JETI model Central Box 200 User manual

EN
1. Introduction ..................................................................................... 2 EN
1.1 Attributes ................................................................................... 3 EN
2. Description ........................................................................................ 3 EN
2.1 Central Box 200 ....................................................................... 3 EN
2.2. Central Box 100 ....................................................................... 5 EN
2.3 Magnetic switch ( Central Box 200 only) ............................ 6 EN
3. Connection ...................................................................................... 7 EN
3.1 Power Supply ............................................................................ 7 EN
3.2 Overload protection of servos ............................................ 10 EN
3.3 Connecting Central Box – PPM variant ............................ 11 EN
3.4 Connecting Central Box – EX Bus variant ........................ 12 EN
4. Configuration via JETIBOX ....................................................... 14 EN
4.1 Actual values .......................................................................... 15 EN
4.2 Minimum / Maximum values ............................................. 15 EN
4.3 Setting ..................................................................................... 16 EN
4.4 Out Pin Set ............................................................................... 17 EN
4.5 Alarms .................................................................................... 18 EN
4.6 Service information .............................................................. 19 EN
5. Configuration via the DC/DS transmitter ............................. 20 EN
5.1 General Settings .................................................................... 21 EN
5.2 Fail-Safe .................................................................................. 22 EN
5.3 Servo Output Mapping ....................................................... 23 EN
5.4 Telemetry ............................................................................... 23 EN
5.5 Telemetry Min/Max .............................................................. 24 EN
5.6 Reset to factory settings ...................................................... 24 EN
6. Firmware update ........................................................................... 25 EN
7. Safety precautions for working with magnets ................... 26 EN
8. Technical specifications of the Central Box .......................... 27 EN
9. Warranty, service and the technical support ....................... 28 EN
1 EN

EN
The Central Box is a switchboard designed for the complete
management of servos in a model with an emphasis on safety. The
Central Box has a unique design that provides overload protection
at each servo output. The Central Box can manage two batteries
and fully supports the JETI EX telemetry system. Up to two receivers
with serial (PPM, EX Bus) output can be connected to the Central
Box. With JETI DC/DS transmitter, the full potential of the Central
Box can be used, such as an easy way to configure the Central Box,
EX telemetry, and very fast servo response.
1 Introduction ENGLISH
100100100
2 EN

EN
1.1 Attributes
• Overload protection on each channel
• Possibility to connect up to 2 receivers with serial interface
(PPM, EX Bus)
• Built-in Expander function for up to 3 sensors
• Input for magnetic switch or RC switch (Central Box 200 only)
• MPX battery input connector(s):
1x Central Box 100, 2x Central Box 200
• 100Hz mode of servo outputs (10ms period)
• Supports EX telemetry (voltage, current, capacity, and
temperature measurement, overload indication, ...)
• Easy settings changes via DC/DS transmitter
• Firmware updates by user
• Suitable for use with high voltage (HV) servos
• Compact size for easy installation
• Each output is individually configurable (channel assignment,
trim, reverse, ATV)
2 Description
2.1 Central Box 200
Central Box 200 has 15 outputs for servos with overload
protection.
Channels 14 and 15 are configurable as:
• servo output
• an input for telemetry sensor
Ext1 port can be configured for use as:
• an output to connect a JETIBOX or Duplex EX receiver to
either configure the Central Box or for the output of
telemetry data
• an input for telemetry sensors
3 EN

EN
The Ext1 slot is also used for the firmware update connection (using
the USBa).
Rx1 - primary input for connecting receivers with serial output (EX
bus or PPM)
Rx2 - secondary (backup) input for connecting receivers with serial
output (EX bus or PPM)
Switch input is reserved for connecting a magnetic switch or RC
switch (optional accessories).
BATT1 and BATT2 – MPX connectors for connecting batteries or a
BEC, etc., to power the servos and receivers connected to the
Central Box.
Fig. 1: Central Box description
RC Switch Magnetic Switch
input voltage
4-14V
4 EN

