Jeven SwingControl unit User manual

WWW.JEVEN.FI
SwingControl unit
Installation guide

Delivery 3
Dimensions and electrical
installation 4
Installation 5
Changing the rotation speed of
TurboSwing 6
Configuration guide 7-9
Automation 10
Table of Contents
WWW.JEVEN.COM
PAGE 2JEVEN Kitchen ventilation
Contact us: jeven@jeven.fi
010 231 2030
All rights reserved

DELIVERY
SwingControl Unit
Check the delivery receipt for the consignee’s name and address. Also inspect if the package is damaged.
When opening the package check the accuracy of the delivery. Any defiencies must be reported immediately to Jeven.
Please note!
Do not install the device in a position where it is exposed to water.
The ambient temperature must be below +30°C.
CONTENTS
SwingControl is delivered in a cardboard box
36x36x23 cm.
Cardboard box contains power cord, brackets and
SwingControl unit.
1. Power switch
2. Power line filter/ input power
(230 V,10A)
Cable length 2 meter
3,4. PIN-liitin, 4-pol
control current cable(0-10V)
5. Building automation socket
Rj 45 e.g. Modbus
6.
7. Led light off
-error
45
7
2
16
3
Led light on
-no error
SwingControl unit with two connected TurboSwings.
Power cord Brackets
SwingControl unit
PAGE 3
WWW.JEVEN.COM
JEVEN Kitchen ventilation
All rights reserved

PAGE 4JEVEN Kitchen ventilation
SwingControl Unit
DIMENSIONS
1
0
25
132
300
200
230
The box is made of polycarbonate
Standard EU 62208,GOST
Impact resistance IK 08
160
Brackets, can also be bent to
the side
ELECTRICAL INSTALLATION
Control current cable0-10V
The safety switch is mandatory and it must be
installed in a visible place and in the immediate vicinity
of the product. The control unit is connected as a
separate input.
The safety switch, socket/outlet box and the cables are
marked with a dashed line are not included in the
delivery.
Control power cables are connected to each TurboSwing
from which they are connected to SwingControl.
One SwingControl can serve max. 20 TurboSwings.
SwingControl unit is connected to the mains for continious
constant power.
SwingControl
unit
Turbo
Swing
Turbo
Swing
Modbus interface
Socket/ Safety switch
Outlet box
230 VAC
230 VAC 230 VAC 230 VAC
Socket
2m
2m
230 VAC
2m
WWW.JEVEN.COM
All rights reserved
Control current cable0-10V

INSTALLATION
SwingControl Unit
SwingControl can be mounted on a wall or pillar, either horizontally or vertically.
Cables that are on top of the hood, should be untied from cable ties and connected to SwingControl in appropriate
locations. Next, connect house automation interface and finally connect the power.
PAGE 5
JEVEN Kitchen ventilation
WWW.JEVEN.COM All rights reserved

SwingControl Unit
CHANGING THE ROTATION SPEED OF TURBOSWING
Open the control unit cover and change the position of the dip switches.
Rotation speed when switch is ”ON” position is 1100 rpm and 750 rpm
when switch is ”OFF”.
Speed is chosen separately for each TurboSwing unit.
The factory setting is the rotation speed according to plans.
PAGE 6JEVEN Kitchen ventilation
WWW.JEVEN.COM
All rights reserved

SwingControl Unit
CONNECTING TO SWINGCONTROL
SwingControl contains inbuilt tool for configuring device's LAN settings and Modbus TCP/IP port. Configuration tool
can be used via standard web browser, such as Internet Explorer, Firefox or Chrome. Configuration tool is accessible in
standard http port of SwingControl device. In order to open configuration tool configurators computer must be
configured to the same network as SwingControl. Computer must be connected to SwingControl via crossover
network cable or hub/router.
SwingControl default settings
Default factory settings for SwingControl network are:
IP:192.168.0.123
Gateway: 192.168.0.1
Netmask: 255.255.255.0
Network settings for Windows 7
Windows 7 local are settings must be set so, that it is possible to access SwingControlo configuration tool. To set up
network for this purpose, the following steps need to be taken:
1. Open ”Network and Sharing Center”
2. Choose ”Local area connection”, which will open a dialog named ”Local area connection status”
PAGE 7
JEVEN Kitchen ventilation
WWW.JEVEN.COM All rights reserved

