Safety information
The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions. The
equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall
before operation. Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
WARNING: Never install this equipment during a lightning storm!
Instruct the end-user to:
lNot attempt to service this product. Opening or removing covers may expose the user to dangerous voltages or other risks.
Any servicing shall be referred to trained service persons only.
lUse authorized accessories only with this equipment.
lDo not dispose of the battery in fire or water. Disposing of the battery in a fire will cause rupture and explosion.
lDo not dispose of the waste battery as unsorted municipal waste. Consult your local regulations and /or laws regarding recyc-
ling with regard to this lead-acid battery. Doing so will help protect the environment. Some of the materials that are found
within the battery could become toxic if not disposed of properly and may affect the environment.
This equipment, LE4000/LE4000E, is fixed and shall be installed by skilled person only; skilled persons are per-
sons who have training or experience in the equipment technology, particularly the various energies and energy
magnitudes used in the equipment. Skilled persons are expected to use their training and experience to recognize
energy sources capable of causing pain or injury and to take action for protection from injury. Skilled persons are
persons who have training or experience in the equipment technology, particularly the various energies and
energy magnitudes used in the equipment. Skilled persons are expected to use their training and experience to
recognize energy sources capable of causing pain or injury and to take action for protection from injuries.
It shall be installed and used within an environment that provides the pollution degree max 2, over voltages cat-
egory II, in non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of the
relevant alarm control panel. All instructions specified within that manual must be observed.
Approvals
For UL Residential Fire and Burglary installations, the LE4000/LE4000E is listed as a sole means of com-
munication or as a back up when used in conjunction with a POTS line (dialer). For UL Residential Fire install-
ations, the LE4000/LE4000E must be connected to a UL-listed power supply with a minimum of 24 hours
standby power or powered using the ADP 1310(W)-NAU and a 2200mAh battery.
For UL Commercial Burglary installations, the LE4000/LE4000E is listed as a sole means of communication
(supervision window of 200s required at monitoring station) or as a back-up when used in conjunction with a
POTS line (dialer).
The LE4000/LE4000E shall be powered from any compatible listed control unit or compatible listed power sup-
ply that complies with the ratings specified. The power supply shall be listed for burglary applications and
provide a minimum of 4 hours standby power capabilities. An example of a suitable listed compatible control
unit is the DSC Model PC1864 with an AUX output rated 11.1 - 12.6Vdc. An example of a suitable Listed
power supply is DSC Model PC5204 with an AUX output rated 11.6 - 12.6Vdc.
For ULC Commercial Burglary installations the LE4000/LE4000E is listed as a passive communication system
with communication line security level P1 when used as single communication path or P2 when used as a back
up in conjunction with a POTS line (dialer). The LE4000/LE4000E is also listed for Active line security levels
A1-A4 (90 seconds heartbeat enabled and supervision window of 180s required at monitoring station receiver
and encryption must be enabled). For ULC Commercial Burg installations, the LE4000/LE4000E must be con-
nected to a ULC-listed power supply with a minimum of 24 hours standby power or powered using the ADP
1310(W)-NAU and a 2200mAh battery. The LE4000/LE4000E can be used in commercial burglary applications
up to Security Level IV.
For ULC Residential Fire and Burglary installations the LE4000/LE4000E is listed as a sole means of com-
munication or as a back up when used in conjunction with a POTS line (dialer). For ULC Residential Fire