EN
2.2 Central Box 100
The Central Box 100 has 8 servo outputs with overload
protection, labeled 1 through 8.
OUT/IN – universal input/output for switching additional
functions or for supervising the operational status
Ext1 – this port can be configured for use as:
• an output to connect a JETIBOX or Duplex EX receiver to
either configure the Central Box or for the output of
telemetry data
• an input for telemetry sensors
The Ext1 slot is also used for the firmware update connection
(using the USBa).
Rx1 - primary input for connecting receivers with serial output
(EX bus or PPM)
Rx2 - secondary (backup) input for connecting receivers with
serial output (EX bus or PPM)
BATT1 – MPX connector for connecting batteries or a BEC, etc., to
power the servos and receivers connected to the Central Box.
7
Rx 1
Rx 2
Ext.
Out/In
BATT
8
8 channel servo interface
100100100
input
voltage
4-14V
Input
Voltage
Fig. 2: Central Box 100 description
5 EN

EN
2.3 Magnetic switch ( Central Box 200 only)
The magnetic switch is used to turn the Central Box 200 on or off
and is connected to a separate slot labeled “Switch”. To turn on the
Central Box using the magnetic switch it is necessary to hold the
supplied magnet carrier (key) to the target so that the carrier (key)
and the target on the magnetic switch are properly oriented
(align the dots).
Fig. 3: Description of magnetic switch and the key
Green LED
- flashing LED signals proper detection of the magnet key
- steady LED signals “On” state
When the magnet key is held to the target in the proper orientation,
the green LED glow steadily after 1 second indicating that the
electronic switch is turned on.
Switching off is done in a similar manner, when the magnet key is
held to the target in the proper orientation, after 1 second, the
green LED goes off and the system switches off.
If the switch is not plugged in the Central Box, the Central Box is
switched on.
The system remembers whether it has been switched on or off. If
the system is switched “on” via the magnetic switch and then the
power supply is disconnected, when the batteries are re-connected
to the system automatically returns to the “on” state. For safety
reasons, always switch the system off via magnetic switch before
disconnecting the power batteries.
Key
Mounting Hole Target Led On
6 EN

EN
When turning on, connect the batteries first and then turn the
system on via magnetic switch. Keep the same rule when switching
off. First switch the system off via magnetic switch and then
disconnect the batteries.
The Central Box is connected to the power supply, receiver, servos,
controller/controllers and eventually sensors. Please follow the
subsequent general guidelines about proper connection of the
Central Box and these other components.
3.1 Power Supply
The Central Box can be powered from batteries which are directly
connected, from voltage regulators connected to batteries or via
BEC. When selecting power sources for the Central Box, be sure to
follow the minimum power requirements. Together, both power
supplies methods must be able to supply a 15A continuous and
90A peak current. If the power source is not strong enough, the
overload protection feature of the Central Box may not function
correctly.
The power batteries are connected to the Central Box using MPX
connectors. The Central Box allows up to two batteries to be
connected. During use, the power is actually supplied from the
battery with the higher voltage. If the voltage is the same, the
power can be used from both batteries at the same time. When the
voltage of the batteries is different, the power is not shared and
each pack is isolated from each other. This allows you to use
batteries of different capacity, number of cells, and chemistry type.
If the power for the Central Box is provided only from one battery, it
can be connected via BATT1 or BATT2 input.
3 Connection
7 EN

EN
Fig. 4: Example of the Central Box 200 powered for use with standard
servos (voltage range up to 6V)
RC Switch Magnetic Switch
Input
Voltage
6V
SERVO standard
SERVO standard
Rsat2 (Rx2)
Rsat2 (Rx1)
input voltage
4-14V
Rsat2 (Rx1)
Rsat2 (Rx2)
7
Rx 1
Rx 2
Ext.
Out/In
BATT
8
8 channel servo interface
100100100
input
voltage
4-14V
Input Voltage 6V
SERVO standard
Fig. 5: Example of the Central Box 100 powered for use with standard
servos (voltage up to 6V)
8 EN
PPM
PPM
PPM
PPM

