
3
If contact is in the closed
posion or device works up
to the AirFilterTimerLimit
(default 1200 hour) , alarm
happens. Device is connu-
ing normal operaon du-
ring alarm.
Contact must be in the closed posion or AirFilterTime-
rAlarm (BMS 145., Service Menu 44. parameter) must
be set to 0 to eliminate the alarm.
8.3 DAMPER CONTROL
In the scenarios contained in the Damper control, one
relay output reserved into for Damper control.
Fresh air and/or exhaust air damper motors are cont-
rolled. Damper motor is controlled considering the
necessary delays ( The device On/O moments, alarm
moments... ).
One relay output reserved into for damper. If there are
more damper motor, must be connected in parallel.
Note : Damper motor must be in the On/O and
spring return property.
MANUAL for JAKKA ADVANCED CONTROLLER
8.4 REMOTE CONTROL
The remote On/O funcon. This contact can be used
to control the device via building automaon/PLC/
External Switches.
To use this feature, selected scenario must be contain
remote control contact.
8.2 ELECTRICAL HEATER CONTROL
1. Controlled Depending on Room Temperature :
Electrical heater is controlled by sensor on the panel
or return air temperature sensor. Control is acve wit-
hout any adjustment. (Default Control Type)
7. ÖZEL KONTROL FONKSİYONLARI
7.1 HAVA KALİTESİ VEYA CO2 KONTROLÜ
0-10V air quality or CO2
sensor must be connected
properly. Operaon mode
must be set to other than
venlaon (heang or coo-
ling) and fan speed must
be set to Auto. When these
condions are met, the fan speed is controlled accor-
ding to the air quality or CO2 sensor value.
8. SPECIAL CONTROL FUNCTIONS
8.1 AIR QUALITY OR CO2 CONTROL
7.4 AL:04 FIRE CONTACT ALARM (NO)
If contact is in the closed
posion, alarm happens.
Supply air fan is closed,
Exhaust air fan run at
maximum speed. All out-
puts are closed except
Damper. The Panel locked.
Disconnect the power of the device to eliminang the
alarm and return to normal operaon.
Note 1: Aer the device restarted, press together MODE and
▲ keys unl unlock the device.
7.3 AL:03 AIR FILTER ALARM (NO)
9.1 MENU DESCRIPTION
While the device is in the O Posion, press together
MODE and ▼ key for 5 seconds.
In the service menu “Main Parameter” is replaced by
the MODE and FAN keys.
“Auxiliary Parameter” is replaced by the ▲ and ▼
keys.
Main Parameter Auxiliary Parameter
9. SERVICE MENU OPERATIONS
2. Controlled Depending on Outdoor Temperature: If
outdoor temperature value less than value set in the
service menu, the heater stages is acvated.
Note: Control according to the outdoor air temperature to
be acve, parameter sengs must be made of appropriate.
(See. Service Menu Operaons)
9.2 PASSWORD PARAMETER
While the device is in the O Posion, press together
MODE and ▼ key for 5 seconds.
To make changes in the parameters, password must be
entered as “123”, to 99. parameter.
Firstly, “Main Parameter”
must be replaced as 99, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be replaced as
“123”, by the ▲ and ▼
keys.
Otherwise, made changes won’ t be saved.
Note: This process is part of the entry to the Service
Menu and must be applied in all entries.