Kanmor tekmarNet 4 User manual

tekmarNet® 4 Thermostat 538e
Installation & Operation Manual
D538e
02/11
Replaces: 02/08
1 of 24 © 2011 D538e - 02/11
The tekmarNet® 4 Thermostat 538e
provides operation for:
One Stage Heat•
Introduction Features
Requires 4 wires (tN4, N, L, )
Auxiliary sensor to measure floor,
outdoor or indoor temperature
Outdoor temperature display
Bright backlight
2 button temperature adjustment
Communication with other
tekmarNet®devices improves
system efficiency and comfort
Schedule member status enables
setback operation
Optimum start
Responds to tekmarNet®Scenes
Cooling Group Member
Freeze protection
Exercising
Zone synchronization
•
•
•
•
•
•
•
•
•
•
•
•
•
Benefits
Energy savings
Reduced temperature swings
Compatible with tekmarNet®
Timers, User Switches and
Gateway for additional control
Monitor and control floor
temperature
•
•
•
•

2 of 24© 2011 D538e - 02/11
Congratulations on the purchase of your new kanmor thermostat.
This manual will step through the complete installation, programming and sequence
of operation for this control. At the back, there are tips for control and system
troubleshooting.
Getting Started
Preparation
kanmor or jeweller screwdriver
Phillips head screwdriver
•
•
Wire Stripper•
Tools Required
------------------------------------------------------
------------------------------------------------------
Materials Required
--------------------------------------------------
--------------------------------------------------
2, 3.5 x 25 mm Wood Screws
0.75 or 1.0 mm2flex cable
(Low Voltage Connections)
•
•
Optional Adapter Plate 008e (for
installation on 85 x 85 mm box)
•
Installation
Table of Contents
Getting Started..............................2
Installation .........................................2
Caution..........................................2
Preparation....................................2
Removing The Thermostat Base...3
Mounting The Thermostat Base....3
Thermostat Wiring.........................4
Testing the Thermostat Wiring ......4
Mounting the Thermostat ..............5
Cleaning the Thermostat...............6
Switch Settings..................................6
User Interface....................................7
Display...........................................7
Button Operation...........................7
Symbols Description .....................7
Settings ....................................8-14
Sequence of Operation....................15
Heating Operation.......................15
Cooling Group Operation ............16
Schedules ...................................17
Scenes (System Override) ..........17
Troubleshooting ...............................18
Error Messages......................18-21
Frequently Asked Questions .......22
Job Record..................................23
Technical Data.............................23
Limited Warranty and Product
Return Procedure........................24
Caution
Improper installation and operation of this control could result in damage to the
equipment and possibly even personal injury or death. It is your responsibility
to ensure that this control is safely installed according to all applicable codes and
standards. This electronic control is not intended for use as a primary limit control.
Other controls that are intended and certified as safety limits must be placed into
the control circuit.

3 of 24 © 2011 D538e - 02/11
Choose the placement of the thermostats early in the construction process to
enable proper wiring during rough-in.
Consider the following:
Interior Wall.
Keep dry. Avoid potential leakage onto the control.
Relative Humidity max 92% up to 40°C, 50% RH above 40°C. Non-condensing
environment.
No exposure to extreme temperatures beyond 2-50°C.
No draft, direct sun, or other cause for inaccurate temperature readings.
Away from equipment, appliances, or other sources of electrical interference.
Easy access for wiring, viewing, and adjusting the display screen.
Approximately 1.5 m off the finished floor.
The maximum length of wire is 150 m.
Strip wire to 10 mm for all terminal connections.
Use standard 4 conductor, 0.75 or 1.0 mm2flex cable.
•
•
•
•
•
•
•
•
•
•
•
Installation Location
-------------------------------------------------
-------------------------------------------------
Removing The Thermostat Base
Push
tab
1Remove thermostat
from base
2
To remove the thermostat base:
Place a small slot screwdriver or similar
tool into the slot located on the top of
the thermostat.
While pushing down against the plastic
tab, pull the thermostat away from the
thermostat’s base.
•
•
Mounting The Thermostat Base
If a single gang switch box is used,
an Adaptor Plate 008e is required to
mount the thermostat to the box.
Fasten the base of the
thermostat to the adaptor plate.
Feed the wiring through the
openings in the back of the
adaptor plate and thermostat.
Use the upper and lower screw
holes to fasten the adaptor plate
to the box.
•
•
•
Mounted on switch box
Adaptor
Plate 008e
Switch
Box

