JUMO iTRON B 70.2040 User manual

JUMO iTRON
Compact
microprocessor
controllers
B 70.2040
Operating Instructions
2008-11-11/00357918
Type 702042 Type 702044 Type 702041
Type 702043
Type 702040
b70.2040en.bk Seite 1 Mittwoch, 19. November 2008 10:15 10

)Please read these Operating Instructions carefully before starting up the instrument. Keep
these operating instructions in a place which is at all times accessible to all users. Please
assist us to improve these operating instructions where necessary. Your suggestions will be
most welcome.
Phone in Germany (0661) 6003-727
from abroad (+49) 661 6003-0
Fax in Germany (0661) 6003-508
abroad (+49) 661 6003-607
)All necessary settings are described in these operating instructions. However, if any difficul-
ties should still arise during start-up, you are asked not to carry out any unauthorized ma-
nipulations on the unit. You could endanger you rights under the instrument warranty!
Please contact the nearest subsidiary or the main factory in such a case.
EWhen returning chassis, assemblies or components, the regulations of EN 100 015 “Protec-
tion of electrostatically sensitive components” must be observed. Use only the appropriate
ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD (electrostatic dis-
charge).
b70.2040en.bk Seite 2 Mittwoch, 19. November 2008 10:15 10

Contents
Contents
1 Identifying the instrument version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Displays and keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Operation of the timer function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5.1 Process value input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Logic input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.4 Limit comparator (alarm contact) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
5.5 Ramp function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.6 Self-optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
5.7 Level inhibit via code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.8 Timer function (extra code) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6 Configuration and parameter tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7 Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
b70.2040en.bk Seite 3 Mittwoch, 19. November 2008 10:15 10

1 Identifying the instrument version
4
1 Identifying the instrument version
1. single-setpoint controller with limit comparator, see factory settings under configuration and parameter level
2. see customer’s ordering text or settings under configuration and parameter level
(1) (2) (3) (4) (5) (6)
7020 .. / .. – ... – ... – .. / ... ,...
(1) Basic type
(bezel in mm) 40 =48x24, 41 = 48 x 48, 42 = 48 x 96 (portrait), 43 = 96 x 48 (landscape), 44 = 96 x 96
(2) Basic type
extension 88 =
99 = controller type configurable1
controller type configured to customer specification2
(3) Inputs 888 =
999 = inputs configurable1
inputs configured to customer specification2
(4) Outputs 000 = Standard Type 702040/41 Type 702042/43/44
Output 1 relay (n.o. make) relay (n.o. make)
Output 2 logic 0/5V, optionally
configurable als logic input logic 0/5V
Output 3 (not available) relay (n.o. make)
Options Type 702040/41 Type 702042/43/44
113 =Output2
(outputs 1+3 as for
Standard)
logic 0/12V, optionally
configurable als logic input logic 0/12V
101 =Output2
(output 1 as for Standard) relay (n.o. make)
(logic input is always available) not possible
b70.2040en.bk Seite 4 Mittwoch, 19. November 2008 10:15 10

1 Identifying the instrument version
5
1. The linearizations for KTY11-6 and thermocouple B have been deleted.
(5) Supply 16 =
22 =
23 =
10—18V DC
20—53V AC/DC, 48—63Hz
110—240V -15/+10% AC 48— 63Hz
(6) Extra code 210 =
220 = Timer function
Timer function + limit switch1
Delivery package Type 702040/41 Type 702042/43/44
1 mounting frame 2 mounting brackets
1 seal, 1 Operating instructions 70.2040
b70.2040en.bk Seite 5 Mittwoch, 19. November 2008 10:15 10

2 Installation
6
2 Installation
Type (bezel) Panel cut-out (WxH)
in mm
Edge-to-edge-mounting
(minimum spacings of panel cut-outs)
horizontal vertical
702040 (48mm x 24mm) 45+0.6 x 22.2+0.3 > 8mm > 8mm
702041 (48mm x 48mm) 45+0.6 x 45+0.6 > 8mm > 8mm
702042 (48mm x 96mm) 45+0.6 x 92+0.8 > 10mm > 10mm
702043 (96mm x 48mm) 92+0.8 x 45+0.6 > 10mm > 10mm
702044 (96mm x 96mm) 92+0.8 x 92+0.8 > 10mm > 10mm
1. Push on seal
2. Insert instrument
3. Push on mounting brackets
4. Tighten screws
Installation 702042
as 702044.
b70.2040en.bk Seite 6 Mittwoch, 19. November 2008 10:15 10

