Jameson Aftercooler JAC-245 User manual

1451 Old North Main Street | Clover, SC 29710 | 800.346.1956
JAMESONLLC.com
Jameson Aftercooler: Operation and Maintenance Manual
Description of operation
A Jameson Aftercooler is a portable system consisting of an air-cooled trim cooler and a
separator/filter. Wet warm air enters the trim cooler where it is cooled to a temperature
approaching ambient. Water is condensed out during this cooling process. The saturated air
and the liquid water proceed to the inlet of the separator/filter where the liquid water is
removed. The process air out of the system is ready for use.
SPECIFICATIONS
2.1 INLET CONDITIONS
Refer to Table 1 below for the recommended operating conditions for the available
Jameson Aftercooler models.
JAC-245
JAC-540
Maximum Working Pressure (PSI)
250
250
Maximum Working Temperature
Aftercooler (°F)
250
250
Maximum Working Temperature
Separator (°F)
150
150
Minimum Recommended
Temperature (°F)
35
35
Internal Airflow Rotary
Compressor (Max CFM)
245 539
Internal Airflow Piston
Compressor (Max CFM)
181 432
Max Air Pressure to Motor (PSI)
60
40
Motor Air Consumption (CFM)
17
25
Max Fan RPM
3450
1725
Table 1: Inlet Conditions

1451 Old North Main Street | Clover, SC 29710 | 800.346.1956
SpartacoGroup.com
2.2 DIMENSIONS
Figure 1: Dimensional drawing
Dimension
JAC-245
JAC-540
A
30.0” (762mm)
36.2” (920mm)
B
42.0” (1067mm)
42.0” (1067mm)
C
24.7” (628mm)
28.9” (627mm)
D
25.1” (638mm)
30.2” (767mm)
Table 2: Overall Dimensions
Inlet Options
JAC-245 JAC-540

1451 Old North Main Street | Clover, SC 29710 | 800.346.1956
SpartacoGroup.com
Outlet Options
JAC-245 JAC-540
Operation
The simple design of the system allows for easy operation. The system requires daily filter
draining and periodic cooler draining to ensure peak performance.
Setup
1. Connect air line from compressor to inlet side of aftercooler, ensure proper
safety clips are installed.
2. Connect air line from aftercooler to equipment, ensure the outlet ball valve
is closed.
3. Slowly pressurize the system and allow some air to bleed through the drain
valves. Once there is no additional liquid coming through the valves they
can be closed.
4. Adjust motor supply pressure to meet the pressure specifications in Table 1
Main Filter Draining – The accumulated water and oil solution should be drained
from the main filter every 4 to 8 hours (or as required based on environmental
conditions).
*If the filter is not drained regularly, it may become flooded and the accumulated
liquid may enter the air system and cause damage to downstream equipment.
Locate the drain valve at the bottom of the large filter assembly. Turn the
fitting to open the valve and drain liquid from the filter assembly. Once
liquid has finished draining close the valve.

1451 Old North Main Street | Clover, SC 29710 | 800.346.1956
SpartacoGroup.com
Motor Filter Draining -The accumulated water and oil solution should be drained
from the main filter every 2 to 4 hours (or as required based on environmental
conditions).
Locate the drain valve at the bottom left of the motor regulator assembly.
Turn the fitting to open the valve and drain liquid from the filter assembly.
Once liquid has finished draining close the valve.
Cooler Draining – The accumulated water and oil solution should be drained from
the radiator assembly periodically to prevent the cooler from becoming flooded.
Remove supply hose on bottom of radiator assembly and allow any liquid to
drain. Reattach the hose and check for air leaks.
Motor Lubrication – The pneumatic motor should be lubricated to run properly.
The bowl located on the right side of the motor regulator assembly is for pneumatic
tool oil. Fill to the appropriate fill lines indicated on the bowl.
Maintenance
Daily Inspection
•Check the operating conditions, ambient temperature and inlet pressure.
•Monitor the unit to make sure it is operating properly.
•Test separator filter drain for proper draining.
•Visually check the unit piping for damage or leaks
Scheduled Maintenance
12 Months
•Replace the separator filter element
•Clean the exterior of the aftercooler
24-60 Months
•Periodically the aftercooler core should be cleaned internally if the
process air contains excessive amounts of lubricating fluids

1451 Old North Main Street | Clover, SC 29710 | 800.346.1956
SpartacoGroup.com
Cleaning the outside of the aftercooler core
The core should be cleaned regularly. Accumulation of dirt or other
contaminants such as oils will greatly reduce the efficiency of the pre-
cooler.
Normal accumulation of dirt can be removed by blowing the core off with
compressed air. If the core becomes contaminated with oil-laden particles,
it can be steam cleaned. Clean with extreme care as the aluminum fins can
be easily damaged.
Preparation for Storage
Shut off the air supply to the Aftercooler and open the filter drain valve to
completely depressurize the system.
Open the filter drain valve to drain all accumulated liquid in the cooler.
Disconnect the inlet and outlet air hoses.
STORAGE
Store the Aftercooler in a location that is free from extreme humidity and
corrosive gasses, which can cause damage to the unit.
Replacement Parts
Description
Part Number
QTY
Required
JAC-245
JAC-540
Axle
FB200015
FB200008
1
Filter Assembly
FB200012
FB200002
1
Pneumatic
Regulator
FB200007
1
Radiator Assembly
FB200011
FB200001
1
Radiator Shroud
FB200022
FB200021
1
Wheel
DR200321
2
Wheel Nut
DR200323
2
To order parts contact your local Jameson representative, the
representative that sold the aftercooler, or the factory.
When ordering parts, have the system model number ready.
Jameson Customer Service can be reached by calling 800-346-1956.
Hours are 8:00 AM EST to 5:00 PM EST, M-F.
This manual suits for next models
1
Table of contents
Popular Air Compressor manuals by other brands

Power Craft
Power Craft PCC 210/8/24 operating instructions

Danfoss
Danfoss SC Series Wiring diagram

Schneider Airsystems
Schneider Airsystems A 713 000 Original operating manual

EXTOL PREMIUM
EXTOL PREMIUM CC 120 Translation of the original user manual

Danfoss
Danfoss LLZ-B instructions

GEA
GEA Bock HGX46 CO2 T Series Assembly instructions