4 of 24© 2011 D538e - 02/11
If a switch box was not used, mount the
thermostat directly to the wall.
Feed the wiring through the openings in
the back of the thermostat.
Use screws in the screw holes to fasten the
thermostat to the wall. At least one of the
screws should enter a wall stud or similar
rigid material.
•
•
Stud
60 mm
screwhole
60 mm
screwhole
Thermostat
Base
Wall
Mounted on wallboard
Thermostat Wiring
The thermostat operates a single heating system zone.
Connect tN4, N, L, and terminals on the thermostat to the 1, L, N, and terminals
on the Wiring Center 375x.
Connect the optional auxiliary sensor wires to the sensor terminals 5 and 6.
12 34
Wiring Center 375x
Slab Sensor 079e
OR
Outdoor Sensor 070e
OR
Indoor Sensor 076e, 084
tNt 538e
538e
One Stage Heat
Made in
Canada
Mmm YYYY
Lot # 12345
1001-06
tN4
1N
2L
3
K
4
6
S1
5
Com
Switch Settings:
For instructions see brochure
Setback
Scene
None
Lock
ON
Unlock
Cool Member 1
Off
Off
No Power
NL
Testing the Thermostat Wiring
Testing the Power
---------------------------------------------------
---------------------------------------------------
1. Remove the front cover from the thermostat.
2. Use an electrical test meter to measure (ac) voltage between the L and N
terminals. The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.

5 of 24 © 2011 D538e - 02/11
Mounting the Thermostat
To place the thermostat back on the
mounting base:
Place thermostat bottom tabs on
matching mounting base notches.
Pivot top of the thermostat
towards wall, ensuring wires clear
obstructions.
The top clasp makes a clicking
sound when properly closed.
•
•
•
Pivot
Tab
Testing the Heat Relay
-----------------------------------------------
-----------------------------------------------
1. Remove the front cover from the thermostat.
2. Press the button and set the heating temperature below the current room
temperature. There should be no H1 symbol on the display.
3. Set the electrical test meter to continuity.
4. Place probes between L (3) and (4). There should be no continuity. If there is
continuity then there may be a wiring fault or the relay may be faulty.
5. Press the button and set the heating temperature above the current room
temperature. Make sure the display does not show “WWSD”. The “H1” symbol
should appear on the display.
6. There should be continuity between the L (3) and (4) terminals.
Testing the tekmarNet® 4 Bus
-----------------------------------------
-----------------------------------------
The symbol is shown on the display when communication is present. If the
thermostat is connected in a network and the communication is missing, there may
be an open or short circuit on the tN4 and N bus wires.
1. Remove the front cover from the thermostat.
2. To test for short circuits:
Disconnect the tN4 bus wires on one end.
Install wire nuts on each wire to ensure the wire ends are not touching.
Disconnect the tN4 bus wires on the other end.
Measure for continuity using an electrical meter.
If continuity is present, there is a short circuit fault along the wires. It is
recommended to replace the tN4 bus wires.
3. To test for open circuits:
Disconnect the tN4 bus wires on one end and connect them together.
Disconnect the tN4 bus wires on the other end.
Use an electrical meter to measure for continuity.
If there is no continuity, there is an open circuit fault along the wires. It is
recommended to replace the tN4 bus wires.
•
•
•
•
•
•
•
•
•

6 of 24© 2011 D538e - 02/11
Switch Settings
Switches are set to “On”
position from the factory, and
do not require changing for
most applications.
12 34
tNt 538e
538e
One Stage Heat
Made in
Canada
Mmm YYYY
Lot # 12345
1001-06
tN4
1N
2L
3
K
4
6
S1
5
Com
Switch Settings:
For instructions see brochure
Setback
Scene
None
Lock
ON
Unlock
Cool Member 1
Off
Off
No Power
12 34
Mmm YYYY
Lot # 12345
Switch Settings:
Setback
Scene
None
Lock
ON
Unlock
Cool Member 1
Off
Off
Switch
Position
Action
1
ON
SETBACK
The thermostat follows a programmable setback schedule
as a schedule member if available. Requires the installation
of a Timer 033e to use this feature.
OFF OFF
The thermostat does not follow a programmable setback
schedule.
2
ON
SCENE
The thermostat responds to changes in the scene (system
wide manual overrides). Requires the installation of a User
Switch 480 or 481 to use this feature.
OFF OFF
The thermostat does not respond to scenes.
3
ON NONE
The thermostat is not part of a cooling group.
OFF COOL MEMBER 1
The thermostat is a member of cooling group number 1.
4
ON LOCK ACCESS LEVEL
Locked to ‘User’ access level. Set to Lock when installation
completed.
OFF
UNLOCK ACCESS LEVEL
Unlock to allow ‘User’ and “Installer’ access level. Set to
Unlock during installation process.
tekmarNet®reset control must also be set to Unlocked
(Installer access level).
The thermostats’s exterior can be cleaned using a damp cloth. Moisten the cloth
with water and wring out prior to wiping the control. Do not use solvents or cleaning
solutions.
Cleaning the Thermostat

