KE2 21710 User manual

KE2 WiFi
Service Tool
(pn 20906)
KE2 LDA (pn 21253)
Application:
▪Designed for small to mid-sized racks - eliminates overly
complicated controls that are designed for larger systems.
▪Easily applied to new or existing installations.
▪Supports up to 5 stages of loading with onboard relays.
▪On racks with compressors all of equal HP, will automatically
equalize runtime
▪Racks with compressors of varying HP, it maintains consis-
tent suction pressure.
▪Master View webpages, allows technicians to quickly and
easily assess the system’s operation & Review historical per-
formance using onboard data logging.
▪Works as a stand-alone rack controller or in conjunction with
KE2 Evaporator Eciency controllers.
▪Can limit the amount of defrost load, as dictated by the site’s
electrical requirements.
The KE2 Compressor Sequencer is new to KE2 Therm’s refrigeration con-
trols suite. Designed for small to mid-sized racks, The KE2 Compressor
Sequencer brings the controller’s features in line with the job’s require-
ments. It eliminates the necessity of using overly complicated controls
designed for larger systems.
The KE2 Compressor Sequencer replaces aging rack controllers or can
retrot racks with existing mechanical controls.
The controller supports up to 5 stages of loading through its onboard
relays. Each relay can be congured as the rack’s: Fixed Speed Compres-
sor, Compressor Unloader, Digital Scroll Compressor, Master Liquid Line
Solenoid, or Hot Gas Defrost Relay.
When applied to racks with compressors all of equal horse power, the
controller will automatically equalize the runtime of each compressor.
Compressors can also be of various HP. When more than one HP is se-
lected the controller will use the stage with the smallest capacity, to
maintain consistent suction pressure.
The KE2 Compressor Sequencer includes KE2 Therm’s Master View web-
pages, allowing technicians to quickly and easily assess the system’s
operation, and review historical performance through onboard data
logging.
The compressor sequencer works as a stand-alone rack controller or in
conjunction with KE2 Evaporator Eciency controllers. When applied
with the KE2 Evaporator Eciency controllers the KE2 Compressor Se-
quencer can limit the amount of defrost load, as dictated by the site’s
electrical requirements.
Part Numbers - Controllers & Accessories
Part Number Description
KE2 Compressor Sequencer
21246 Controller only
Pressure Transducers
20201 Pressure Transducer – 0 to 150 psia, 10 ft. leads
20202 Pressure Transducer – 0 to 500 psig, 10 ft. leads
Temperature Sensors
21230 High temp for discharge at condenser inlet, 15 ft.
20199 Standard for all other temp inputs, 10 ft. (black)
Solid State Relay
21304 Solid State Relay for Compressor Sequencer (used to control
5th compressor stage or digital scroll
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43
April 2018
KE2 Compressor Sequencer pn 21710
Quick Start Guide
This reference should remain on site with the installed KE2 Compressor Sequencer
Parts List - Included
The following are included in the KE2 Compressor
Sequencer kit 21710:
(1) KE2 Compressor Sequencer 120/208-240 VAC
controller
(1) high voltage safety shield
(1) 15’ high-temperature sensor
(1) 0-150 psia pressure transducer with 10ft. lead
(1) 0-500 psig pressure transducer with 10ft. lead
(1) 10 ft. temperature sensor for suction temperature
(4) 90 degree quick disconnects
(4) self-tapping screws
(2) course thread screws (1) ne thread machine screw with lock washer
(4) wire ties (rated for high & low temp)
(1) 5-position pluggable connector
(4) 3-position pluggable connectors (for power in, transducer & 3A relay)
(9) 2-position pluggable connectors (for sensors & digital input, analog output)
(1) 120 Voltage jumper
(1) 208-240V Voltage jumper (already installed on controller)
Other Supplies - Not Included
The KE2 Compressor Sequencer installation requires standard truck stock items.
A list of items is provided.
Conduit to go between the controller and the electrical panel
(2) Conduit connectors (straight or elbow as required)
High voltage wires matched to the number of compressors, liquid line so-
lenoid (if used), and the controller
Wire labeling (numbers, colors, etc.)
Additional wire ties
18 gauge twisted shielded pair (if extending sensor wires)
Before you begin:
NOTE: After the controller is wired, the KE2 Compressor Sequencer is
setup using the controller’s onboard webpage.
To access the webpage on the controller you will need a laptop and
Ethernet cable, or a mobile device and either the KE2 LDA communica-
tion device, or the KE2 WiFi Service Tool. (See page 3)

