Keison Bibby Scientific Techne Afterburners AB-100 User manual

AB-100 & AB-500
Afterburners
OPERATOR'S MANUAL
Issue 3
5/08

CONTENTS
PAGE
INTRODUCTION 1
SPECIFICATION 3
OPERATOR SAFETY 4
GUARANTEE 4
CONTACT INFORMATION 5
INSTALLATION 6
COMMISSIONING 7
SETTING THE EXTRACTION SYSTEM 8
OPERATION 9
MAINTENANCE 9
FAULT FINDING 9
ILLUSTRATION OF AB-100 10
WIRING DIAGRAM 11

INTRODUCTION
The Techne Afterburners AB-100 & AB-500 are designed to reduce smoke emission from the exhaust gas
flue of certain sized techne fluidised bath cleaning systems. The Afterburner consists of a burner plate
mounted within a thermally insulated combustion chamber. The input to the combustion chamber is
designed to mate directly to a standard Techne extraction fan, while the output is suitable for connection
to an insulated exhaust stack.
The system is designed and built to comply with British Gas Council regulations, and has an approved
flame control unit, which monitors the flame via a flame probe.
The gas train consists of a pilot line pressure regulator, a control solenoid, a gas flow adjuster and a pilot
burner running in parallel with a main line pressure regulator, two control solenoid valves in series, a gas
flow adjuster, a maximum flow limiter and the main burner.
A safety interlock, in the form of a differential air pressure switch which monitors air flow across the
burner, inhibits operation of the burner upon loss of air flow.
The start up sequence for the burner is as follows:-
With the fume extraction fan running, and the Afterburner power switch in the ON position, (it is normal
practice to wire the electrical supply to the Afterburner via an auxiliary contact of the extraction fan motor
starter), after a pre-purge period of approximately 10 seconds both the ignition system and the pilot
solenoid valves are energised. Once the flame probe has detected that the pilot flame is correctly
established, the ignition system is switched off and the burner operates on the pilot flame only for a
period of approximately 15 seconds, after which the main solenoid valves are energised to establish the
main flame.
If the pilot flame is not established correctly during the start-up sequence, the lock out safety circuit
causes the burner to shut down to a safe position. Shut down will occur within 5-6 seconds, after the
initial release of gas.
The lock out lamp on the control panel will illuminate and the burner cannot be restarted until the START
switch has been depressed.
A compulsory minimum delay of 60 seconds is provided by the flame control system before the unit can
be re-started. This delay allows the Afterburner to be purged of any combustible gases which may be
present.
If during normal operation the gas burner flame is extinguished, the flame probe reacts instantly to the
loss of the flame. The solenoid valves are switched off immediately and after a delay period of
approximately 10 seconds, the ignition system and the pilot solenoid are energised in an attempt to
re-establish the flame in the normal manner.
If the re-light attempt is unsuccessful, the flame control system goes to a lock out state as described
above.
The Techne Afterburner system is one of several fume treatment components that may be used in
conjunction with Techne fluidised bath cleaning systems. The components selected will depend upon the
1

materials being treated and the working environment. A brief description of the components is as
follows:-
Cyclone assemblies to remove the majority of any fluidised medium that may become entrained in the
extracted fumes. The cyclone(s) are positioned in the exhaust ductwork directly after the fluidised bath
so that the fluidised medium is removed from the fumes before it contaminates other fume treatment
equipment.
A filter assembly to remove any fine particles of fluidised medium and any non-organic particles such as
paint pigments or fillers that may be present in the extracted fumes. The filter assembly is positioned in
the exhaust ductwork directly after the cyclone(s).
A liquid scrubber to remove any corrosive acids and other soluble noxious fumes (especially hydrochloric
acid and harmful by products of PVC and other halogenated polymers) from being emitted into the
atmosphere. The scrubber is positioned in the exhaust ductwork after the cyclone(s) (and filter if used),
but before the extraction fan.
An extraction fan to direct any fumes generated in the fluidised bath through the various fume treatment
components. The extraction fan is positioned in the exhaust ductwork after the cyclone(s) (and filter and
scrubber, if used), but before the Afterburner.
In addition, the exhaust ductwork should contain a damper valve to enable the rate of fume removal to
be adjusted according to system requirements. A dilution tee should be positioned between the fluidised
bath and the cyclone(s) to be optimised and to ensure that the oxygen content of the exhaust fumes is
sufficient to obtain stable combustion within the Afterburner.
The exhaust ductwork should be designed to have a minimal pressure drop and should be as short as
possible with the minimum of bends. Some polymers produce oil vapour when thermally decomposed,
these oils can condense on the walls of the ductwork where they combine with any particular matter and
may eventually block the ductwork or the cyclone(s). It is therefore important to ensure that the ductwork
can easily be dismantled for cleaning. In applications where the formation of oils cause serious ductwork
problems, the ductwork may be thermally insulated to reduce the level of condensation.
The exhaust stack from the outlet spigot of the Afterburner to atmosphere should be suitable for
operation with exhaust temperatures in the order of 450°C. A stainless steel lined double walled
insulation stack is suggested. The stack should be fitted with a weather-proof termination where it
terminates to atmosphere.
2