7 of 24 © 2011 D538e - 02/11
SECONDARY DISPLAYMAIN DISPLAY
HEAT
Heat is turned on.
SUN
Operating at the occupied
(day) temperature.
MOON
Operating at the unoccupied
(night) temperature.
AWAY
Operating at the Away scene
temperature.
COOL GROUP
The cooling group is cooling.
Heating can start once the
cooling is finished.
LOCK
Locked to ‘User’ access level.
CLOCK
Operating on a
programmable schedule.
tekmarNet®
Communication is present.
WARNING SYMBOL
Indicates an error is present.
WARM WEATHER SHUT
DOWN
The heating system has been
shut off for the summer.
Display
Symbols Description
User Interface
Button Operation
Press the or the button to select the room temperature.

8 of 24© 2011 D538e - 02/11
Settings (1 of 7)
Display Range Access Description Set to
40 to 95°F
(4.5 to 35.0°C)
Default = 70°F
(21.0°C)
Installer
User
SET ROOM HEAT
Set the room heating temperature while in the
event.
40 to 95°F
(4.5 to 35.0°C)
Default = 65°F
(18.5°C)
Installer
User
SET ROOM HEAT
Set the room heating temperature while in the
event.
40 to 95°F
(4.5 to 35.0°C)
Default = 62°F
(16.5°C)
Installer SET ROOM HEAT AWAY
Set the room heating temperature while in the Away
scene.
Continued on next page.
• Press and hold down both the and buttons for 2 seconds to change from one step to the next.
• Release both buttons once the step has been reached.
• Press the or the button to change the setting, if available.
• Press and hold down both the and buttons for 2 seconds to go to the next step, OR
• After 10 seconds of no button activity, the display goes back to normal operation.
• Note: Set switch setting #4 and tekmarNet®system control to Unlock to change Access level to Installer.
Press
+
Together

9 of 24 © 2011 D538e - 02/11
Settings (2 of 7)
Display Range Access Description Set to
40 to 122°F
(4.5 to 50.0°C)
Default = 72°F
(22.0°C)
Installer
User
SET FLOOR HEAT
Set the floor heating temperature while in the
event.
Available when:
A slab sensor is installed on the auxiliary sensor
input AND Sensor setting in the Adjust menu is set
to Floor AND Room Sensor setting in the Adjust
menu is set to Off.
•
40 to 122°F
(4.5 to 50.0°C)
Default = 65°F
(18.5°C)
Installer
User
SET FLOOR HEAT
Set the floor heating temperature while in the
event.
Available when:
A slab sensor is installed on the auxiliary sensor
input AND Sensor setting in the Adjust menu is set
to Floor AND Room Sensor setting in the Adjust
menu is set to Off.
•
Off, 30 sec, On,
On +
Default = 30 sec
Installer
User
BACKLIGHT
Select the backlight operation.
Off = Permanently Off
30 = Temporary on for 30 seconds
On = Permanently On
On + = On during and off during
Continued on next page.

10 of 24© 2011 D538e - 02/11
Display Range Access Description Set to
°F or °C
Default = °F
Installer
User
TEMPERATURE UNITS
Press the or the button to change from °F to
°C and vice versa.
Device Type with
Software Version,
Address
Installer
User
DEVICE TYPE
Display alternates between the Device Type (large
number) with Software Version (upper right corner)
and the thermostat address.
40 to 95°F
(4.5 to 35.0°C)
Default = 85°F
(29.5°C)
Installer MAXIMUM SET ROOM HEAT
Set the maximum room heating limit while in the
event.
40 to 95°F
(4.5 to 35.0°C)
Default = 85°F
(29.5°C)
Installer MAXIMUM SET ROOM HEAT
Set the maximum room heating limit while in the
event.
40 to 95°F
(4.5 to 35.0°C)
Default = 45°F
(7.0°C)
Installer MINIMUM SET ROOM HEAT
Set the minimum room heating limit.
Settings (3 of 7)
Continued on next page.