3 Electrical connection
7
3 Electrical connection
Installation notes
- The choice of cable, the installation, the fusing and the electrical connection must conform to
the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with nominal
voltages below 1000V”, or the appropriate local regulations.
- The electrical connection must only be carried out by qualified personnel.
- If contact with live parts is possible when working on the instrument, it must be isolated on
both poles from the supply.
- A current limiting resistor interrupts the supply circuit in the event of a short-circuit. The load
circuit must be fused for the maximum relay current in order to prevent welding of the output
relay contacts in the event of an external short-circuit.
- Electromagnetic compatibility conforms to the standards and regulations listed under
Technical Data.
- Run input, output and supply lines separately and not parallel to each other.
- Do not connect any additional loads to the supply terminals of the instrument.
- The instrument is not suitable for installation in hazardous areas.
- Apart from faulty installation, there is a possibility of interference or damage to controlled
processes due to incorrect settings on the controller (setpoint, data of parameter and
b70.2040en.bk Seite 7 Mittwoch, 19. November 2008 10:15 10

3 Electrical connection
8
configuration levels, internal adjustments).
Safety devices independent of the controller, such as overpressure valves or temperature
limiters/monitors, should always be provided and should be capable of adjustment only by
specialist personnel.
Please refer to the appropriate safety regulations in this connection. Since auto-tuning (self-
optimization) cannot be expected to handle all possible control loops, there is a theoretical
possibility of unstable parameter settings. The resulting process value should therefore be
monitored for its stability.
- All input and output lines that are not connected to the supply network must be laid out as
shielded and twisted cables (do not run them in the vicinity of power cables or components).
The shielding must be grounded to the earth potential on the instrument side.
b70.2040en.bk Seite 8 Mittwoch, 19. November 2008 10:15 10

3 Electrical connection
9
20—53V
10—18V
AC/DC
ⵒ
ⵒ
DC
AC
110—240V
5V(12V)/20mA
1. Output or logic input (configurable)
2. resistive load
Output 1
250V/3A
Logic input
Process value input
+
+
+
–
–
+–
+–
–
NL198654321
Current
0/4—20mA
Pt100/1000
KTY11-6
(2-wire)
Pt100/1000
(3-wire)
Thermocouple
Voltage
0/2—10V
Output 21
2
J
J
Logic output Relay
+–
=
floating contact
Supply
see label
1
VThe electrical con-
nection must only
be carried out by
qualified personnel.
Type 702040/41
b70.2040en.bk Seite 9 Mittwoch, 19. November 2008 10:15 10

3 Electrical connection
10
20—53V
AC/DC
ⵒ
ⵒ
AC
110—240V
12
Logic input
Process value input
+–
-+
+–
NL19854321
Current
0/4—20 mA
Pt100/1000
KTY11-6
(2-wire)
Pt100/1000
(3-wire)
Thermocouple
Voltage
0/0.2—1 V
Outputs
J
J
Relay 250 V/3 A
+–
7
Supply
see label
10—18V
DC
+–
=
VThe electrical connection
must only be carried out
by qualified personnel.
Type 702040/41 with
2 relay outputs (option)
b70.2040en.bk Seite 10 Mittwoch, 19. November 2008 10:15 10

3 Electrical connection
11
20—53V
ⵒ
ⵒ
AC
110—240V
Output 2
5V(12V)/20mA
Current
0/4—20mA
Pt100/1000
KTY11-6
(2-wire)
Pt100/1000
(3-wire)
Thermocouple
Voltage
0/2—10V
Output 3Output 1
250V/3A 250V/3A
Logic input
Process value input
+
+–
+–
+–
–
13 N L1121097654321
floating contact
22
Logic output Relay Relay
2. resistive load
+–
J
AC/DC
10—18V
DC
+–
=
J
Supply
see label
Type 702042/43/44
VThe electrical connection must
only be carried out by qualified
personnel.
b70.2040en.bk Seite 11 Mittwoch, 19. November 2008 10:15 10