SwingControl Unit
3. Choose ”Properties” 4. In ”Local area connection properties” choose
”Internet Protocol Version 4(TCP/IPv4)” from the list
and then choose ”Properties”.
5. Select ”Use the following IP address” and input IP
address, subnet mask and default gateway to match the
settings of SwingControl.
NOTE!
If you are connecting to SwingControl device that has
default factory settings, you can use the values shown
in screenshots. After saving the settings in your
computer, provided that network cabling is done
correctly, you should be able to open SwingControl
configuration panel by pointing you web browser to
address ”http://192.168.0.123”
PAGE 8JEVEN Kitchen ventilation
WWW.JEVEN.COM
All rights reserved

SwingControl Unit
CHANGING NETWORK SETTINGS AND MODBUS PORT
From SwingControl configuration tool it is possible to
change the device to either use DHCP addressing or static
IP address.
1. Point your web browser to SwingControl's current IP
address, by deafult: http://192.168.0.123
2. Using configuration tool requires you to input the
following user name and password: ”admin”, ”J3V3NSC”
3. Provided the user name and password are correct,
configuration panel should open in your browser.
4. You can choose either DHCP or static IP address. If you
choose static IP address, you must also provide valid IP
address, gateway and netmask that match your network.
5. In modbus settings it is possible to configure
SwingControl to use another port than the default 4433.
6. Finally changes are applied by selecting
”SAVE/REBOOT”. This saves your changes to
SwingControl persisten memory and causes a reboot to
the device. After reboot, new settings are applied.
PAGE 9
JEVEN Kitchen ventilation
WWW.JEVEN.COM All rights reserved

SwingControl Unit
PAGE 10 JEVEN Kitchen ventilation
AUTOMATION
Rekisteri Tietotyyppi Merkitys
1-24 bool
25-48 bool
0 - Not used
The SwingControl control units can be connected to the building automation system through the Modbus TCP/IP
interface (TCP/IP port 4433). The Modbus interface is available via the Ethernet interface. The SwingControl unit uses
the DHCP protocol for IP requests. If the connected Ethernet network does not allow automatic IP allocation,
SwingControl uses the following fixed settings:
IP: 192.168.0.123
Netmask: 255.255.255.0
SwingControl operates as a so-called Modbus slave device. The current status of each TurboSwing device connected to
a SwingControl unit, including any potential alarms, can be read via the Modbus interface. The registers used by the
Modbus interface are listed in the table below
Example of the use of Modbus registers:
TurboSwing is connected to interface 4.
Real-time device status information is found in the Modbus register number 4.
Possible alarm information is found in the register number 28.
Example reading modbus register with CAS:
Use ”Read holding registers” command.
WWW.JEVEN.COM
All rights reserved
Real-time connected TurboSwing on/off status information.
Status information is not filtered on the basis of the operating conditions.
Also other devices connected to the digital passive inputs of Swing Control
are visible in these registers. For the monitoring of the device alarms, it is
recommended to use separate alarm registers in the register range 25-48.
(See below)
If FALSE, the connected TurboSwing separating plate does not
rotate or rotates too slowly. The device is either off or not working properly.
The LED in the SwingControl device for the TurboSwing device is also off.
If TRUE, the connected TurboSwing is operating normally.
The LED of SwingControl unit is also on.
The Register number corresponds to the connected Turbo Swing device
order number.
The alarm information of the connected TurboSwing device.
Alarms are decided based on the operation parameters of the TurboSwing
equipment. Upon determining an alarm should be triggered, the
SwingControl control unit takes into account the so-called normal
operational conditions and seeks to minimize false alarms.
This register area is recommended to be primarily used in building
automation interfaces.
FALSE means that the TurboSwing device operates in a normal way.
TRUE means the SwingControl unit has identified the corresponding
TurboSwing device is not working properly.
The register number is calculated by adding 24 to the order number of the
connected TurboSwing device.
Table of contents
Popular Control Unit manuals by other brands

Tews Technologies
Tews Technologies TPMC917-10 user manual

Handson Technology
Handson Technology ESP8266 WiFi manual

Panasonic
Panasonic AJ-EC3P operating instructions

Texas Instruments
Texas Instruments TPS568236 user guide

EOS
EOS EmoStyle Di Installation and operation manual

Allmatic
Allmatic BIOS1 24V manual