11 of 24 © 2011 D538e - 02/11
Display Range Access Description Set to
Off, 40 to 122°F
(Off, 4.5 to
50.0°C)
Default = 72°F
(22.0°C)
Installer
User
SET FLOOR MINIMUM
Set the floor minimum temperature while in the event.
The floor minimum heats the floor even when the room
temperature is satisfied.
The measured floor temperature is shown in the upper
right hand corner of the display.
Available when:
Room Sensor setting in the Adjust menu is set to
On AND
A slab sensor is installed on the auxiliary sensor
input AND
Sensor setting in the Adjust menu is set to Floor.
•
•
•
Off, 40 to 122°F
(Off, 4.5 to
50.0°C)
Default = Off
Installer
User
SET FLOOR MINIMUM
Set the floor minimum temperature while in the event.
The floor minimum heats the floor even when the room
temperature is satisfied.
The measured floor temperature is shown in the upper
right hand corner of the display.
Available when:
Room Sensor setting in the Adjust menu is set to
On AND
A slab sensor is installed on the auxiliary sensor
input AND
Sensor setting in the Adjust menu is set to Floor.
•
•
•
Settings (4 of 7)
Continued on next page.

12 of 24© 2011 D538e - 02/11
Display Range Access Description Set to
40 to 122°F, Off
(4.5 to 50.0°C,
Off)
Default = 85°F
(29.5°C)
Installer
FLOOR MAXIMUM
Set the floor maximum temperature in order to protect
the floor covering.
Available when:
Room Sensor setting in the Adjust menu is set to
On AND
A slab sensor is installed on the auxiliary sensor
input AND
Sensor setting in the Adjust menu is set to Floor.
•
•
•
1, 2, 3, 4
Default = 1 Installer
SCHEDULE
Thermostat can follow schedule master 1, 2, 3, or 4.
Available when:
Switch setting 1 is set to Setback (On Position).•
On or Off
Default = On Installer
ROOM SENSOR
Select whether the built-in air temperature sensor is
on or off.
Available when:
A floor sensor or room sensor is installed on the
auxiliary sensor input.
Settings (5 of 7)
Continued on next page.

13 of 24 © 2011 D538e - 02/11
Display Range Access Description Set to
Off, Room,
Outdoor, Floor,
Floor dSP Installer
AUXILIARY SENSOR
Select the type of auxiliary sensor.
Off = no auxiliary sensor
Room = Indoor Sensor 076e, 084
Outdoor = Outdoor Sensor 070e
Floor = Slab Sensor 079e
Floor dSP = Show floor sensor reading in upper
number field.
Available when:
Auxiliary sensor automatically detected.
Auto,
SYn(Synchronize)
Default =
Sychronize
Installer
HEAT CYCLES PER HOUR
Select either Auto cycle or Synchronize with other
thermostats on the tekmarNet®system.
Choose Synchronize when zone heated using a boiler.
Choose Auto when zone is non-hydronic heating.
Available when:
No reset control on the tekmarNet®system.•
OFF, dLy (delay),
On
Default = On Installer
HEATING SUPPLY PUMP
Select whether or not the system supply pump should
turn on, be delayed (for thermal motor or wax actuator)
or be off to allow a zone group pump per manifold.
Available when:
A reset control is present on the tekmarNet®system.•
Settings (6 of 7)
Continued on next page.

14 of 24© 2011 D538e - 02/11
Display Range Access Description Set to
01 to 24
(no reset control),
b:01 to b:24
(reset control - boiler),
1:01 to 1:24
(reset control - mixing)
Installer
tekmarNet®ADDRESS
The address is shown in the large number field. “Auto” is
shown in the upper number field when using automatic
addressing.
Press the or the button to manually select
an address.
The address can be returned to automatic “Auto”
addressing when address set above 24.
None Installer
User
ESCAPE
Press the or the button to return to normal
operation.
Settings (7 of 7)