Q.2.43 April 2018
Page 2
KE2 Compressor Sequencer
Quick Start Guide
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
D1
D3
D2
Ground
T2 Air Optional
T3 Discharge
T1 Suction
GREEN (SIGNAL)
Digital Scroll Unloader
(0-10V ANALOG OuT)
RED (+5V)
BLACK (GROUND)
PT SH
DIGITAL INPUTS
ROUTER / SWITCH
CAT5e CABLE
(ETHERNET)
RJ 45
L1
NO NC
COM
NO NC
COM
COM
NO
NC
COM
NO
NC
LINE
NEUTRAL
GROUND
CONTROLLER
POWER INPUT
KE2 COMPRESSOR SEQUENCER - Fixed Speed Compressors
COMP
STAGE 4
COMP
STAGE3
COMP
STAGE 2
COMP
STAGE 1
VOLTAGE JUMPER
208-240V Default
L1
CON2
Compressor 2
CON1
Compressor 1
L1
L1
L1
–+
CON3
Compressor 3
CON4
Compressor 4
Signal
–+
PT DH
GREEN
RED
BLACK
+14V
EXTERNAL DIGITAL
SWITCH
12VDC; 100 OHMS
120 AMPS
CON5
Compressor 5
L2
LEGEND
Digital Scroll Unloader −
Analog
output to control digital scroll compressor.
PT SH −
0-150 psia pressure transducer
for suction header
T1 Suction −
-50° to 150°F Tempera-
ture sensor for suction header
T2 Air −
Optional -50°to 150°F tempera-
ture sensor for space temperature. Allows
oating suction control feature.
T3 Discharge −
0° to 300°F temperature
sensor for discharge header
PT DH −
0 to 500 psig pressure transducer
for discharge header
Wiring the Controller
D1
D3
D2
Ground
T2 Air Optional
T3 Discharge
T1 Suction
GREEN (SIGNAL)
Digital Scroll Unloader
(0-10V ANALOG Out)
RED (+5V)
BLACK (GROUND)
PT SH
DIGITAL INPUTS
ROUTER / SWITCH
CAT5e CABLE
(ETHERNET)
RJ 45
L1
NO NC
COM
NO NC
COM
COM
NO
NC
COM
NO
NC
LINE
NEUTRAL
GROUND
CONTROLLER
POWER INPUT
KE2 COMPRESSOR SEQUENCER - Compressor with Unloaders
COMP
STAGE 4
COMP
STAGE3
COMP
STAGE 2
COMP
STAGE 1
VOLTAGE JUMPER
208-240V Default
L1
CON2
Unloader 1
CON1
Compressor 1
L1
L1
L1
–+
CON3
Unloader 2
CON4
Compressor 2
Signal
–+
PT DH
GREEN
RED
BLACK
+14V
EXTERNAL DIGITAL
SWITCH
12VDC; 100 OHMS
120 AMPS
CON5
Compressor 3
L2
NOTE : Unloaders are wired to the
Normally Closed contacts

Q.2.43 April 2018
Page 3
KE2 Compressor Sequencer
Quick Start Guide
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Setup the controller by going to the
Setpoints page.
❶After the controller is wired, the KE2 Compressor Sequencer is setup using the
controller’s onboard webpage. To access the webpage on the controller you will
need a laptop and Ethernet cable, or a mobile device and either the KE2 LDA com-
munication device, or the KE2 WiFi Service Tool.
Power Up & Enter Setpoints
thermsolutions
ENTER
BACK
Compressor
Sequencer
®
Controller
wired and ready
Ethernet Cable
Computer
thermsolutions
ENTER
BACK
Compressor
Sequencer
®
Superheat
0.0 F Suct Pressure
96.2 F Suct Temp
87.7 F
Superheat
0.0 F Suct Pressure
96.2 F Suct Temp
87.7 F
Controller
wired and ready
Ethernet Cable
Computer, Tablet or Smart Phone
thermsolutions
PWR WIFILANWAN 3G/4G
Ethernet Cable
thermsolutions
ENTER
BACK
Compressor
Sequencer
®
Controller
wired and ready
Superheat
0.0 F Suct Pressure
96.2 F Suct Temp
87.7 F
Computer, Tablet or Smart Phone
Option A
Option B
Option C
NOTE: Computer requires Static IP.
See bulletin Q.5.11
❸ This will take you to the controller’s Home Page. From the Home Page select the
Setpoints tab.
❷Enter the controller’s IP address, into your web browser’s address bar. The IP ad-
dress is found on a sticker on the controller.
Specications
Controller
Input Voltage: 100VAC - 240VAC
Ambient Temp: -40°F to 140°F (-40°C to 60°C)
Operating Temp: -40°F to 140°F (-40°C to 60°C)
Inputs:
(3) temperature sensor
(3) digital input
(2) pressure sensor inputs
Relays: (4)10A inductive fan contactor
pilot
Digital Input
No function, Compressor Module,
Oil Safety Switch, High Pressure
Switch, System O, 2nd Pressure
Set Point
Communication: Standard TCP/IP
Pressure Transducer - pn 20201 (10 ft lead)
Pressure Range: 0 to 150 psig
Proof Pressure: 450 psi
Burst Pressure: 1500psi
Operating Temp: -40°F to 275°F (-40°C to 135°C)
Pressure Transducer - pn 20202 (10 ft lead)
Pressure Range: 0 to 500 psig
Proof Pressure: 1000 psi
Burst Pressure: 2500 psi
Operating Temp: -40°F to 275°F (-40°C to 135°C)

Q.2.43 April 2018
Page 4
KE2 Compressor Sequencer
Quick Start Guide
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
❹ On the Setpoints page choose Login, in the
lower right corner.
Default User Name: ke2admin
Default Password: ke2admin
Click on Submit.
❺ You will be back on the Setpoints page. Make
desired setpoint changes. Click the Save button.
Note: For security reasons, the User Name and
Password should be changed from the default.
Once your are logged in, go to the Setting page to
change the User Name and Password.
❻ On the Setpoints page click System is O. The button will be yellow.
The button will return to its normal color, and the system will start.
Login
❻ ❹
❺
Variables Menu - View Only
Full Name Description
SUCTION PRESSURE Suction Pressure as read by the controller
CAP % Available horse power currently being utilized
COMPRESSOR 1 RELAY Current state of the 1st Compressor Relay
COMPRESSOR 2 RELAY Current state of the 2nd Compressor Relay
COMPRESSOR 3 RELAY Current state of the 3rd Compressor Relay
COMPRESSOR 4 RELAY Current state of the 4th Compressor Relay
COMPRESSOR 5 RELAY Current state of the 5th Compressor Relay
SUPERHEAT Superheat as calculated by the controller
T1 SUCTION TEMP Suction temperature as measured by the controller
SATURATION TEMP Saturation temperature as calculated by the controller
Only one of these or the other
is displayed, if selected.
T2 MONITOR Temperature to be monitored that is selected by the installer
INT COMP TEMP Input is reading digital scroll’s internal temperature sensor
DISCH PRESSURE Discharge Pressure as read by the controller
DISCH SUPERHEAT Superheat as calculated by the controller
DISCH TEMP Discharge Temperature sensor reading as measured by the controller
DISCH SAT TEMP Discharge Temperature as read by the controller
DIG 1 STATUS Current status of the Digital Input #1
DIG 2 STATUS Current status of the Digital Input #2
DIG 3 STATUS Current status of the Digital Input #3
IP OCTET 1 The rst three digits of the IP address
IP OCTET 2 The second three digits of the IP address
IP OCTET 3 The third three digits of the IP address
IP OCTET 4 The fourth three digits of the IP address
SUBNET MASK OCTET 1 The rst three digits of the subnet mask
SUBNET MASK OCTET 2 The second three digits of the subnet mask
SUBNET MASK OCTET 3 The third three digits of the subnet mask
SUBNET MASK OCTET 4 The fourth three digits of the subnet mask
FIRMWARE VERSION Current version of the rmware on the controller