EN
Central Box does not contain circuitry to stabilize or regulate
voltage to the servos.
The level of the input voltage is equal to the level of (output) supply
voltage level to the servos. Be sure to match the proper type of servos
with your selected power supply. Eg. when using 2 Li-xx cells without a
regulator, it is necessary to use servos labeled “High Voltage”.
Fig. 6: Example of the Central Box 200 powered for use with HIGH Voltage
servos
RC Switch Magnetic Switch
Input
voltage
8.4V
SERVO High Voltage
Rsat2 (Rx2)
Rsat2 (Rx1)
SERVO High Voltage
input voltage
4-14V
It is not recommended to supply power to the
Central Box through the outputs for servos, sensors
or receivers.
Caution:
9 EN
PPM
PPM

EN
3.2 Overload protection of servos
The Central Box has an overload protection circuit on every servo
output. In case of an overload, the affected servo output is
disconnected from the power supply while the remaining servo
outputs are still powered.
Rsat2 (Rx1)
Rsat2 (Rx2)
7
Rx 1
Rx 2
Ext.
Out/In
BATT
8
8 channel servo interface
100100100
input
voltage
4-14V
Input Voltage 8.4V
SERVO High Voltage
Fig. 7: Example of the Central Box 100 powered for use with HIGH Voltage
servos
SERVO
SERVO
SERVO
NO
SERVO
NO
SERVO
YES
Fig. 8: Correct connection of servos to the Central Box
10 EN
PPM
PPM

EN
3.3 Connecting Central Box – PPM variant
The receivers can be connected to the Central Box using the Rx1
and Rx2 inputs.
The Ext1 port is for output of telemetry data from the Central Box in
the form of EX telemetry. To use the Central Box telemetry and other
sensors connected to it, use a Duplex EX receiver. Simply connect
the Central Box output labeled Ext1 with the Duplex EX receiver
input labeled Ext.
Channels 14 and 15 can be configured as servo outputs, or as
inputs for telemetry sensors .( Central Box 200 only)
Configuring the Central Box is in this way done by using a JETIBOX;
either directly connected to the Central Box, or wirelessly using a
JETI transmitter.
Caution: It is not recommended:
- to connect more Central Box outputs to one servo
- to use a Y cable (connecting two servos to one
output)
7
Rx 1
Rx 2
Ext.
Out/In
BATT
8
8 channel servo interface
100100100
input
voltage
4-14V
Input Voltage
SERVO
Rsat2 (Rx1)
Rsat2 (Rx2)
Fig. 9: Block diagram of Central Box 100 connection - PPM variant
11 EN
PPM
PPM
Ext.

EN
RC Switch Magnetic Switch
Input Voltage
SERVO
Rsat2 (Rx1)
SERVO
Rsat2 (Rx2)
SERVO/Sensor
input voltage
4-14V
Fig. 10: Block diagram of Central Box 200 connection - PPM variant
3.4 Connecting Central Box – EX Bus variant
Receivers can be connected to the Central Box using the Rx1 and
Rx2 inputs.
Ext1 is an input for telemetry sensor. Telemetry is transmitted to the
receivers via EX Bus.
Channels 14 and 15 can be configured as servo outputs or as
inputs for connecting telemetry sensors ( Central Box 200 only).
Configuring the Central Box is in this case done directly in the
transmitter via EX Bus.
When operating the Central Box with DC/DS transmitter, it is
recommended to use two receivers communicating with the
transmitter in the wireless mode "Double path".
12 EN
PPM
PPM
Ext.

EN
7
Rx 1
Rx 2
Ext.
Out/In
BATT
8
8 channel servo interface
100100100
input
voltage
4-14V
Input Voltage
SERVO
Rsat2 (Rx1)
Rsat2 (Rx2)
Jetibox/Sensor
Fig. 12: Block diagram of Central Box 200 connection - EX Bus variant
RC Switch Magnetic Switch
Input Voltage
SERVO
Rsat2 (Rx1)
SERVO
Rsat2 (Rx2)
SERVO/Sensor
Jetibox/Sensor
input voltage
4-14V
Fig. 11: Block diagram of Central Box 100 connection - EX Bus variant
The Central Box can be configured in two ways:
• by JETIBOX connection (directly to the Central Box or wirelessly via
the transmitter)
• by DC/DS transmitter via Device Explorer (EX Bus)
13 EN
PPM
PPM
PPM
PPM

