4
ZZ829/3
5
ZZ829/3
8.4 THREE WAYVALVE or MOTOR REMOVAL:
8.4.1 Ensure that the electrical supply is switched off and isolated.
8.4.2 Close the isolating valves and drain down the unit, taking care to prevent water from dripping onto the electrical
panel or fan on UPFLOW models.
8.4.3 Disconnect the unit pipework from the left hand (lower) connection the heat exchanger, and the FLOW connection
beneath the three way valve.
8.4.4 Slacken the connection at the left hand end of the three way valve to permit the pipework to swing away from the
heat exchanger. Disassemble the three way valve from the pipework.
8.4.5 To gain access to the motor, loosen the screw at the right hand side of the valve actuator and lift the cover.
8.4.6 To replace the motor, follow the manufacturer’s instructions included with the motor kit.
8.4.7 Reassembly is in reverse order. Ensure that all air locks are expelled, and check for water soundness.
8.5 FAN CONTROL REMOVAL:
8.5.1 Ensure that the electrical supply is switched off and isolated.
8.5.2 Release the single screw and remove the fan control cover.
8.5.3 Disconnect the 2 leads from the fan control, leaving the earth connected.
8.5.4 Release the 2 screws securing the fan control and remove the control.
8.5.5 Refitment or replacement is in reverse order.
8.6 HEAT EXCHANGER REMOVAL:
8.6.1 Ensure that the electrical supply is switched off and isolated.
8.6.2 Close the isolating valves and drain down the unit, taking care to prevent water from dripping onto the electrical
panel or fan on UPFLOW models.
8.6.3 Release the 2 x retaining screws and withdraw the panel containing the ‘SUMMER AIR CIRCULATION’switch,
disconnect the flying terminal strip and remove the panel from the unit.
8.6.4 Disconnect the wiring to the water valve and time control (if fitted) at the electrical panel terminal block and earth
post, noting their positions for subsequent reconnection.
8.6.5 Release the 4 hexagonal headed screws and remove the heat exchanger and its associated pipework from the unit.
8.6.6 Refitment or replacement is in reverse order. Ensure that all air locks are expelled, and check for water soundness.
8.7 FAN ASSEMBLY REMOVAL:
8.7.1 Remove the electrical panel as detailed in para. 8.3.
8.7.2 Release the 2 screws at either end of the fan tray, and withdraw the fan assembly.
8.7.3 Refitment is in reverse order.
8.8 FAN CAPACITOR REPLACEMENT:
8.8.1 Remove the fan assembly as detailed in para 8.7.
8.8.2 Disconnect the capacitor leads at the capacitor.
8.8.3 Remove the capacitor from its securing clip.
8.8.4 Refitment or replacement.
8.9 FAN REPLACEMENT:
8.9.1 Remove the fan assembly as detailed in para 8.7.
8.9.2 Disconnect the 4 x fan wires from the terminal block and withdraw the leads from the grommet and ‘P’ clip.
8.9.3 Release the 4 x round headed screws and lock washes and remove the fan from the fan assembly.
8.9.4 Refitment or replacement is in reverse order. Do not omit the lock washers from beneath the 4 x screws, and
ensure that the capacitor is connected correctly.
8.10 AIR FILTER REMOVAL:
8.10.1 The air filter is removed by sliding it out from the front of the unit.
9. DEFECT DIAGNOSIS
IMPORTANT: If an electrical defect occurs after installation of the appliance, preliminary earth continuity,
polarity and resistance to earth checks should be carried out using a multimeter. Upon completion of any
service or fault finding task that has required the breaking and remaking of electrical connections, then
checks of continuity, polarity and resistance to earth must be repeated.
WARNING: When carrying out electrical testing, a test meter MUST be used. Low resistance test devices can cause damage to
the electronics module.
Prior to commencement of fault finding, set the Thermista-stat to maximum, turn the mains electrical supply ON and check that
the time control (if fitted) is set to an on position.
Care must be taken during the replacement and handling of electronic assemblies (i.e. electrical assembly and Thermista-stat). It
is not practical to rectify any defects in these assemblies except in the factory, and any attempt to do so may render any
guarantee or factory replacement agreement void.
9.1 OPERATIONAL CHECKS:
HEATER NOTOPERATING
Check for fan voltage at terminal 12.
NOVOLTAGE VOLTAGE PRESENT
Set ‘SUMMER AIR’ switch to ‘I’. Check for fan voltage at terminal 11.
FANSTARTS FAN FAILSTO START NOVOLTAGE VOLTAGE PRESENT
Replace electrical Replace fan. Check water Check for fan voltage
panel. temperature. at terminal 24.
Water Temp. Water Temp.
below 70OC above 70OC
Check water supply. Replace Fan
Adjust lockshield control.
to restrict flow.
NOVOLTAGE VOLTAGE PRESENT
Check wiring Check socket connection
between terminals in fan compartment.
11 and 24, and
rectify defect. Socket connection OK
Replace fan.
WATERVALVE NOTOPERATING
Check that Thermista-stat is calling for heat.
Check Mains electrical supply.
Check supply to electrical panel at supply terminals.
Check 500mA fuse.
Check time control (if fitted) is at an ON setting.
Check for 230V at terminal 17.
NOVOLTAGE VOLTAGE PRESENT
Replace electrical panel Check for 230V at terminal 19
NOVOLTAGE VOLTAGE PRESENT
Replace time control (if fitted) Replace valve actuator
or check shorting link between motor
terminals 17 and 18
FAN RUNNINGWHEN NO HEAT REQUIRED
Check ‘SUMMER AIR’ switch is set to ‘O’, and check water temperature.
If water temperature is below 60OC, replace fan control.