Q.2.43 April 2018
Page 5
KE2 Compressor Sequencer
Quick Start Guide
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Setpoints
Setpoint Description Range / Options Default
Front of Controller
These can be accessed from front of
controller. All other setpoints are ac-
cessed on the controller’s web page.
SUCTION PRESSURE Suction Pressure setpoint to cycle the compressors
Min 0 psig
Most refrigerants: 150 psia; R410A: 300 psig
R744: 500 psig
250 psig for
R-744, 25 psig
for all else
CUT OUT PRESSURE When below the cut out pressure, system turns o
Min 0 psig
Most refrigerants: 150 psia; R410A: 300 psig
R744: 500 psig
5 psig
2ND SUCTION
PRESSURE
When enabled w. digital input (short across terminals),
will control fans to run at this pressure, overriding nor-
mal operation until short removed from digital input
Min 0 psig
Most refrigerants: 150 psia; R410A: 300 psig
R744: 500 psig
50 psig
TEMP UNITS Temperature Units Fahrenheit, Celsius Fahrenheit
SUC PRESS DIFF Suction Pressure Dierential 0.1 to 5.0 psi 2.0 psi
REFRIGERANT Type of refrigerant being used in the system.
R404A, R507, R407A,R407C, R422A, R422D,
R134A, R22, R717, R438A, R408A, R409A, R407F,
R410A, R744, R448A, R450A, R513A
404A
Relays
RELAY#1 Relay controls the 1st stage
HG Defr Relay, LLS, Digital Comp*, Fixed Speed,
Unloader for Cmp 2, Unloader for Cmp 3,
Unloader for Cmp 4, Unloader for Cmp 5
Disabled
RELAY#2 Relay controls the 2nd stage
HG Defr Relay, LLS, Digital Comp*, Fixed Speed,
Unloader for Cmp 1, Unloader for Cmp 3,
Unloader for Cmp 4, Unloader for Cmp 5
Disabled
RELAY#3 Relay controls the 3rd stage
HG Defr Relay, LLS, Digital Comp*, Fixed Speed,
Unloader for Cmp 1, Unloader for Cmp 2,
Unloader for Cmp 4, Unloader for Cmp 5
Disabled
RELAY#4 Relay controls the 4th stage
HG Defr Relay, LLS, Digital Comp*, Fixed Speed,
Unloader for Cmp 1, Unloader for Cmp 2,
Unloader for Cmp 3, Unloader for Cmp 5
Disabled
RELAY#5 Relay controls the 5th stage
HG Defr Relay, LLS, Digital Comp*, Fixed Speed,
Unloader for Cmp 1, Unloader for Cmp 2,
Unloader for Cmp 3, Unloader for Cmp 4
Disabled
* Only one digital compressor Digital Comp ON/OFF requires a solid state relay
COMP HP PER RELAY labels the HP of each compressor 0.1 to 50 HP None
Defrost
Load
MAX LOAD Maximum circuit concurrent load 6,000,000 Btu
15,000 Amps 0
UNITS Units for heater load input Btu/Amps Amps
Refrigeration
SUCTION PRESSURE
(Also available from the front of
the controller.)
Target Suction Pressure - Setpoint to cycle the com-
pressors
Min 0 psig
Most refrigerants: 150 psia; R410A: 300 psig
R744: 500 psig
250 psig for
R-744, 25 psig
for all else
REFRIGERANT
(Also available from the front of
the controller.)
Type of refrigerant being used in the system.
R404A, R507, R407A,R407C, R422A, R422D,
R134A, R22, R717, R438A, R408A, R409A,
R407F, R410A, R744, R448A, R450A, R513A
404A
MIN COMP RUN TIME Min. run time to keep any compressor relay energized 0 to 240 seconds 60 seconds
MIN COMP OFF TIME Minimum o time to keep any compressor relay de-
energized 0 to 240 seconds 60 seconds
MIN COMP SWITCH TIME Min. time between switching compressor on or o 0 to 240 seconds 15 seconds
2ND SUCTION
PRESSURE(Also available
from the front of the controller.)
When enabled w. digital input (short across terminals),
controls fans to run at this pressure, overriding normal
operation until short removed from digital input
Min 0 psig
Most refrigerants: 150 psia ; R410A: 300 psig
R744: 500 psig
50 psig
CUT OUT PRESSURE
(Also available from the front of
the controller.)
When below the cut out pressure, system turns o
Min 0 psig
Most refrigerants: 150 psia; R410A: 300 psig
R744: 500 psig
5 psig
MAX PUMP OUT TIME Sets time limit to reach cut out pressure 0 to 240 minutes 2 minutes
AUX TEMP TYPE Options for using the auxiliary temperature sensor O (Disabled) /monitor/2nd liquid
temperature for circuit #2 Disabled
TEMP UNITS Temperature Units (can also be accessed from front of
the controller) Fahrenheit, Celsius Fahrenheit
MIN SAFETY SUC SH Safety for Minimum Suction Superheat 0 to 50ºF / 0 to 27.8K 0ºF / 0K
MAX SAFETY SUC TMP Safety for Maximum Suction Temperature 5 to 90ºF / -15 to 32ºC 90º F / 32ºC
MAX SAFETY PRESSURE Safety for Maximum Pressure - when
exceeded sends Alerts 0 to 500 psig 400 psig