EN
4 Configuration via JETIBOX
The JETIBOX terminal can be used for parameter setting and
retrieving data. After connecting to the Central Box (output Ext1), a
startup screen appears that contains identification of the device in
the first line of the JETIBOX display. The second line contains the
data showing the consumed capacity of batteries 1 and 2.
By pushing the R button (to the right) on the JETIBOX, you get to the
expander menu.
In the expander menu, the second lines display the sensors that are
connected to inputs Ext1, Ext2/15 and Ext3/14.
Using buttons U and D (down and up arrows) of the JETIBOX it is
possible to browse through the expander inputs. The selected
input is marked with a curly bracket brace after the input number,
eg. 1}. By pushing the R button (right arrow) it is possible to enter a
selected sensor, where you can adjust and display its parameters.
Return from the sensor menu:
- by holding the L button (left arrow) for extended time
- by holding the L button (left arrow) for short time, in
case you are in the basic menu of the sensor (in the first line there is
identification of the sensor and in the second line there are actual
data, such as „MUI 30; 14,2V 7,8A“)
The input marked 1}… means that there is no device connected to
this input or the connected device is not compatible, or the input
from the Central Box is not properly configured.
By pushing the D button (down), you get from the initial screen of
the Central Box to its menu.
14 EN

EN
• Temperature – actual temperature of Central Box
• Information on the status of receivers - number of detected
channels and the period of signal
4.2 Minimum / Maximum values
*CENTRAL BOX*: MIN / MAX – by pushing the D button (down
arrow) you select a display of extreme voltage, current,
temperature, and status of the receiver, which occurred during the
operation. Recorded extremes are deleted manually in the Settings
menu - Erase Data.
• Minimal voltage – the lowest voltage detected by the Central
Box on the inputs during its operations
• Maximal voltage – the highest voltage detected by the Central
Box on the inputs during its operation
• Maximal current – the highest current detected by the Central
Box on the inputs during its operation
4.1 Actual values
*CENTRAL BOX*:
Actual Value – by pushing the D button (down arrow) you select
the display of actual measured values
• Accu voltage - shows the actual voltage of both inputs
• Accu current - displays the actual current flowing from the
battery to the output
• Accu capacity – consumed capacity of each battery
• Over-I Monitor - indication of servo output; (-) output is fine (x)
the output is overloaded. Outputs are ordered:
Fig. 13: Description of outputs
15 EN

EN
• Min/Max Temper. - the highest and the lowest temperature of
the Central Box during its operation (since the last manual reset)
Statistics of the received signal expressed in time
R1: how long was the signal from the primary receiver available to
the Central Box
R2: how long was the signal from the secondary receiver available
to the Central Box
Statistics of the received signal expressed as a percentage
R1: what percentage of the total operating time was the signal from
the primary receiver available to the Central Box
R2: what percentage of the total operating time was the signal from
the secondary receiver available to the Central Box
• Over-I Monitor - indication of servo output during the operating
time of the Central Box; (-) output is fine (x) the output is overloaded
4.3 Setting
*CENTRAL BOX*: SETTING – By pushing the D button (down
arrow) you get to the basic setting of the device.
• Fail Safe – switches on/off of the Fail Safe function. If the Fail Safe
function is deactivated, there is no signal generated in any Central
Box outputs at the signal loss. If you activate the Fail Safe function,
you can also select how the Central Box responds at the signal loss
for each of the individual outputs (OUT off, hold, fail safe).
• Signal Fault Delay – the length of time from when the Central
Box detects a signal loss to when the programmed Fail Safe output
is performed. During this time the last servo input is held. After the
selected time has elapsed, the Central Box outputs behave
according to setting for each specific output.
• Output Period – setting for the period of the output signals
(default Auto-synchronous mode with the transmitter ). This
parameter significantly affects the behavior of the servos. For
analog servos the reaction (response) accelerates and the power
16 EN

