Jinergy JNHM60 Series User manual

A_ V4200530
Crystalline silicon PV module
installation guide-HJT

1
1.Introduction
1.1 Purpose
This document provides detailed instructions and valuable safety information regarding the installation,
electrical connection and maintenance of JINERGY Double Glass Photovoltaic modules (JINNENG modules),
involved module model are JNHM60-XXX and JNHM72-XXX.
All instructions and mechanical and electrical requirements should be read and understood before attempting
installation.
The installer should conform to all safety precautions in this guide when installing the module. Keep this guide
in a safe place for further reference.
1.2 Limitation of Liability
Because the conditions and methods of installation, operation, use and maintenance of photovoltaic (PV)
products referring to the use of manual are beyond JINERGY control, JINERGY does not undertake any related
responsibility, and expressly disclaims liability for loss, damage, or expense increasing arising out of or in any way
connected with such installation, operation, use or maintenance. JINERGY reserves the right to change the manual
without prior notice.
1.3 Others
Modules rated for use in this application class may be used in systems operating at greater than 50V DC
or 240W, where general contact access is anticipated. Modules qualified for safety through IEC 61730-1 and
this part of IEC 61730 within this application class are considered to meet the requirements for safety class
II.
2.Safety
2.1 General Safety
2.1.1 Consult and follow local codes and other applicable laws concerning required permitting as well as installation
& inspection requirements, rules, and regulations.
2.1.2 PV modules should be installed and maintained by qualified personnel.
2.1.3 Use the same performance modules within a given series.
2.1.4 Follow all safety precautions of all components used in the system.

2
2.1.5 Do not shade portions of the PV module surface from the sun for a long period of time. The shaded cell may
become hot (hot spot phenomenon), which can result in solder joints peeling off.
2.1.6 Do not clean the glass surface with chemicals.
2.1.7 Do not drop the PV module or objects onto the PV module.
2.1.8 Do not concentrate sunlight on the modules or panels.
2.1.9 Do not attempt to disassemble the modules, and do not remove any attached components from the modules.
2.1.10 Do not scratch or hit at the back sheet, the glass and the terminal box. Do not pull the cables or touch them
with bare hands.
2.1.11 Keep the PV module packed in the carton until installation.
2.1.12 Do not use modules near equipment or in places where flammable gases may be generated.
2.1.13 Photovoltaic system must be closed before electrical maintenance. Improper maintenance may cause fatal
electric shock or burns.
2.2 Installation Safety
2.2.1 Use the special sucker when handling and installation modules, do not move modules with bare hand to prevent
slip.
2.2.2 Wear protective head gear, insulating gloves, safety shoes, and insulated tools when installing the modules.
2.2.3 Do not install the modules in rain, snow, or otherwise wet or windy conditions.
2.2.4 Completely cover the PV module surface with an opaque material during PV module installation and wiring to
prevent accidental charge buildup.
2.2.5 Plug in connectors tightly when working on wiring.
2.2.6 Due to the risk of electrical shock, do not perform any work if the terminals of PV module are wet.
2.2.7 Do not touch the terminal box and the end of output cables (connectors) with bare hands.
2.2.8 Do not unplug the connector under load.
2.2.9 Do not work alone.
2.2.10 Wear a safety belt if working far above the ground.
2.2.11 Do not wear metallic jewelry, which can cause electric shock, while installing or troubleshooting the PV
system.
2.2.12 Follow the safety regulations for any and all other system components, including wires, connectors, charging
regulators, batteries, inverters, etc.