KE2 Compressor Sequencer
Quick Start Guide
Q.2.43 April 2018
Page 6
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Setpoint Description Range / Options Default
Digital
Inputs
DIG IN 1, 2, 3 MODE Sets the function of the Digital Input HG Defr Req, 2nd Pres, Comp Mod, Oil Safety
Sw, Hi Pres Switch, Sys O Disabled
DIG IN 1, 2, 3 STATE Sets whether the switch activates with Open or Closed Open / Closed Closed
Sensor Offsets
AUX TEMP OFFSET An oset added or subtracted from the auxiliary tem-
perature sensor reading, if needed -5 to 5 Fº / -2.8 to 2.8K 0 Fº/K
SUCT PRESSURE OFFSET An oset added or subtracted from the suction line
pressure transducer reading, if needed -5 to 5 Fº / -2.8 to 2.8K 0 Fº/K
SUCT TEMP OFFSET An oset added or subtracted from the suction tem-
perature sensor reading, if needed -5 to 5 Fº / -2.8 to 2.8K 0 Fº/K
DISCH TEMP OFFSET The oset added or subtracted from the discharge
temperature sensor reading, if needed -5 to 5 Fº / -2.8 to 2.8K 0 ºF/K
DISCH PRESS OFFSET An oset added or subtracted from the discharge
pressure transducer reading, if needed -5 to 5 Fº / -2.8 to 2.8K 0 ºF/K
Alarms
MAX DISCH PRES Turns system of when exceeded 100 to 500 psig 450 psig
MIN SUCTION SH The lowest acceptable superheat. Turns system o
when exceeded 5 to 50 ºF / 2.8 to 27.8K 15 ºF / 8.3K
MAX SUCTION SH The highest acceptable superheat 25 to 200 ºF / 13.9 to 111.1K 50 ºF / 27.8K
MIN/MAX SH DELAY
The amount of time, in minutes, before an alarm is
initiated when the minimum or maximum superheat
setting is surpassed.
0 to 254 minutes Disabled
MAX DISCH TEMP The maximum discharge temperature before an alarm
is initiated. Turns o system when exceeded. 25 to 300ºF /-3.9 to 148.9 ºC 268
ºF/131.1ºC
MAX DISCH TEMP
DELAY
The amount of time, in minutes, before an alarm is
initiated when the Maximum Discharge Temperature
setting is surpassed.
0 to 254 minutes Disabled
MAX DIS PRS DELAY
The amount of time, in minutes, before an alarm is
initiated when the Maximum Discharge Pressure set-
ting is surpassed.
0 to 254 minutes Disabled
Setpoints - Continued
Manual Menu
Name Description Range Default
MANUAL CONTROL
CLEAR ALARMS Clear all active alarms
FACTORY RESET Reset the controller to the factory default setpoints Reset
WEB PASSWORD RESET Reset the web password to the factory default Reset
KE2 SMART ACCESS MODE Turn KE2 Smart Access on or o Disable, Enable Disable
DHCP MODE Turn DHCP mode on or o Disable, Enable Disable

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 7
KE2 Compressor Sequencer
Quick Start Guide
Critical Alarms: the System is NOT working & Red LED is illuminated
Alarm Name Description
*Low Suction
Superheat
• If the suction superheat is below the Min Suction SH (Minimum Suction Superheat) setpoint for longer than Min/Max SH Delay (Minimum/
Maximum Superheat Delay)
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll Low Suction Superheat across the front panel
*High
Suction
Superheat
• If the suction superheat is below the Max Suction SH (Maximum Suction Superheat) setpoint for longer than Min/Max SH Delay (Minimum/
Maximum Superheat Delay)
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll High Suction Superheat across the front panel
*High
Discharge
Temperature
• If the discharge temperature is above Max Disch Temp (Maximum Discharge Temperature) setpoint for longer than Max Dis Tmp Del
(Maximum DischargeTemperature Delay)
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll High Disch Temperature across the front panel
- NOTE: The max discharge temperature alarm turns on at the setpoint and turns o at 18 degrees F below its setpoint.
*High
Discharge
Pressure
• If the discharge pressure is above the Max Disch Pres (Maximum Discharge Pressure) for longer than the Max Dis Prs Del (Maximum Discharge
Pressure Delay)
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll High Disch Pressure across the front panel
Discharge
Pressure
Sensor Alarm
• If the Discharge Pressure Sensor is Alarming, the sensor is shorted, open, or out of range.
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll Discharge Pres Sensor across the front panel
Discharge
Temperature
Sensor Alarm
• If the Discharge Temperature Sensor is Alarming, the sensor is shorted or open.
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll T3 Disch Sensor across the front panel
Suction
Pressure
Sensor Alarm
• If the Suction Pressure Sensor is Alarming, the sensor is shorted, open, or pressure is out of range.
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll Pressure Sensor across the front panel
Suction
Temperature
Sensor Alarm
• If the Suction Temperature Sensor is Alarming, the sensor is shorted or open.
- All stages will be turned o
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Red LED on the front Panel will be illuminated
- The controller will scroll T1 Suction Sensor across the front panel
* Alarms may be disabled by typing Disabled in the Time Delay eld in the Alarms section of the Setpoints page.

