Mounng the QFX5200-48Y
The QFX5200-48Y is available in AC and DC power models. Only mount QFX5200-48Y models in a
four-post rack. This procedure describes the installaon into a four-post rack and connecng AC power.
For DC connecon procedures, see the complete QFX5200-48Y hardware documentaon at hps://
www.juniper.net/documentaon/.
To install a Juniper Networks QFX5200-48Y, you need:
•Electrostac discharge (ESD) grounding strap (not provided)
• One pair of front mounng brackets (provided)
• One pair of adjustable rear mounng blades (provided)
• One pair of rear mounng brackets to aach the mounng blades to the chassis (provided)
• Twenty black at head screws to secure the mounng rails and mounng blades to the chassis
(provided)
• Eight screws and cage nuts to secure the chassis and rack-mount kit to the rack (not provided)
• Two washer head Phillips screws to lock the mounng blades to the rear brackets (provided)
• Screwdriver appropriate for your rack-mounng screws (not provided)
• Two power cords with plugs appropriate for your geographical locaon (provided)
• RJ-45 cable and RJ-45 to DB-9 serial port adapter (not provided)
NOTE: We no longer include a DB-9 to RJ-45 cable or a DB-9 to RJ-45 adapter with a CAT5E
copper cable as part of the device package. If you require a console cable, you can order it
separately with the part number JNP-CBL-RJ45-DB9 (DB-9 to RJ-45 adapter with a CAT5E
copper cable).
• Management host, such as a PC laptop, with a serial port (not provided)
• Grounding cable and lug (not provided)
• Two Phillips screws with star washers to ground the chassis (provided) (For instrucons to aach the
grounding cable and lug to earth ground, see the
QFX5200 Hardware Guide
.)
To mount the switch in a four-post 19-in. rack:
1. Aach the ESD grounding strap to your bare wrist and to a site ESD point.
1