3
2.2.13 Do not expose wires to direct sunlight. Use UV-resistant cabling.
2.2.14 Do not damage the surrounding PV modules or mounting structure when replacing a PV module.
2.2.15 Do not change any PV module components (diode, junction box, plug connectors, etc.).
2.2.16 Maximum reverse current is 20.25A for module with 6 inch cells. A subsidiary blocking diode or a fuse should
be installed when photovoltaic module was paralleled in series circuit.
2.2.17 The solar modules are recommended to be installed over a fireproof and insulating roof covering when
installed on a roof.
2.2.18 Module may not be contacted during working.
2.2.19 Maximum system voltage must not exceed 1500V DC .
2.2.20 It is recommended to use jinergy type PV-JN02,5.7~7.1 mm cable for connector which supplied by
module factory, these connectors are not recommended to replace the module connector
3. Mechanical Installation
3.1 Environmental conditions
JINNENG modules should be installed under the following conditions:
3.1.1 Ambient temperature :-40℃to +40℃
3.1.2Operating temperature : -40℃to +85℃
3.1.3Storage temperature:-20℃to +40℃
3.1.4Humidity :< 85% RH
3.1.5Mechanical load on panels (e.g., from wind or snow): Design value:front pressure is less than 3600 Pa /the
back pressure is less than 1600 Pa, safety factor is 1.5.
3.1.6Tilt Angle selection: The installation should be facing north in the southern hemisphere and facing south in the
northern hemisphere.
The load ability (including wind and snow load) of module depends on installation method of JINNENG
modules. Mechanical load should be calculated based on the system design by professional system installation
personnel.
3.2 Site selection
In most applications, JINNENG modules should be installed in the location of maximum sunlight absorption
annual.

4
3.2.1 Modules should not be shaded at any time of the day by objects, such as buildings, trees, chimneys,
etc.
3.2.2 Do not install in corrosive environment, such as the beach or the landfill area where easily eroded
by floods.
3.2.3 Do not install modules in a location where they may be immersed in water or continually exposed
to water from a sprinkler or fountain, etc.
3.2.4 Photovoltaic modules should be installed away from fire or flammable objects.
3.2.5 To maintain the modules’ Class C fire rating, the fire class of the roof and building materials should
be higher than Class C. The fire rating of this module is valid only when mounted in the manner specified in
the mechanical mounting instructions.
3.2.6 Raise the distance when installation requirement is greater than or equal to 0.3 m. Appropriate
installation angle of modules refers to the following Table 1.
Local latitude
Installation angle
0°~15°
15°
15°~25°
latitude
25°~30°
latitude+5°
30°~35°
latitude+10°
35°~40°
latitude+15°
>40°
latitude+20°
Table 1
3.3 Mounting Methods
Please completelyread this chapter content, be familiar with all process and then start the installation. In addition,
prepare for all the scene before starting the installation.
Modules must be laid across the supporting bars(The supporting bars width should be 40~80mm), Clamps
installed symmetrically as follows (Fig. a).

5
Fig. a 6-clamp installation
Each clamp comes with an M8 bolt, a spring washer, a flat washer and an M8 nut. Use six clamps on each
module, three clamps should be attached on each long side of the module. To fasten the module:
1. Mounting middle clamps and edge clamps, Fig. b and Fig. c for your reference. Complete set of fasteners are
M8 bolts. The choice of hex bolt and cuboid nut depend on the structure and size of the beam. If you choose C beam
or C type steel, using matched bolts and nuts.
Fig. b Middle clamp Fig. c Edge clamp
2. Insert the cuboid nut into rail and thread bolt through spring washer, flat washerand clamp in turn. Finally screw
hex bolt and cuboid nut, do not need to tighten, avoid falling, as shown in figure (d) and (e).

6
Fig. d Fig. e
3. Insert modules into clamps and tighten the M8 screws, which have a torque of 15-18 N*m as show in Fig .f.
Fig. f
4. As shown in the above installation method, slide bolts through groove on the supporting bars next to the
locations where the clamps are to be fastened. Clamp position is very important, the module must be clamped only
on the long edge, Fig. a "D" dimension the centerline of clamps to module edge. Number of clamps, clamps positions
match relevant mechanical load, please refer to Table 2 and tab 3.
photovoltaic module type
JNHM72(2.0+2.0Glass Pane)
JNHM72(2.5+2.5Glass Pane)
Fastening method
6-clamp
installation
4-clamp
installation
6-clamp
installation
4-clamp
installation
Mounting position D/mm
300±75
————
300±75
————
The first cycle (Pa)
+3600/-1600
————
+3600/-1600
————
The second cycle (Pa)
+3600/-1600
————
+3600/-1600
————
The third cycle(Pa)
+3600/-1600
————
+3600/-1600
————
(Note: 1) safety factor 1.5; 2) Clamp length d=250mm)
Table 2 JNHM72 Mechanical load test
photovoltaic module type
JNHM60(2.0+2.0Glass Pane)
JNHM60(2.5+2.5Glass Pane)
Fastening method
6-clamp
4-clamp
6-clamp
4-clamp