4 Operation
12
4 Operation
4.1 Displays and keys
(1) Display
7-segment display 4 places, green
Display alternates when
setpoints, parameters and
codes are entered and
indicated.
Character height Type 702040/41/42: 10mm
Type 702043/44: 20mm
Display range -1999 to +9999 digit
Decimal places none, one, two
Unit °C/ °F (process value display)
(2) Status indicators
LED two LEDs for the outputs 1 and 2, yellow
(3) Keys
q, i, dfor operating and programming the instrument.
Dynamic modification of settings and parameters.
hIncrease value with i
hDecrease value with d
Automatic value acceptance after 2 seconds.
Example: Type 702041
b70.2040en.bk Seite 12 Mittwoch, 19. November 2008 10:15 10

4 Operation
13
4.2 Principle of operation
Normal display
The display shows the process value.
Operating level
The setpoint SP is input here. On active setpoint switching via the logic input, SP 1 or SP 2 ap-
pears in the display. When the ramp function is active, the ramp setpoint SPr is displayed. With
activated timer function, the timer value tior the timer start value ti0 is shown.
The setpoint is altered dynamically using the iand dkeys. The setting will be accepted auto-
matically after approx. 2 sec.
Parameter level
The setpoints, the limit value of the limit comparator, the controller parameters and the ramp slo-
pe are programmed here.
Configuration level
The basic functions of the controller are set here.
In order to make the settings, it is necessary to change to the configuration level
Avia the parameter y:0 (parameter level).
Timer level
The current timer value (only when the timer has been started) and the timer start value are al-
tered here. The parameters at this level are marked with an underscore in the display.
Time-out
If no operation occurs, the controller returns automatically to normal display after approx. 30 sec
(exception: with timer functions starting via power ON, the timer value is displayed). If the timer
value is displayed at the operating level, time-out is not active.
b70.2040en.bk Seite 13 Mittwoch, 19. November 2008 10:15 10

4 Operation
14
Process value
Parameter level
Configuration level
Timer level (timer stopped!)
C111
Pb:1
259
- setpoint 1+2
- limit value for
limit comparator
- controller parameters
- ramp slope
Setpoint
(with setpoint
switching
or )SP 1 SP 2
alter current
timer value
(only when timer has
been started)
set/alter
timer start value
* only displayed if function is configured
Ramp setpoint*
(display only)
Timer value*
(operating only;
different display
depending on
timer condition (see table))
SP
SPr
ti
ti
ti0
- configuration codes
- standard signal scaling
- process value correction
- switching differential
of limit comparator
> 2s
qd+
Normal display Operating level > 2s
> 2s
after last
parameter via y.0 !
Time-out
(30s)
Time-out
or
after last
parameter
ii d/+
Y.0
A
Underscore to differentiate operating
and timer level
b70.2040en.bk Seite 14 Mittwoch, 19. November 2008 10:15 10

4 Operation
15
4.3 Operation of the timer function
The timer can be operated with the keys (start, stop, cancel, acknowledge) if the timer at opera-
ting level is indicated. Time-out is not active here. If the logic input is configured accordingly,
then a key, such as the ikey, can be used. In this case, the timer can also be operated even if
the timer value does not appear in the display.
Possible displayed parameters for timer function at operating level
Display State/Action Display State/Action
Timer not running
hStart with i
Timer has stopped
hContinue with i
hCancel with i+ d
Timer has been started but
the tolerance limit has not
yet been reached
hCancel with i+ d
Timer has run down
hAcknowledge with any key
(timer start value ti0 is
indicated)
With time-delayed control
(C120=3), acknowledge
with i+ d
Timer running;
tiis displayed
hStop with i
hCancel with i+ d
When the timer has been started, the decimal point in the display for the timer value will blink!
b70.2040en.bk Seite 15 Mittwoch, 19. November 2008 10:15 10

5 Functions
16
5 Functions
We recommend the following procedure:
1. not for Type 702040/41 with 2 relay outputs (option)
hFamiliarize yourself with the controller functions
hEnter the configuration codes and the parameter values in the tables provided for this pur-
pose in Chapter 6. Write down the appropriate values ( ), or mark selection with a cross
( ). The parameters and the configuration codes are listed in the order of their
appearance. Parameters which are not relevant are masked out (see table below).
hEnter the configuration code and parameters on the instrument
Configuration Masking out the parameters for Parameter
Single-setpoint controller Double-setpoint controller Pb:2, Cy 2, db, HyS.2
Double-setpoint controller Limit comp. for Type 702040/41
Logic input for Type 702040/411C114, HySt, AL
C117
Limit comparator no function Limit comparator HySt, AL
Limit comparator activated Logic input for Type 702040/411C117
Resistance thermometer, thermocouple Standard signal scaling SCL, SCH
Ramp function off Ramp function rASd, SPr
Setpoint switching not activated Setpoints at the parameter level SP 1, SP 2
Timer function: no function Timer function ti, C121, C122, C123
Type 702040/41 Output 3 C118
X
b70.2040en.bk Seite 16 Mittwoch, 19. November 2008 10:15 10