EN
consumption is higher when the values for the output period are
lower. This can lead to vibration in some servos if the values are set
too low.
• Erase data – by pushing the arrows R and L (right and left)
together, the minimum and maximum are reset, see "MIN / MAX -
Minimum / Maximum".
• Shutdown Voltage - input voltage level at which the Central Box
automatically turns off. If Central Box evaluates the input voltage is
lower than the stop level for more than 60 seconds, it automatically
turns off.
4.4 Out Pin Set
*CENTRAL BOX*: Out Pin Set – pushing the D button (down arrow)
moves you to basic settings of particular outputs of the Central Box.
• Set Output pin -selection of the slot that will be used for the
following settings. In this menu the output deflection of the
selected output is displayed as a percentage. Y1 is the Central Box
output labeled 1, Y2 is the Central Box labeled 2, etc.
• Function – setting of alternative functions of the outputs. This
function is available for outputs:
Central Box 200
• Y14 and Y15: Servo Output function or Telemetry Input.
• EXT1: Telemetry Input function or JETIBOX
Central Box 100:
• EXT1: Telemetry Input function or JETIBOX
• SetInChannel – assigns the input channel (marked as Chx) to a
specific output (marked as Yx)
• Reverse – reverses the output direction
• Signal Fault - setting behavior of the receiver in case of signal loss
• hold - repeats the last valid deflection command before
signal loss
• out off – does not generate any signal for servo in case of
signal loss
• FailSafe – transition to preset deflection of individual outputs
17 EN

EN
• FS position – setup of the selected output deflection in case of
signal loss
• FS speed – setup for how quickly the output transitions to its
programmed deflection in case of signal loss
• ATV High Limit Yx – sets the upper travel (throw) limit of the
output
• ATV Low Limit Yx – sets the lower travel (throw) limit of the
output
• Output Trim – setting the neutral deflection of the receiver
output
• Output Group – setting the output to a selected group of output
pulses that will be generated from the receiver at the same time
4.5 Alarms
*CENTRAL BOX*: Alarms – pushing the D button (down arrow)
moves you to the menu for setting the alarms. If the alarm is set to
OFF, the alarm is deactivated.
• Capacity Alarm - level of the capacity taken from the battery at
which the alarm will sound
• Current Alarm - level of current drawn from the battery at which
the alarm will sound
• Voltage Alarm – if the battery voltage drops below this level, the
alarm will sound
• Short Circuit Alarm - Activating/deactivating the alarm for when
the outputs are overloaded
• Temperature Alarm – Activating/deactivating alarms for the
Central Box overheating
18 EN

EN
4.6 Service information
*CENTRAL BOX*: SERVICE – pushing the D button (down arrow)
moves you to the display of the firmware version and the menu for
restoring the default settings of the Central Box.
• PresetToSetup – pushing arrows R and L (right and left) together
leads to loading the default settings of the Central Box.
• CBOXxxx v. xx.xx ID xxxxx:xxxxx – designation of the product
with the firmware version and the serial number (ID)
19 EN

EN
5 Configuration via the DC/DS transmitter
The Central Box can be configured by a DC/DS transmitter via the
Device Explorer menu. It is necessary to follow these rules for
configuring the Central Box via transmitter:
- Receiver firmware version Duplex 3.12 and newer (with
setting Output mode->EX Bus)
- The receiver must be connected to the Central Box via EX bus
- Transmitter firmware version 2.02 and newer + the device
profile (CBOX100.bin or CBOX200.bin) recorded in the devices
directory on the SD card of the transmitter
When everything is properly connected and configured, the
CBOX100.bin or CBOX200.bin item appears in the Device Explorer
menu. Entering the item moves you to the configuration menu.
Fig. 14: Device Explorer
20 EN
This manual suits for next models
1
Table of contents
Other JETI model Remote Control manuals

JETI model
JETI model DUPLEX DC-24 User manual

JETI model
JETI model Duplex DC-16 II User manual

JETI model
JETI model Duplex DC/DS-16 II User manual

JETI model
JETI model Main Switch 200 ex User manual

JETI model
JETI model Duplex DS-16 User manual

JETI model
JETI model Duplex DS-12 User manual

JETI model
JETI model Duplex DC-16 User manual
Popular Remote Control manuals by other brands

TanGO
TanGO Generation TV Getting started guide

Hayward
Hayward AQL2-WB-RF-PS-4 Installation & operation manual

Marantz
Marantz RC2000MKII user guide

Ambient Technologies
Ambient Technologies RMSC Installation and operating instructions

Fujitsu
Fujitsu UTY-RVRU Operation manual

Marantz
Marantz RC2001 Service manual