Number 11 Digital Output
0...1
4213
212
Number 12 Digital Output
0...1
4214
213
Number 13 Digital Output
0...1
4215
214
Number 14 Digital Output
0...1
4216
215
Number 15 Digital Output
0...1
4217
216
Number 16 Digital Output
0...1
4218
217
Number 17 Digital Output
0...1
4219
218
Number 18 Digital Output
0...1
4220
219
Number 19 Digital Output
0...1
Analog Input Check Parameters
4222
221
Number 1 Analog Input
-9999...9999
4223
222
Number 2 Analog Input
-9999...9999
4224
223
Number 3 Analog Input
-9999...9999
4225
224
Number 4 Analog Input
-9999...9999
4226
225
Number 5 Analog Input
-9999...9999
4227
226
Number 6 Analog Input
-9999...9999
4228
227
Number 7 Analog Input
-9999...9999
4229
228
Number 8 Analog Input
-9999...9999
Analog Output Check Parameters
4232
231
Number 1 Analog Output
-9999...9999
4233
232
Number 2 Analog Output
-9999...9999
4234
233
Number 3 Analog Output
-9999...9999
4235
234
Number 4 Analog Output
-9999...9999
4236
235
Number 5 Analog Output
-9999...9999
4237
236
Number 6 Analog Output
-9999...9999
4238
237
Number 7 Analog Output
-9999...9999
4239
238
Number 8 Analog Output
-9999...9999
Universal Input Calibration Setting Parameters
4242
241
Number 1 Universal Input Calibration
-9999...9999
4243
242
Number 2 Universal Input Calibration
-9999...9999
4244
243
Number 3 Universal Input Calibration
-9999...9999
4245
244
Number 4 Universal Input Calibration
-9999...9999
4246
245
Number 5 Universal Input Calibration
-9999...9999
4247
246
Number 6 Universal Input Calibration
-9999...9999
4248
247
Number 7 Universal Input Calibration
-9999...9999
4249
248
Number 8 Universal Input Calibration
-9999...9999
4250
249
Number 9 Universal Input Calibration
-9999...9999
4251
250
Number 10 Universal Input Calibration
-9999...9999
4252
251
Number 11 Universal Input Calibration
-9999...9999
4253
252
Number 12 Universal Input Calibration
-9999...9999
4254
253
Number 13 Universal Input Calibration
-9999...9999
4255
254
Number 14 Universal Input Calibration
-9999...9999

4256
255
Number 15 Universal Input Calibration
-9999...9999
4257
256
Number 16 Universal Input Calibration
-9999...9999
4258
257
Number 17 Universal Input Calibration
-9999...9999
4259
258
Number 18 Universal Input Calibration
-9999...9999
4260
259
Number 19 Universal Input Calibration
-9999...9999
Universal On/Off Selection Setting Parameters
4262
261
Uın1 Input On/Off Selection
0…1
.
4263
262
Uın2 Input On/Off Selection
4264
263
Uın3 Input On/Off Selection
4265
264
Uın4 Input On/Off Selection
4266
265
Uın5 Input On/Off Selection
4267
266
Uın6 Input On/Off Selection
4268
267
Uın7 Input On/Off Selection
4269
268
Uın8 Input On/Off Selection
4270
269
Uın9 Input On/Off Selection
4271
270
Uın10 Input On/Off Selection
4272
271
Uın11 Input On/Off Selection
4273
272
Uın12 Input On/Off Selection
4274
273
Uın13 Input On/Off Selection
4275
274
Uın14 Input On/Off Selection
4276
275
Uın15 Input On/Off Selection
4277
276
Uın16 Input On/Off Selection
4278
277
Uın17 Input On/Off Selection
4279
278
Uın18 Input On/Off Selection
4280
279
Uın19 Input On/Off Selection
Universal(Digital) Input Signal Detecting Delay Setting Parameters
4282
281
Uın1 Input Signal Detecting Delay
0...999
.