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 8
KE2 Compressor Sequencer
Quick Start Guide
Non -Critical Alarms: the System is working and the Amber LED is illuminated
For each non-critical alarm, the system will continue running
and the controller will try and compensate for the issue.
Alarm Name Description
T2 Aux Sensor
T2 Monitor
• Auxiliary Temperature Sensor Alarm indicates the sensor is short or Open
- The system will continue running and the controller will try and compensate for the issue.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- The controller will scroll T2 Aux Sensor across the front panel
T2 Aux Sensor
Internal Compres-
sor Temperature
• Auxiliary Temperature Sensor Alarm indicates the sensor is short or Open
- The system will continue running and the controller will try and compensate for the issue.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- The controller will scroll T2 Aux Sensor across the front panel
Evaporator
Communications
• If the Site View Manager is selected, and one or more of the KE2 Evap Site View members are not communicating
- The system will continue running and the controller will try and compensate for the issue.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- The controller will scroll Communication Error across the front panel
High Suction
Superheat
• Auxiliary Temperature Sensor Alarm indicates the sensor is short or Open
- The system will continue running and the controller will try and compensate for the issue.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- The controller will scroll High Superheat across the front panel
High Discharge
Pressure
• If the discharge pressure is above the Max Disch Pres (Maximum Discharge Pressure) for longer than the Max Dis Prs Del (Maximum
Discharge Pressure Delay)
- The system will continue running and the controller will try and compensate for the issue.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- The controller will scroll High Disch Pres across the front panel
Compressor
Module Alarm
• If a Digital Input is set to function as the Compressor Module (Comp Mod), the Compressor Module Alarm is activated when
the digital input receives an active signal, as determined by the Digital Input State.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- Across the front panel, the controller will scroll Comp Module*1 (for Digital Input 1), Comp Module*2 (for DI 2) or Comp
Module*3 (for DI 3)
Oil Pressure
Alarm
• If a Digital Input is set to function as the Oil Safety Switch (Oil Safety Sw), the Oil Pressure Alarm is activated when the digital
input receives an active signal, as determined by the Digital Input State.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- Across the front panel, the controller will scroll Oil Safety Alarm *1 (for Digital Input 1), Oil Safety Alarm *2 (for DI 2) or, Oil
Safety Alarm *3 (for DI 3)
High Pressure
Safety Switch is
Tripped
• If a Digital Input is set to function as the High Pressure Safety Switch, the High Pressure Safety Switch is Tripped Alarm is acti-
vated when the digital input receives an active signal, as determined by the Digital Input State.
- The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
- The Amber LED on the front Panel will be illuminated
- Across the front panel, the controller will scroll High Pres Safety *1 (for Digital Input 1), High Pres Safety *2 (for DI 2) or,
High Pres Safety *3 (for DI 3)

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 9
KE2 Compressor Sequencer
Quick Start Guide
Safety Features :
Alarm Name Description
Low Suction
Pressure Cut-Out
System is ON
• If System is On and the pressure goes below Cut Out Pressure setpoint, all compressor relays will be de-energized. The
controller will maintain current o state until pressure rises Suct Press Di above the Suction Pressure setpoint as long as the
Min Comp Otime has been satised
System is OFF
• The system may be turned o at any time by using one of three methods: Digital Input, Manual Menu, or Setpoints webpage.
After receiving the System O command the controller will turn o all but the largest capacity compressor. It will continue
to run until the pressure goes below Cut Out Pressure or Max Pump Out Time has been reached. If a Digital Scroll has been
selected it will always be the last compressor on. The controller will maintain current System O state until signal has been
removed and pressure rises Suct Press Di above the Suction Pressure setpoint as long as the Min Comp Otime has been
satised
Minimum
Safety Suction
Superheat
Stand Alone Operation
• The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
• The Amber LED on the front Panel will be illuminated
• The controller will scroll Min Safety Suc SH across the front panel
Utilizing KE2 Evaporator Eciency controllers
• The compressor sequencer will utilize the superheat of the KE2 Evap controllers with EEVs to assist in raising the superheat at
the rack using the following sequence:
- Every 5 minutes the Superheat Setpoint of each KE2 Evap controller will be increased 1 degree
- If the superheat is able to be maintained 2 degrees above the Min Safety Suc SH the compressor sequencer will lower the
superheat 1 degree every 5 minutes until the setpoint has returned to its original value.
- Once all of the KE2 Evap controllers have been returned to their original setpoint values and the superheat reading is main-
taining above the Min Safety Suction Superheat the alarm will be cleared.
• The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
• The Amber LED on the front Panel will be illuminated
• The controller will scroll Min Safety Suc SH across the front panel
Maximum Safety
Suction Temp
Stand Alone Operation
• The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
• The Amber LED on the front Panel will be illuminated
• The controller will scroll Max Safety Suc Tmp across the front panel
Utilizing KE2 Evaporator Eciency controllers
• The compressor sequencer will utilize the superheat of the KE2 Evap controllers with EEVs to assist in lowering the suction
temperature at the rack using the following sequence:
- Every 5 minutes the Superheat setpoint of each KE2 Evap controller will be lowered 1 degree
- If the temperature decreases the compressor sequencer will increase the superheat 1 degree every 5 minutes until the
setpoint has returned to within 2 degrees of its original value.
- Once all of the controllers have been returned to their original setpoint value and the suction temperature reading is main-
taining itself below the Max Safety Suction Temp the alarm will be cleared.
• The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
• The Amber LED on the front Panel will be illuminated
• The controller will scroll Min Safety Suc SH across the front panel
Maximum Safety
Pressure
If the discharge pressure is above the Max Safety Pressure for the time provided in the Max Dis Temp Delay:
• The controller will unload the next stage to attempt to reduce the pressure
- Wait the time dened by Min Comp Switch Time, then unload next stage
- Continue to unload until all stages are o
• The controller will send a notication to the email address or phone number provided in the Address for Alerts eld on the
Settings page of the controller.
• The Amber LED on the front Panel will be illuminated
• The controller will scroll Max Safety Pres across the front panel