SPECIFICATION
AB-100
Overall external dimensions (approx) Height 2170mm
Width 740mm
Depth 880mm
Outlet spigot 203mm
Burner rating 3kW to 60kW
10,000BTU/hr to 200,000BTU/hr
Fuel consumption range
Natural gas 0.3m3/hr to 6m3/hr (10 to 200 ft3/hr)
Butane 0.1m3/hr to 2.6m3/hr (3 to 60 ft3/hr)
Propane 0.13m3/hr to 2.6m3/hr (4.5 to 90 ft3/hr)
Gas supply pressure
Natural gas 1.5kPa to 2.5kPa (6-10 inch WG)
Butane 2.5kPa to 3.5kPa (10-14 inch WG)
Propane 2.5kPa to 3.5kPa (10-14 inch WG)
AB-500
Overall external dimensions (approx) Height 2500mm
Width 1200mm
Depth 1000mm
Outlet spigot 305mm
Burner rating 6kW to 120kW
20,000 BTU/hr to 400,000 BTU/hr
Fuel consumption range
Natural gas 0.6m3/hr to 12m3/hr (20 to 400 ft3/hr)
Butane 0.2m3/hr to 4m3/hr (6 to 120 ft3/hr)
Propane 0.26m3/hr to 5.2m3/hr (9 to 180 ft3/hr)
Gas supply pressure
Natural gas 1.5kPa to 2.5kPa (6-10 inch WG)
Butane 2.5kPa to 3.5kPa (10-14 inch WG)
Propane 2.5kPa to 3.5kPa (10-14 inch WG)
Both Units
Exhaust gas temperature Typically 450°C
Electrical Supply 220/240V 1PH 50/60Hz
3

4
OPERATOR SAFETY
All users of Techne equipment must have available the relevant literature needed to ensure their safety.
It is important that only suitably trained personnel use this equipment, in accordance with the instructions
contained in this Operator's Manual and with general safety standards and procedures. If the equipment
is used in a manner not specified by Techne the protection provided by the equipment to the user may
be impaired.
The unit has been designed to conform to international safety specification.
GUARANTEE
This instrument is guaranteed against any defect in material or workmanship for a period as specified on
the enclosed guarantee card. This period is from the date of purchase, and within this period all defective
parts will be replaced free of charge provided that the defect is not the result of misuse, accident or
negligence. Servicing under this guarantee should be obtained from the supplier.
Notwithstanding the description and specification(s) of the units contained in the Operator's Manual and
Service Manual, Bibby Scientific Limited hereby reserves the right to make such changes as it shall see fit
to the units or to any component of the units. This Service Manual has been prepared solely for the
convenience of Bibby Scientific Limited customers and nothing in this Service manual shall be taken as a
warranty, condition or representation concerning the description, merchantability, fitness for the purpose
or otherwise of the units or the components.