15 of 24 © 2011 D538e - 02/11
Heating Operation Section A
Sequence of Operation
When using only a room temperature sensor, the thermostat operates the heating
system to maintain the Set Room Heat temperature.
When using only a floor temperature sensor, the thermostat operates the heating
system to maintain the Set Floor Heat temperature. In this case, the thermostat
does not try to control the air temperature. This is ideal for bathrooms and some
kitchen applications where the customer wants their feet to feel warm on the floor.
This is also ideal for garages so that the heating system is not affected by the
opening of the garage door in cold outdoor weather.
When using both a room temperature sensor and a floor temperature sensor, the
thermostat always maintains the Floor Minimum temperature, even when the air
temperature is satisfied. When the air temperature is below the Set Room Heat
temperature, the thermostat operates the heating system to maintain the Set Room
Heat temperature. The floor is never heated above the Floor Maximum setting in
order to protect the floor covering.
The H1 symbol is shown on the display when the thermostat is heating. The heat
can cycle on and off within +/- 1°C of the Set Room Heat temperature.
Freeze Protection
----------------------------------------------------
----------------------------------------------------
The thermostat operates the heat whenever the room or floor temperature falls
below 4.5°C.
Exercising
----------------------------------------------------------
----------------------------------------------------------
When connected to a tekmarNet®reset control, the thermostat exercises the heat
relay for 10 seconds every 3 days. Exercising helps prevent zone valves or zone
pumps from failing due to precipitate buildup. During exercising, the thermostat
shows “TEST” on the display.
Flushing
------------------------------------------------------------
------------------------------------------------------------
The flushing feature is for open-loop systems that use a domestic hot water tank
as a heat source. Flushing ensures that fresh potable water is circulated through
the system once each day. If the thermostat is connected to a tekmarNet®reset
control with the Flushing feature turned on, the thermostat display will display the
“FLUSH” icon for the duration of the flushing operation.
Hydronic System Supply Pump
---------------------------------------
---------------------------------------
When connected to a tekmarNet
®
reset control, the thermostat’s Supply Pump
setting affects how the primary pump or mix pump on the reset control operates.
When connected to the boiler bus, the primary pump is affected. When connected
to the mix bus, the mix system pump is affected.
If the thermostat operates a motorized zone valve or a zone pump, the Supply
Pump setting should be set to On.

16 of 24© 2011 D538e - 02/11
If the thermostat operates a thermal motor (wax actuator) zone valve, set the Supply
Pump setting to Delay. This provides a three minute delay to allow the zone valve
to open before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the Supply Pump setting
can be set to Off. This allows the Wiring Center 375x to operate the pump for the
manifold.
DHW Tank Priority
---------------------------------------------------
---------------------------------------------------
When a tekmarNet®reset control is heating an indirect Domestic Hot Water (DHW)
tank, the thermostat may shut off the heating zones to allow the DHW tank to recover
quickly. This is determined by the DHW priority of the tekmarNet®reset control.
Warm Weather Shut Down
--------------------------------------------
--------------------------------------------
When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD)
setting on the tekmarNet®reset control, the heating system is shut off.
Cooling Group Operation Section B
In order to prevent heating and cooling at the same time, this thermostat can operate
together with other thermostats on a tN4 system to form a cool group.
In a cool group, one thermostat is assigned as the cool group master. The cool
group master operates the cooling equipment for the group. This thermostat can
be set to be a member of the cool group.
When operating as a cool group, the air temperature readings of all the cool group
member thermostats are communicated to the cool group master and a temperature
average is determined.
When the cool group master is in cooling operation, the cool group member
thermostats do not operate the heating system for air heating.
If the Set Room Heat temperature is adjusted while the cool group is cooling, the
snowflake icon is flashed to alert the user that the cooling is presently on. Once
the cooling shuts off, the heating can start operation.
This thermostat joins cool group number 1 when switch setting 3 is set to cool member
1 (Off position).
Cool Group 1
Master MemberMember
tN4 Communication

17 of 24 © 2011 D538e - 02/11
Schedules Section D
Lowering the room temperature setting reduces the amount of fuel required to heat
the building resulting in energy savings.
This thermostat can follow a programmable schedule in order to automatically
lower the room temperature setting. A schedule master such as a Timer 033e is
required in order to gain programmable schedule functionality.
When operating on a programmable schedule, a symbol is shown, as well as a
or a . The or indicates the current operating temperature.
If a symbol does not appear, there is no schedule available.
Display Action
Occupied temperature. No schedule.
Unoccupied temperature. No schedule.
Programmable schedule at
occupied
temperature.
Programmable schedule at
unoccupied
temperature.
Scene Display Room Temperature Setting
1or or Follows programmable schedule or
operates at the occupied temperature.
2Away Away temperature.
3Unoccupied temperature.
Scenes (System Override) Section E
When a programmable schedule is selected, there is a time delay for the temperature
to change from the temperature to the temperature.
The thermostat uses Optimum Start to predict the heat up and cool off rate of
the room. The optimum start feature allows the room to reach the set room
temperature by the time set in the programmable schedule. This applies for both
heating and cooling.
Scenes provide an easy way to save energy while away on vacation, or override a
pre-set schedule when plans change. tekmarNet®devices such as a User Switch
480 or 481 provide scene adjustment.
This thermostat responds to the following scenes:
While in the Away scene, the room temperature cannot be changed using the or
buttons. Change the scene from Away to or to change the temperature.