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 10
KE2 Compressor Sequencer
Quick Start Guide
When applying the controller to a system consisting of xed speed
compressors with or without unloading capabilities, the controller
requires the user to assign a relay output for each compressor stage
available using the controller’s web pages. (Maximum Stages – 5)
Once the controller setup is completed through the controller’s Mas-
ter View web pages, it is ready to turn the System On, or allow Re-
frigeration, by either clicking the yellow System is O button on the
Setpoints web page, or using the Manual Menu -> Manual Control
option.
When Fixed Suction Pressure and Fixed Speed Compressors are se-
lected the controller will use the compressor capacity in HP as dened
on the Setpoints Page. Stages will be loaded and unloaded based on
the smallest step available. If all available stages are equal the con-
troller will automatically select the option with the least amount of
runtime.
The Suction Pressure Setpoint will serve as the target pressure the
controller works to achieve while in Refrigeration. The Suction Pres-
sure Dierential determines the pressure above and below the Suc-
tion Pressure Setpoint the controller will allow the suction pressure
to vary before it makes an adjustment to the compressor capacity.
Once a stage has been loaded or unloaded that stage must remain on
or o as determined by the Min Comp Runtime and Min Comp O-
time. Stages of capacity will be made as necessary by the controller,
however, it will not load or unload more often than the time dened
in the Min Compressor Switch Time.
If the system is maintaining the suction pressure within the normal
operating range, which is dened as the Suction Pressure Setpoint
+/- the Suction Pressure Dierential it will maintain the current
capacity.
Mode of Control: Fixed Suction Pressure & Fixed
Speed Compressors
Determining Compressor ON / OFF Order
Mode of Control: Fixed Suction Pressure with
Digital Scroll Compressors
When applying the controller to a system consisting of xed speed
compressors with or without unloading capabilities and one digital
scroll, the controller requires the user to assign a relay output for each
compressor stage available using the controller’s web pages.
Once the controller setup has been completed through the control-
ler’s Master View web pages, it is ready to turn the System On, or al-
low Refrigeration, by either clicking the yellow System is O button
on the Setpoints web page, or using the Manual Menu -> Manual
Control option.
The Digital Scroll will serve as the primary stage to provide the most
consistent suction pressure possible. Initially the compressor will be
started unloaded.
If the pressure rises above the Suction Pressure Setpoint plus the
Suction Pressure Dierential the Digital Scroll will be loaded by en-
ergizing the solenoid.
If the pressure falls below the Suction Pressure Setpoint minus the
Suction Pressure Dierential it will energize the solenoid to unload
the compressor. If the low pressure is maintained the main digital
scroll’s compressor relay will be de-energized if the Min Comp Run-
time has been met. *
If the Digital Scroll is fully loaded and the pressure exceeds the Suc-
tion Pressure Setpoint plus the Dierential the next stage will be
loaded based on the smallest step available. If all available stages are
equal, the controller will automatically select the option with the least
amount of runtime. The compressors will continue to be loaded until
all compressors are running.
If the pressure falls below Suction Pressure Setpoint minus the Suc-
tion Pressure Dierential the controller will rst unload the Digital
Scroll. The pressure will primarily be controlled by loading and un-
loading the Digital Scroll.
If that is not sucient to bring the pressure within the normal operat-
ing range, the controller will de-energize the smallest stage, or if all
available stages are equal, the controller will automatically select the
option with the most amount of runtime.
*The Digital Scroll’s requirements for unloading follow its own ruleset
that is not adjustable. It has been designed to be within the limits of the
compressor manufacturer, and to ensure that specication is maintained
the minimum times for transitioning are not adjustable.

Q.2.43 April 2018
Page 11
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer
Quick Start Guide
Digital Inputs Sequence
Digital Input Mode: Sets Digital Input Function (Complete Mode
descriptions on the table below)
Disabled
HG Def Required
2nd temp setpoint
2nd suction pressure set point
compressor module
oil safety switch
high pressure safety switch
system o
Digital Input Active State: Sets whether the Digital Input performs
the selected function (Digital Input Mode) when the input receives an
open or shorted signal.
Descriptions of Digital Input Mode Options
Disabled • Digital input is nonfunctional.
Hot Gas Defrost
Required
• If the Digital Input receives an Inactive signal the controller will de-energize the relay selected as Hot Gas Defrost
Relay.
• If the Digital input receives an Active signal the controller will energize the relay selected as Hot Gas Defrost Relay.
2nd Temp setpoint • If the Digital Input receives an Inactive signal the controller will control to Suction Pressure setpoint.
• If the Digital input receives an Active signal the controller will control to 2nd Suction Pressure set point.
2nd suction
pressure Setpoint
• If the Digital Input receives an Inactive signal the compressor module is running normally.
• If Digital Input is receiving an Active signal a compressor module is tripped with an alarm. The Amber LED will be
illuminated, and an e-mail will be sent.
• If multiple digital inputs are selected for compressor module, any compressor module input will control in manner
described above.
Compressor Module
• If the Digital Input receives an Inactive signal the compressor module is running normally.
• If Digital Input is receiving an Active signal a compressor module is tripped with an alarm. The Amber LED will be
illuminated, and an e-mail will be sent.
• If multiple digital inputs are selected for compressor module, any compressor module input will control in manner
described above
Oil Safety Switch
• If the Digital Input receives an Inactive signal the oil safety switch normal.
• If Digital Input is receiving an Active signal the oil safety switch is tripped with an alarm. The Amber LED will be
illuminated, and an e-mail will be sent.
• If multiple digital inputs are selected for Oil Safety Switch, any Oil Safety Switch input will control in manner de-
scribed above.
High Pressure
Safety Switch
• If the Digital Input receives an Inactive signal the High Pressure safety switch is running normally.
• If Digital Input is receiving an Active signal the High Pressure Safety Switch is in alarm. The Amber LED will be il-
luminated and an e-mail will be sent.
• If multiple digital inputs are selected for High Pressure Safety Switch, any High Pressure Safety Switch input will
control in manner described above.
System O • If the Digital Input receives an Inactive signal operate system normally.
• If Digital Input is receiving an Active signal the controller will go to System O Mode.
There are 3 Digital Inputs available. Each has 2 setpoints needed to congure its functionality.