7
installation
installation
installation
installation
Mounting position D/mm
225±25
————
225±25
————
The first cycle (Pa)
+3600/-1600
————
+3600/-1600
————
The second cycle (Pa)
+3600/-1600
————
+3600/-1600
————
The third cycle(Pa)
+3600/-1600
————
+3600/-1600
————
(Note: 1) safety factor 1.5; 2) Clamp length d=250mm)
Table 3 JNHM60 Mechanical load test
5. Compatibility of Clamp and double glass modules : fig .h
shows the critical dimensions of clamp that could satisfy the
requirement of JINNENG modules (unit of drawing is mm).
Fig. h clamp installation section
4.Electrical Installation
We require that all wiring and electrical connections comply with the appropriate National Electrical Code.
4.1 The electrical characteristics are within ±10 percent of the indicated values of ISC, VOC, and Pmax under
standard test conditions (irradiance of 1000W/m2, AM 1.5 spectrum, and a cell temperature of 25°C (77°F)).
4.2 The maximum system voltage is 1500 V。
4.3 The number of PV modules in a series circuit should match with inverter’s technology parameters of voltage.
The series voltage of modules that connected together in a series circuit should not higher than the permitted
maximum system voltage under the worst local temperature conditions.
4.4 Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current
and/or voltage than reported at standard test conditions. The requirements of the National Electrical Code (NEC) in
Middle clamp is made up of the bottom and
the top half two parts. The material are
aluminum alloy 6063 with lengths of 250
mm. Connect two parts with M8 bolts.
Clamp has four rubber strips of 2-3 mm
thickness (Suggest to use EPDM rubber)

8
Article 690 shall be followed to address these increased outputs. In installations not under the requirements of the
NEC, the values of ISC and VOC marked on this module should be multiplied by a factor of 1.25 when determining
component voltage ratings, conductor capacities, over current device ratings, and size of controls connected to the
PV output.
4.5 Each module (or series-connected string of modules) shall be provided with the maximum series overcurrent
protective device, specified as 15A for the 6 inch cell module series.
4.6 Use a special solar cable and plugs for installing the PV system and make sure that all connections are safe and
tight. The cable cross section size should be 4mm2(12AWG) and able to withstand the maximum possible system
open-circuit voltage.
4.7 Bypass diodes are included in module junction boxes to avoid decreased module performance in the event of
shade or shelter.
4.8 Please check the relevant product datasheet for the specific diodes of J-box.
5.Maintenance and Disposal
5.1 Regularly carry out a visual inspection for dirt, dust, bird dropping, leaves, and other detritus covering the
modules.
5.2 If there is a build-up of dirt or dust on the module surface, wash the module with clean water and a gentle
implement (a sponge). Never use chemicals on the surface of the module.
5.3 If snow is present, a soft-bristled brush with soft bristles may be used to clean the surface of the modules.
5.4 Don't use cold water to clean modules in higher temperature to prevent thermal shock damage on modules.
5.5 At least once a year, it is recommended to check the torque of terminal bolts and the general condition of
wiring. Also, check that mounting hardware is properly torqued.
5.6 Regular electrical and mechanical inspection by a licensed professional will keep the system safe and operating
at maximum efficiency.
Note:All the above are sketch map
This manual suits for next models
1
Table of contents
Other Jinergy Solar Panel manuals
Popular Solar Panel manuals by other brands

evergreensolar
evergreensolar ES-A Series Safety, installation, and operation manual

Jinko Solar
Jinko Solar JKM PP-60 Series manual

GOAL ZERO
GOAL ZERO Ranger 300 user manual

Sun Power
Sun Power Equinox SPR-X21-335-BLK-C-AC Safety and installation instructions

Sanyo
Sanyo HIP-190BE3 installation manual

Aleo
Aleo ELEGANTE installation manual

Conergy
Conergy EcoPro P Series installation manual

Sanyo
Sanyo HIT-N220E01 General installation manual

Sunman
Sunman eArc SMF290M-6X10DW installation manual

Panasonic
Panasonic VBHNxxxSJ25 series installation manual

GH Solar
GH Solar GH175M125 Safety and installation manual

TTI
TTI FLAT JACK installation manual