KEPCO m Series User manual

991036 08/13/19
-
-
-
, mA
- Optional secondary sensor input
- Dual or multi point calibration for voltage & Current input
Configurable ON/OFF, P, PI, PD and PID control forms
- Auto-tune and Self-tune PID
- Manual/Automatic mode selection for control outputs
- Bumpless transfer
- Motorized valve control function
- Programmable heating, cooling and alarm functions for control
outputs
- 8 steps profile control ( Ramp & Soak ) function and start-hold stop by
using logic input module
- Remote set point function by using analog input modules
- Re-Transmission
mL-PIDC6 & mL-PIDC8 Universal Input PID Process
Controllers
-4 digits process (PV) and 4 digits process set (SV) display
- Universal process input(TC, RTD, mV Z, V Z Z)
Z Z
Detection of heater failure by using 0...5 AVCT input module
RS-485 serial communication with Modbus RTU protocol
PROCESS CONTROL UNITS
mL-PIDC6 & mL-PIDC8
Electrical Connections
SPECIFICATIONS:
Universal Input:
Measurement Range:
:
:
:
CONTROL
(TC) : L(DIN 43710) ,J , K , R , S , T , B , E ve N
(IEC584.1)(ITS90) ,C (ITS90)
(RTD): PT-100 (IEC751)(ITS90)
: mV, V, mA
Please refer to Table-1 for selection of input
type and scale.
Maximum 10 Ohm
Z
Process Inputs
Accuracy:
Cold Junction Compensation
Line Compensation
Sensor Break Protection:
Sampling Cycle
Input Filter :
Control Forms:
Universal input, TC, RTD, Voltage/Current
Thermocouple
Thermoresistance
Input
± 0,25% of full scale for thermocouple, thermoresistance
and voltage
Automatically ± 0.1°C/1°C.
Upscale
3 samples per second
0.0 to 900.0 seconds
Programmable ON / OFF, P, PI, PD or PID.
Z
OUTPUT
:5A@250V
-
-0/4...20 mA
V
Z
Standard Relay Output
ADDITIONAL INPUT
Extra Analog Input
(Programmable control or
alarm output) (Electrical Life : 100.000 Operation (Full Load))
Extra Relay Output
3A@250V Relay Output
Current Input
INDICATORS
Process Indicators :
mL-PIDC6 : 10.1 mm Red 4 digit LED Display
mL-PIDC8 : 13.2 mm Red 4 digit LED Display
Setpoint Indicators :
mL-PIDC6 & mL-PIDC8 : 8 mm Green 4 digit LED Display
LED Indicators : AT(Auto Tuning), SV(Set Value), Man(Manual
Operation),Auto(Auto Operation), O1/2/3 (Output status LEDs),°C,°F,
V, Ramp and Remote LEDs
Environmental Ratings and Physical Specifications
Installation:
Over Voltage Category:
Pollution Degree:
Fixed installation Category II
II
II, office or workplace, none conductive pollution
Operating Temperature:
Max. Operating Humidity (non-condensing)
Protection Class NEMA 4X (IP65 at front, IP20 at rear).
0...50°C
0-90%RH
Type-1 Enclosure Mounting
:
:
Mounting:
Weight:
mL-PIDC6 : (48 x 96mm, Depth: 86.5 mm) / (46 x 92mm)
mL-PIDC8 : (96 x 48mm, Depth: 86.5 mm) / (92 x 46mm)
Minimum Distance Between Panel Cut-Out Centers:
mL-PIDC6 : X=65mm, Y=129mm
mL-PIDC8 : X=129mm, Y=65mm
Dimensions / Panel Cut-Out:
Supply Voltage
100-240V 50/60 Hz (-%15;+%10) -6VAV
V
mL-PICD6 & mL-PIDC8 : 260 gr.
21 3456 7 98 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
TC
0to20mA
0to50mV
0to10V
MODULE-1 MODULE-2
Pt-100
5A@250V
OUTPUT-3
CNONC
CATII
Universal
ProcessInput
(TC,RTD, Voltage/Current)
SensororTransmitter
SupplyVoltage
Output-3
StandardRelayOutput
SupplyVoltageInput
100-240VAC (-15%;+10%)
50/60Hz -6VA
Additional
0/4-20mA
Input
Communication
Socket
24V ±10%
Max.50mA
Additional Relay
Form A
3A@250V
mLINE

2
DIMENSIONS
°C
°F
V
O1
O2
O3
AT SV
REMOTE
RAMP
MAN
AUTO
SET
Cut Out
mL-PIDC8
°C
O1
°F
O2
O3
REMOTE RAMP MAN AUTO
AT
SV
SET
Cut Out
mL-PIDC6
PANEL MOUNTING
1-
2-
Before mounting the device in
your panel, make sure that the
cut-out is of the right size.
Check front panel gasket
position
3-Insert the device through the
cutout. If the mounting clamps are
on the unit, remove them before
inserting the unit to the panel.
4-Insert the unit in the panel cut-out
from the front side.
5-Insert the mounting clamps to the
holes that are located on top and
bottom sides of the device and
tighten the fixing screws until the
unit is completely immobile within
the Panel