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 12
KE2 Compressor Sequencer
Quick Start Guide
Menu
Parameters:
Manual Control
Clear Alarms
Factory Reset
Web Password Reset
KE2 Smart Access Mode
DHCP Mode
Menus: Variables Manual
(view only)
Non-adjustable
Suction pressure sensor alarm
Suction temperature sensor alarm
Discharge temperature sensor alarm
Discharge pressure sensor alarm
Auxiliary temperature sensor alarm
High suction superheat
Low suction superheat
Low discharge superheat
High discharge pressure
Compressor module alarm
Oil pressure alarm
Safety switch tripped
T2 Aux Sensor
Alarms
(view only)
Left and Right Arrows - use to move between Menus
Up Arrow and Down Arrow - scroll through Menu Parameters
ENTER
Press and hold ENTER for 3 seconds, when display begins
blinking changes can be made
BACK
Press BACK to return to the previous view.
ENTER
Press and hold ENTER for 3 seconds to save change
To change settings:
To save setting changes:
To move through
controller menus:
To return to Main Menu:
Indicator lights Red light - critical alarm (system is not running)
Amber/Yellow light - non-critical alarm (system running)
Green light - system is running
Suction pressure
Cap %
Compressor 1 relay
Compressor 2 relay
Compressor 3 relay
Compressor 4 relay
Compressor 5 relay
Superheat
T1 suction temp
Saturation Temp
Int Comp Temp
If T2 is Selected:
Disch Press
Disch Superheat
Disch Temp
Disch Sat Temp
Cap%
Dig 1 status
Dig 2 status
Dig 3 status
IP Octet 1
IP Octet 2
IP Octet 3
IP Octet 4
Subnet Mask Octet 1
Subnet Mask Octet 2
Subnet Mask Octet 3
Subnet Mask Octet 4
Firmware Version
ENTER
Press ENTER to go from parameter to value.
To toggle beween
description and value :
Suction Pressure
Cut Out Pressure
2nd Suction Pressure
Temp Units
Suc Press Di
Refrigerant
* All other Setpoints must
be accessed from the
controller’s webpage.
Setpoints* Enter
Password
thermsolutions
ENTER
BACK
Compressor
Sequencer
®
T2 Monitor
− or −
T2 Internal Comp Temp
Controller Navigation
Controller Navigation

Q.2.43 April 2018
Page 13
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer
Quick Start Guide
First line is the
function
Second line is the
current system
performance
For each
Displays number of
users currently
viewing this specific
controller’s webpage.
System alarms
and messages
are displayed.
DESCRIPTION:
Displays real time system information, and shows the interaction of multiple system conditions.
This screen looks at the system conditions, and can help with diagnostics, system performance, or
just oer peace of mind that the system is running properly.
Home Page
Appendix A
Webpages
Home Page

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 14
KE2 Compressor Sequencer
Quick Start Guide
Basic (Port 25)
KE2 Therm Default Server
Update firmware.
Refer to Q.5.6 KE2
Bootloader Guide.
Site and Password may be
changed by customer to create a
unique KE2 Smart Access login
Standard
SiteView MANAGER
Required to make changes to
Settings page. See page 15.
Remotely reboots
the controller.
Use to verify proper e-mail
configuration. Click Save button
(bottom right of page)
before testing
Removes all data
stored by controller.
Do not use unless
instructed to by KE2
Therm.
Resets controller’s
alarms and alarm
conditions.
Customer information is
displayed
Use to customize the
User Name and
Password from the
default setting.
The KE2 Smart Access Settings are
provided by KE2 Therm, and are only
needed when using KE2 Therm’s customer
portal for accessing the controller
Use to verify
proper API
configuration
User defines
controller location for
future access. KE2
Smart Access and
alarm notifications
Customer may input their
company information
Enter e-mail address
and subject for alerts.
DESCRIPTION:
The Settings page contains controller conguration for e-mail and web access.
It also allows installers to customize the MasterView with their company information. The Settings
page includes the buttons to update the controller, reset power to the controller, send a test
e-mail, clear data collected, and clear alarms.
Settings Page
Appendix A
Webpages
Settings Page

Appendix A
Webpages
Q.2.43 April 2018
Page 15
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer
Quick Start Guide
To make changes to the Settings page, Network page and Setpoints
page the User Name and Password must be provided.
The default User Name: ke2admin
The default Password: ke2admin
For security reasons, the User Name and Password should be
changed from the default. Once you are logged in, go to the
Settings page to change the User Name and Password.
DESCRIPTION:
The Login feature prevents unauthorized access to the controller.
The user must enter the password to make changes to the Settings page, Network page, and
Setpoints page.
Login Page
Login Page

Appendix A
Webpages
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 16
KE2 Compressor Sequencer
Quick Start Guide
IP Address may
be changed to
match the onsite
network. Typically
the subnet mask,
gateway and
primary DNS
should also be
changed.
Network settings may be
changed to match customer’s
environment.
IP address is Enabled or Disabled
Enabled - if selected IP is Dynamic
Disabled - if selected IP is Static
Prevents unauthorized access to the
controller. User must enter User
Name and Password to make
changes to the Network Setup page.
Saves changes to the
controller’s network.
DESCRIPTION:
Provides setup for adding controllers to an existing customer network.
Network Page
Network Page

Appendix A
Webpages
Q.2.43 April 2018
Page 17
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer
Quick Start Guide
Active when Open
(i.e. door open)
Active when Closed
Dig In 1, 2 or 3 Mode
Disabled
HG Defr Req
2nd Temp
2nd Pres
Comp Module
Oil Safety Sw
Hi Pres Switch
Sys Off
Digital Inputs
Relay 1
Dropdown Options
HG Defr Relay
LLS
Variable Speed
Unldr for Comp 2
Unldr for Comp 3
Unldr for Comp 4
Unldr for Comp 5
Relay 2 - 5
Dropdown Options
All Relay Options the
same as Relay 1,
except the list of
Unloaders for the
compressor never
includes the active
compressor.
R-404A
R-507
R-407A
R-407C
R-422A
R-422D
R-134a
R-22
R-717
R-438A
R-408A
R-409A
R-407F
R-410A
R-744
Fahrenheit
Celsius Disabled
T2 Monitor
T2 Room Temp
Int Comp Temp
DESCRIPTION:
Allows the user to setup the controller, and to customize the controller to meet specic
application needs.
The KE2 Compressor Sequencer begins in System O Mode. The user must congure relays and
refrigeration setpoints to ensure the system runs properly, then turn the system on.
Setpoints Page
Setpoints Page