6
INSTALLATION
Mount the Afterburner in a convenient position adjacent to the fluidised bath ensuring that sufficient
space is left around the Afterburner for access during maintenance. In particular access to the front of
the Afterburner is required to enable the burner plate to be removed for cleaning if required.
Connect the lower input spigot to the output of the fume extraction fan. The ductwork between the
output duct of the fluidised bath and the input to the extraction fan should be generally in line with
recommendations covered in the earlier General Description section of this manual.
Connect the output spigot to a suitable insulated exhaust stack directed to atmosphere (see General
Description section).
AB-100
Connect a suitably sized gas main to the 3/4" BSP input connection below the control/gas train console,
positioning a lockable manual shut-off valve close to the Afterburner to ensure safety during maintenance
periods, etc.
AB-100
Connect a suitably sized gas main to the 2" BSP input connection below the control/gas train console,
positioning a lockable manual shut-off valve close to the Afterburner to ensure safety during maintenance
periods, etc.
Connect a single phase electrical supply to the input terminals in the control cabinet, see rating plate for
details. The base of the control cabinet may be machined to accept suitable conduit. The electrical supply
to the Afterburner should be interlocked with the motor starter of the extraction fan (see General
Description and circuit diagram).
Connect the low pressure side of the differential air pressure switch (terminated at the rear of the
Afterburner) to the ducting just prior to the input of the extraction fan using 5/16" OD copper tubing or
a suitable alternative. The differential air pressure switch monitors the pressure drop across the extraction
fan in its normal working mode and is intended to switch off the Afterburner when the exhaust gas flow
ceases due to a blocked flue or seized fan impeller, etc.
Purge the gas supply line to the burner by removing the 1/8" BSP plug from the main gas train situated
between the pressure regulator and first main gas solenoid valve.
Remove the inspection panel containing the sight glass and ensure that the burner plate is clean and free
of any swarf or insulation material.

7
COMMISSIONING
With the extraction fan switched on and operating in the correct direction, ensure that the gas supply is
turned on at the remote manual shut off valve (if fitted in supply line), and that an input gas pressure of
greater than 6 inches is registered on the input gas pressure gauge.
With the main gas flow regulating valve (situated in the main gas line prior to the burner but within the
gas train console) in the OFF position, switch the power switch to the ON position.
The fan failure neon should be extinguished. If the neon is illuminated, check the operation of the
extraction fan and the connections between either side of the differential pressure switch and the
ductwork/base of the Afterburner. The operating position of the differential switch may be adjusted if
required by removing the yellow plastic plug on the side of the switch body and rotating, the internal
screw.
When the fan failure light is extinguished, the automatic start up sequence should commence, as detailed
in the General Description of this manual.
It is not common for the burner to initially fail to ignite due to the air within the gas supply line or an
incorrectly set pilot flame adjuster. If the flame control system goes into a lock-out mode, leave for
approximately 60 seconds with the power switch in the ON position before depressing the start button
to re-initiate the start up procedure.
The pilot light adjuster needs to be used either to establish a flame initially or to modify the flame.
Remove the end cap of the pilot light adjuster, situated above the main gas flow manual adjusting valve,
and adjust the internal screw. A pilot flame of sufficient size to successfully sustain the flame control
system in the ON position is needed.
Once the pilot flame has been successfully established and detected by the flame probe, the main gas
solenoid valves will be heard to open as they are energised.
The main gas flow limiter, or ballofix valve, adjacent to the main gas flow valve, should initially be set in
the fully open position.
Opening the main gas flow adjusting valve should establish the main burner flame. Adjustment to the
size of the flame and the setting of the gas flow limiter should be attempted during a cleaning cycle in
the fluidised bath. Under conditions where the maximum fumes are generated within the fluidised bath
the flame should be adjusted and may also be limited such that acceptable fume emission from the
exhaust stack is achieved.
Adjustable profile plates are situated either side of the burner plate within the combustion chamber.
These plates may be moved towards or away from the burner plate so as to achieve ideal contact
between the flame and the fumes being treated with the minimum pressure drop within the system.
Adjustments built into the ductwork system as described in the General Description section of this
manual allow the fume treatment system to be tuned according to system requirements. However,
adjustments tend to be interactive, the best results being usually obtained by trial and error.
The ducting damper valve may be used to reduce the overall extraction flow rate, which reduces the gas
consumption of the exhaust fumes. However, the fume extraction flow rate must be high enough to
entrain any fumes produced during the cleaning process.