18 of 24© 2011 D538e - 02/11
Troubleshooting
Error Messages (1 of 4)
Error Message Description
CONTROL ERROR
The thermostat was unable to correctly read settings from memory and has reloaded the factory
default settings. The thermostat does not operate the heating, cooling, or the fan while this error
message is present.
Error clears once all adjust menu settings in the Installer access level (unlocked) have been
checked. Set thermostat’s switch setting #4 to unlock and unlock the tekmarNet®system control.
Then press and hold and buttons together for 2 seconds to enter the adjust menu. Continue
until all settings have been reviewed.
BUS ERROR
The tekmarNet®4 communication bus has either an open or a short circuit. The result is that there
are no communications. Check for loose wires. Check for short circuits between the tN4 and N
wires. Check for correct polarity between the N and L wires.
Error clears automatically once wiring fault has been corrected.
If the thermostat is intentionally removed from the tekmarNet®4 bus, press the and buttons
together to clear the error message.
DEVICE LIMIT
The number of devices on the tekmarNet
®
bus has exceeded 24. Devices include tekmarNet
®
Thermostats and Setpoint Controls. The device count must be lowered to 24 or less. If possible,
move devices to other tekmarNet®buses.
Error clears automatically once the number of devices on the tekmarNet®bus is at 24 or lower.

19 of 24 © 2011 D538e - 02/11
Error Messages (2 of 4)
Error Message Description
ADDRESS ERROR
This thermostat and another device have been manually given the same tekmarNet®address.
Error clears automatically once this thermostat is given a new manually set address or if the
thermostat is set to automatic addressing.
ROOM SENSOR SHORT CIRCUIT
The built-in air temperature sensor has a short circuit fault. Do not confuse this error with the auxiliary
room sensor short circuit error.
This error cannot be field repaired.
Contact your wholesaler or kanmor sales representative for details on repair procedures.
ROOM SENSOR OPEN CIRCUIT
The built-in air temperature sensor has an open circuit fault. Do not confuse this error with the
auxiliary room sensor short circuit error.
This error cannot be field repaired.
Contact your wholesaler or kanmor sales representative for details on repair procedures.
COOL MEMBER ERROR
Switch setting #3 has been selected to join a cooling group as a member, yet there is no cooling
group master thermostat.
Error clears once the thermostat detects a cool group master or switch setting #3 is set to none.

20 of 24© 2011 D538e - 02/11
Error Message Description
FLOOR SENSOR SHORT CIRCUIT
The auxiliary floor sensor has a short circuit. Check for damaged wires. Locate and repair the
problem as described in the Data Brochure D079e.
Error clears once the floor sensor fault is corrected.
FLOOR SENSOR OPEN CIRCUIT
The auxiliary floor sensor has an open circuit. Check for loose or damaged wires. Locate and repair
the problem as described in the Data Brochure D079e.
Error clears once the floor sensor fault is corrected.
If the floor sensor was intentionally removed, locate the Room Sensor setting in the Adjust menu
and set to On. Power the thermostat down and up to clear the error.
OUTDOOR SENSOR SHORT CIRCUIT
The auxiliary outdoor sensor has a short circuit. Check for damaged wires. Locate and repair the
problem as described in the Data Brochure D070e.
Error clears after the outdoor sensor fault is corrected.
OUTDOOR SENSOR OPEN CIRCUIT
The auxiliary outdoor sensor has an open circuit. Check for loose or damaged wires. Locate and
repair the problem as described in the Data Brochure D070e.
Error clears once the outdoor sensor fault is corrected.
If the outdoor sensor was intentionally removed, power the thermostat down and up to clear the
error.
Error Messages (3 of 4)
This manual suits for next models
2
Table of contents
Other Kanmor Thermostat manuals