5 Functions
17
5.1 Process value input
Symbol Notes
C111 Transducer/probe (process value input) vpage 31
C112 Unit of process value (°C/°F)/decimal places of display vpage 31
SCL Start/end value of value range for standard signals vpage 35
Example: 0—20 mA→20—200°C: SCL = 20 / SCH = 200
SCH
OFFS Process value correction vpage 35
Using the process value correction, a measured value can be corrected by a programmable
amount upwards or downwards (offset).
Lead compensation can be implemented in software for 2-wire circuit through process value
correction.
Examples:
Measured value Offset Displayed value
294.7 + 0.3 295.0
295.3 - 0.3 295.0
dF Filter time constant (damping) to adapt the digital input filter (0sec = filter off) vpage 36
if dF high: - high damping of interference signals
- slow reaction of the process value display to changes in the process value
- low cut-off frequency (2nd order low-pass filter)
b70.2040en.bk Seite 17 Mittwoch, 19. November 2008 10:15 10

5 Functions
18
5.2 Logic input
Key inhibit Operation is possible from keys. No operation from keys.
Level inhibit Access to the parameter and
configuration levels is possible.
Starting self-optimization is possible.
No access to the parameter and
configuration levels.
Starting self-optimization is not possible.
Ramp stop Ramp running Ramp stopped
Setpoint switching Setpoint SP 1 is active Setpoint SP 2 is active
The appropriate symbols SP 1 and SP 2 are displayed at the operating
level.
Timer control Acknowledge start/stop/continue/timer run-down (edge-triggered)
Symbol Notes
C117 Function of the logic input vpage 33
On Type 702040/41, the parameter C117 is masked out if output 2 has been programmed as
controller output (C113) or the limit comparator has been configured (C114) (double assign-
ment; not on Type 702040/41 with 2 relay outputs (option)).
b70.2040en.bk Seite 18 Mittwoch, 19. November 2008 10:15 10

5 Functions
19
5.3 Controller
Controller structure
The controller structure is defined via the parameters Pb, dt and rt.
Example: Setting for PI controller →Pb .1=120, dt=0sec, rt=350sec
Symbol Notes
C113 Controller type and assignment of the controller outputs to the physical
outputs 1+2 vpage 32
C116 Outputs in fault condition vpage 33
The switching states of the outputs are defined here in the event of over/underrange, probe
break/short circuit or display overflow.
vChapter 7
C118 Assignment of the outputs vpage 33
Only for Type 702042/43/44; overwrites the assignment of C113 (controller type as C113)
Pb:1 Proportional band 1 (controller output 1) vpage 36
Proportional band 2 (controller output 2)
Influences the P action of the controller. If Pb=0, the controller structure is not effective.
Pb:2
dt Derivative time vpage 36
Influences the D action of the controller. If dt=0, the controller has no D action.
rt Reset time vpage 36
Influences the I action of the controller. If rt=0, the controller has no I action.
Cy 1 Cycle time 1 (controller output 1) vpage 36
Cycle time 2 (controller output 2)
The cycle time has to be selected so that the energy supply to the process is virtually
continuous, while not subjecting the switching elements to excessive wear.
Cy 2
b70.2040en.bk Seite 19 Mittwoch, 19. November 2008 10:15 10

5 Functions
20
db Contact spacing vpage 36
for double-setpoint controller
HYS.1 Differential 1 (controller output 1) vpage 36
Differential 2 (controller output 2)
for controllers with Pb.1=0 or Pb.2=0
HYS.2
Y:0 Working point (basic load) vpage 36
Output if process value=setpoint
Y:1 Output limiting vpage 36
y:1 - maximum output
y:2 - minimum output
Y:2
Symbol Notes
HFor controllers without controller structure (Pb.1=0 or Pb.2=0), it is necessary
that y:1=100% and y:2=-100%.
b70.2040en.bk Seite 20 Mittwoch, 19. November 2008 10:15 10
Table of contents
Other JUMO Computer Hardware manuals