4283
282
Uın2 Input Signal Detecting Delay
4284
283
Uın3 Input Signal Detecting Delay
4285
284
Uın4 Input Signal Detecting Delay
4286
285
Uın5 Input Signal Detecting Delay
4287
286
Uın6 Input Signal Detecting Delay
4288
287
Uın7 Input Signal Detecting Delay
4289
288
Uın8 Input Signal Detecting Delay
4290
289
Uın9 Input Signal Detecting Delay
4291
290
Uın10 Input Signal Detecting Delay
4292
291
Uın11 Input Signal Detecting Delay
4293
292
Uın12 Input Signal Detecting Delay
4294
293
Uın13 Input Signal Detecting Delay
4295
294
Uın14 Input Signal Detecting Delay
4296
295
Uın15 Input Signal Detecting Delay
4297
296
Uın16 Input Signal Detecting Delay
4298
297
Uın17 Input Signal Detecting Delay
4299
298
Uın18 Input Signal Detecting Delay
4300
299
Uın19 Input Signal Detecting Delay
Digital Output On/Off Selection Setting Parameters
4302
301
Dın1 Output On/Off Selection
0...1
4303
302
Dın2 Output On/Off Selection
4304
303
Dın3 Output On/Off Selection
4305
304
Dın4 Output On/Off Selection
4306
305
Dın5 Output On/Off Selection
4307
306
Dın6 Output On/Off Selection

4308
307
Dın7 Output On/Off Selection
4309
308
Dın8 Output On/Off Selection
4310
309
Dın9 Output On/Off Selection
4311
310
Dın10 Output On/Off Selection
4312
311
Dın11 Output On/Off Selection
4313
312
Dın12 Output On/Off Selection
4314
313
Dın13 Output On/Off Selection
4315
314
Dın14 Output On/Off Selection
4316
315
Dın15 Output On/Off Selection
4317
316
Dın16 Output On/Off Selection
4318
317
Dın17 Output On/Off Selection
4319
318
Dın18 Output On/Off Selection
4320
319
Dın19 Output On/Off Selection
Analog Input Minimum Value Calibration Setting Parameters
4322
321
Analog Input 1 Minimum Value
-9999...9999
4323
322
Analog Input 2 Minimum Value
-9999...9999
4324
323
Analog Input 3 Minimum Value
-9999...9999
4325
324
Analog Input 4 Minimum Value
-9999...9999
4326
325
Analog Input 5 Minimum Value
-9999...9999
4327
326
Analog Input 6 Minimum Value
-9999...9999
4328
327
Analog Input 7 Minimum Value
-9999...9999
4329
328
Analog Input 8 Minimum Value
-9999...9999
4330
329
Analog Input 9 Minimum Value
-9999...9999
Analog Input Maximum Value Calibration Setting Parameters
4332
331
Analog Input 1 Maximum Value
-9999...9999
4333
332
Analog Input 2 Maximum Value
-9999...9999
4334
333
Analog Input 3 Maximum Value
-9999...9999
4335
334
Analog Input 4 Maximum Value
-9999...9999
4336
335
Analog Input 5 Maximum Value
-9999...9999
4337
336
Analog Input 6 Maximum Value
-9999...9999
4338
337
Analog Input 7 Maximum Value
-9999...9999
4339
338
Analog Input 8 Maximum Value
-9999...9999
4340
339
Analog Input 9 Maximum Value
-9999...9999
Analog Output Minimum Value Calibration Setting Parameters
4342
341
Analog Output 1 Minimum Value
-9999...9999
4343
342
Analog Output 2 Minimum Value
-9999...9999
4344
343
Analog Output 3 Minimum Value
-9999...9999
4345
344
Analog Output 4 Minimum Value
-9999...9999
4346
345
Analog Output 5 Minimum Value
-9999...9999
4347
346
Analog Output 6 Minimum Value
-9999...9999
4348
347
Analog Output 7 Minimum Value
-9999...9999
4349
348
Analog Output 8 Minimum Value
-9999...9999
4350
349
Analog Output 9 Minimum Value
-9999...9999
Analog Output Miimum Value Calibration Setting Parameters
4352
351
Analog Output 1 Maximum Value
-9999...9999
4353
352
Analog Output 2 Maximum Value
-9999...9999
4354
353
Analog Output 3 Maximum Value
-9999...9999
4355
354
Analog Output 4 Maximum Value
4356
355
Analog Output 5 Maximum Value
-9999...9999
4357
356
Analog Output 6 Maximum Value
-9999...9999
4358
357
Analog Output 7 Maximum Value
-9999...9999