The dilution tee may be used to ensure that the oxygen content of the exhaust is high enough to
maintain the burner flame during the smoke cycle. The dilution tee also enables the velocity in the
cyclone to be maintained at a suitable value to ensure efficient separation of any fluidising medium, while
the velocity in the fluidised bath exhaust duct may be limited to reduce the amount of fluidising medium
entrained.
A correctly adjusted system should result in a minimal loss of fluidising medium from the fluidised bath.
The majority of the entrained medium should be retained by the cyclone, from where it may be returned
to the bath. The fume concentration within the ducting should be below the LEL (lower explosion limit)
for the various products generated during the cleaning process. The exhaust emission from the
Afterburner outlet should be within locally acceptable limits. The environment adjacent to the fluidised
bath should have gas concentrations within locally accepted TLV (threshold limit values).
SETTING THE EXTRACTION SYSTEM
1. Switch on the extraction system setting the dampers initially as follows:
Dilution Tee 50%
Damper 50%
2. Heat up the bath to the working temperature, adjusting the air flow for correct fluidisation.
3. When at the working temperature, adjusting the damper so that any fine dust particles omitted
from the surface of the bath are just entrained by the extraction system.
4. Operate as above for 30 minutes.
5. Switch off the extraction system and check:
a. The amount of sand in the collector bin (cyclone)
b. The amount of sand in the duct
6. If there is more than 2" of sand in the bin ensure that fluidisation is not excessive and that the bath
was not overfilled. Tip the sand back into the bath.
7. If 6 is satisfactory check that the extraction rate is not excessive.
NOTE: IF A LID IS USED ON THE BATH, ENSURE THAT IT IS NOT AIRTIGHT
8. If there is sand in the Afterburner the velocity through the cyclone is incorrect. Therefore open the
dilution tee and increase damper so that system still just entrains fines. Re-check the system from 4.
9. Check the operation of the afterburner. Set the flame to maximum (gate valve fully open).
10. With the Afterburner running immerse slightly contaminated component.
11. Check fume extraction above the bath visibly ensuring all fumes are extracted
ie: Drager to check concentration. Check the Lower Explosive Limit.
12. Check the visible smoke from the stack, check the fume concentration is acceptable.
13. If the visible smoke is present or the fume concentration is too high decrease the smoke generation
rate, ie: reduce the temperature of the bath.
14. When 11 is satisfactory, immerse a maximum contamination item and re-check as 11.
15. Repeat 14 and decrease the flame size until conditions are just acceptable to minimise gas
consumption.
8

OPERATION
The Afterburner may be used either continuously during cleaning operations in the fluidised bath or, to
reduce the overall gas consumption, during the initial part of the cleaning cycle when visible fumes are
provided.
With the electrical and gas supplies to the Afterburner switched on, the burner may be initiated by
switching the power switch to the ON position. The automatic start-up sequence (as described in the
General Description section of this manual) will commence, and after the appropriate time delays the
main burner flame will ignite.
Should the system fail to ignite, or for some reason the burner flame be extinguished during operation,
the control system will go into lock-out state. A delay of approximately 60 seconds occurs in this state
before it is possible to recommence the start-up sequence by depressing the start button.
To stop the Afterburner at any time, switch the power switch to the OFF position.
MAINTENANCE
The following points should be checked as part of a regular maintenance routine. The period between
checks depends upon the types of materials being treated in the fluidised bath and the frequency at
which the system is used.
a. Check ignition electrode, clean and replace as necessary.
b. Check the condition of the burner plates, and clean if necessary.
Note: excessive deposits of fluidising medium on the burner plate are an indication of poor system
adjustment or incorrect maintenance of the cyclone.
c. Check the condition of the thermal insulation within the combustion chamber, damaged insulation
should be replaced before the outer casing of the Afterburner is subjected to high temperatures.
d. Check the condition of the flame probe, clean and replace as necessary.
e. Check the function of the flame control system.
FAULT FINDING
1. Burner will not start
a. Check for electrical supply at burner control terminal 9. This will prove air pressure switch is
operational.
b. Check that the control is not in the lock-out position.
2. Burner starts but control goes to lock-out
a. Check that gas supply is turned ON.
b. Check that flame sensing probe is correctly positioned and not shorting to earth.
c. Check ignition circuit is functioning correctly, ie: transformer or spark plug is not shorting to
earth.
9

10
Burner inspection panel
Burner
May be mounted separately
on wall
Flame safety control box
Ignition transformer
UV Flame detector
Ballofix control valve
Pressure gauge
Gate valve
Insulation
Pilot solenoid valve
Additional gas pressure
regulator required for propane
Manual gas shut-off valve
(supplied by customer)
Pilot gas pressure regulator
Main gas pressure regulator
Main gas safety shut-off valves
Exhaust
Ø200
Air flow detector
Inlet Ø100
Gas supply
(3/4" gas fitting)
AB 100

11

Thank you for reading this data sheet.
For pricing or for further information, please contact us at our UK Office, using the details
below.
UK Office
Keison Products,
P.O. Box 2124, Chelmsford, Essex, CM1 3UP, Engl nd.
Tel: +44 (0)330 088 0560
F x: +44 (0)1245 808399
Em il: s [email protected]
Please note - Product designs and specifications are sub ect to change without notice. The user is responsible for determining the
suitability of this product.
This manual suits for next models
1
Table of contents