Appendix A
Webpages
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 18
KE2 Compressor Sequencer
Quick Start Guide
The SiteView shows a
live view of each
controller’s perfor-
mance
When the controllers
are in the same
network, clicking on the
controller’s location will
open the webpage of
that controller.
Each member is
viewed by clicking on
the location name in
the SiteView Master’s
list.
The SiteView Master
may contain up to 49
members. All mem-
bers must be in the
same network. i.e. a
router divides a
network.
The SiteView may be
organized by logging
into the controller.
Air / Electric
Hot Gas
DESCRIPTION:
SiteView provides the ability to setup multiple controllers in the same network into defrost
groups to manage the concurrent defrost load by setting Capacity, Group, and Defrost
Type. If the user needs more detailed information, or to make adjustments, clicking on the name
of the controller, shown in the Location column, will open the Home Page of that controller.
Hot Gas must be selected for KE2 Compressor Sequencer to energize the Hot Gas Defrost Relay.
SiteView Page
SiteView Page

Q.2.43 April 2018
Page 19
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer
Quick Start Guide
Example:
5.460 Cap Load100 Suct Pres 11.4
Weekly view
Monthly view*
Current activity
Writes the data stored on the
controller to a CSV file.*
Date and Time are pulled
from the connected
computer.
5.460
Day, Capacity Load, and
Suction Pressure are
displayed when moving the
mouse over the data.
Days ago
DESCRIPTION:
The Graphing Snapshot shows the past seven days of Capacity Load and Suction Pressure
readings. It is an essential tool for system analysis and troubleshooting.
The experts at KE2 Technical Support can help troubleshoot your system using this information
Graphs Page
Appendix A
Webpages
Graphs Page

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.2.43 April 2018
Page 20
KE2 Compressor Sequencer
Quick Start Guide
KE2 Therm Solutions
12 Chamber Drive . Washington, MO 63090
1.888.337.3358 . www.ke2therm.com
Enter default information and click Log In button
Site: installer
Password: controller’s Mac Address (from sticker on back of
controller)
Enable KE2 Smart Access in the Setpoints menu
After the initial Introduction Mode setup, press the arrow
to get to Manual Menu.
Press
ENTER
and the controller will display Enter Password.
Press
ENTER
and (4) zeros will appear. Use the and
to enter 2222
Press and hold
ENTER
for 3 seconds.
Press until Smart Access Mode is displayed
Press
ENTER
and Disabled will be displayed.
Press & hold
ENTER
for 3 seconds. Red & Amber LEDs will
blink.
Press and Enabled will be displayed.
Press & hold
ENTER
for 3 seconds. Red & Amber LEDs will
stop blinking.
Go to smartaccess.ke2therm.net
Using your PC, tablet or smartphone, enter
http://smartaccess.ke2therm.net in the web browser’s
address bar.
KE2 Smart Access - Online Access In 3 Easy Steps
For additional information on KE2 Smart Access, visit:
http://ke2therm.com/literature/literature-ke2-smartaccess/
See Q.1.34 KE2 Smart Access Setup and Customizing and
A.5.89 Purchasing a KE2 Smart Access License.
Introduction to KE2 Smart Access
KE2 Smart Access provides quick and easy, real time access to your refrigera-
tion systems, 24/7
Now it’s easier than ever to monitor and adjust your KE2 Compressor Se-
quencer remotely. While the KE2 Compressor Sequencer’s free connectiv-
ity is still available, KE2 Therm recognizes that some customers prefer the
simplicity and convenience of KE2 Smart Access to enjoy the benefits of
the controller’s communication capability.
For a nominal monthly fee, KE2 Smart Access provides easy, real time ac-
cess to your refrigeration system 24/7. No port forwarding. No VPN.
All the KE2 Compressor Sequencer needs is a physical connection to the
network router. Once enabled, KE2 Smart Access quickly connects to your
personal web portal, hosted by KE2 Therm, and provides a “customized”
dashboard of all the controllers you setup with KE2 Smart Access.
Preliminary
Connect the KE2 Compressor Sequencer to the customer’s network.
CAT5 Ethernet
Cable
1 2 3 654 7
Link/ACT
100/1000Mbps
POWER
Customer Network
thermsolutions
ENTER
BACK
Compressor
Sequencer
®
Setup the controller by going to the
Setpoints page.
Screen shot of a single KE2 Compressor Sequencer connected through KE2 Smart Access.
Screen shots of KE2 Smart Access dashboard. Controller and system information is displayed for all of the
controllers on the portal.
Benets of KE2 Smart Access
KE2 Smart Access auto launches, and often eliminates costly IT support
Doesn’t require port forwarding or a vpn
Customized dashboard lets you view all your controllers on one page
It’s easier than ever to set up every controller you service to provide alarm
notications via text or e-mail
Easy setup of remote monitoring & system control
youtube.com/ke2therm
Visit our YouTube channel for videos on KE2 Smart Access.
Step 3
Step 2
Step 1
IP-10.10.52.19
MAC
00:04:A3:14:E5:92
IP-10.10.52.19
MAC
00:04:A3:14:E5:92
installer
Appendix B
KE2 Smart Access
Table of contents
Other KE2 Air Compressor manuals
Popular Air Compressor manuals by other brands

Sparmax
Sparmax AC-500 user manual

Quincy Compressor
Quincy Compressor DEFENDER 7-2716 SCFH Installation, operation & maintenance manual

NARDI COMPRESSORI
NARDI COMPRESSORI SANYAIR operating manual

Hyundai
Hyundai HYSC75300 manual

Gardner Denver
Gardner Denver VST110 Operating and service manual

Frascold
Frascold RTSL-30-120 Installation and start-up instructions