3
Adjustment of Process Set Value
Press menu
button
Change set value with
increment and
decrement buttons.
Press SET/OK button to accept
the new Set value.
Press menu button to
exit without saving Set value
Main Operation
Easy Access Diagram for Operator Parameters
Process Set Display
Run List:Selection of PID Tune and Operation Form
Auto-Self Tune Self Tune operation is performed, if the conditions are
realized when power on firstly. In normal operation, it controls the tune
conditions in selection which explained below. If any of the
conditions is realized, it performs the operation
Auto Tune
Auto Tune
AUTOMATIC TUNE SELECTION
Device does not do (Limit Cycle Tuning) operation
Device does (Limit Cycle Tuning) operation
TUNE SELECTIONBy selecting one of the methods below,
device can determine the PID parameters.
Self tune (Step Response Tuning) operation
Device operates according to the defined PID
Auto tune (Limit Cycle Tuning) operation
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET SET SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
Press menu button
for entering to the
operator parameters
section.
Main Operation Screen
Enter the password
with increment and
decrement buttons
Press
SET/OK
button
Operator Menu Entering Screen
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
Confirm the
password with
SET/OK
button
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Easy Access Diagram for Technician Parameters
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
Main Operation Screen O p e r a t o r m e n u entering screen
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
Press menu button Press menu
changing next
Button
Enter the password
with increment
and decrement
buttons
Press SET/OK
button Confirm the
password with
SET/OK button
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
SET
SET
SET
SET
SET
SET
SET
SV
REMOTE RAMP MAN AUTO
°C
V
O1
O2
O3 AT
°F
SV
REMOTE RAMP MAN AUTO
°C
°F
V
O1
O2
O3
AT
Set List: Set values
Proses Set (-1999,9999)Unit
Alarm-1 Set (-1999,9999)Unit
Alarm-2 Set (-1999,9999)Unit
Alarm-3 Set (-1999,9999)Unit
OPERATION FORM SELECTION
Automatic:The device automatically calculates the % output
Manual: % output rate can be controlled manually by using
direction buttons.
Ramp/Soak Control
Ramp/Soak function is deactivated
Ramp/Soak function is active
Ramp/Soak function is holding. Real time is stopped
MOTORIZED VALVE CONTROL
Motorized valve control is deactivated
Motorized valve runs with heating PID function.
Motorized valve runs with cooling PID function.
BUMPLESS TRANSFER
Process output value in manual control is not taken into consideration
while passing from manual control to automatic control. New control output
that is measured in automatic control is applied to process output. Last %
output value is taken output value of manual control and manual control
continues while passing from automatic control to manual control
Not1

4
ALARM LATCH CANCELING
Alarm latch canceling is not performed.
Display Function Selection for Top and Bottom Display
It defines the function of the top display.
This parameter determines which value is shown in top
display.
Process value (PV) is shown in top display
Result of subtraction of process set value from process
value (SV-PV) is shown in top display
It defines the function of the bottom display
This parameter determines which value is shown in bottom
display.
Process set value (SV) is shown in bottom display.
%Output value that is applied to process control output is
shown in bottom display.
Configure Process Input Type and Relevant Parameters with Process Input
Defines the process input
TC input type selection
RTDinput type selection
ZVoltage/Current input type selection.
Defines type and scale of the thermocouple for TC input. It
is active if TC input type is selected
L (-100°C;850°C) (-148°F;1562°F)or
L (-100.0°C;850.0°C) (-148.0°F;999.9°F)or
J (-200°C;900°C) (-328°F;1652°F)or
J (-199.9°C;900.0°C) (-199.9°F;999.9°F)or
K (-200°C;1300°C) (-328°F;2372°F)or
K (-199.9°C;999.9°C) (-199.9°F;999.9°F)or
R (0°C;1700°C) (32°F;3092°F)or
R (0.0°C;999.9°C) (32.0°F;999.9°F)or
S (0°C;1700°C) (32°F;3092°F)or
S (0.0°C;999.9°C) (32.0°F;999.9°F)or
T -200 4 - 8 75( °C; 00°C) ( 32 °F; 2°F)or
T ( °C; °C) ( °F; °F)-199.9 400.0 -199.9 752.0or
B (44°C;1800°C) (111°F;3272°F)or
B (44.0°C;999.9°C) (111.0°F ; 999.9°F)or
E 15 7 23 129 F)(- 0°C; 00°C) (- 8°F; 2°or
E ( 150.0°C;7 .0°C) ( 199.9°F;999.9°F)- 00 -or
N ( 200°C;13 °C) ( 328°F;2372°F)- 00 -or
N ( °C;999.9°C) ( °F;999.9°F)-199.9 -199.9or
C (0°C;2300°C) (32°F;3261°F)or
C (0.0°C;999.9°C) (32.0°F;999.9°F)or
Defines type and scale of sensor for RTD input. It is active if
RTD input
PT-100 ( -200°C ; 650°C ) or ( -328°F ; 1202°F)
PT-100 ( -199.9°C ; 650.0°C ) or ( -199.9°F ;999.9°F)
No point
Fixed dual point display adjustment. Display adjustment low
point value is fixed to -1999, display adjustment high point
value is fixed to 9999.
Between second and third digits “0.00”
User can do defined 16 display adjustment points.
Between third and fourth digits “0.000”
Between first and second digits “0.0”
User can do dual point display adjustment with tPoL and tPoH.
ZVoltage / Current Input Selection
This parameter is active if Voltage / Current isZselected.
0...50mV ( -1999 ; 9999 )Z
0...5V ( -1999 ; 9999 )Z
0...10V ( -1999 ; 9999 )Z
0...20mA ( -1999 ; 9999 )Z
4...20mA ( -1999 ; 9999 )Z
Display Point Position
This parameter is active if Voltage / Current is selected.Z
Display Value Adjustment Type
Low Point Display adjustment (-1999, 9999)Unit
Active if oltage / Current input is selected.ZV
High Point Display adjustment (-1999, 9999)Unit
Active if oltage / Current input is selected.ZV
Display adjustment points (-1999, 9999)Unit
For example :
This parameter is active if oltage / Current is selected.
In multi point display adjustment operation, defined scale is
divided into 16 adjustment points.
is (0-50 mV ) .
Z
Z
V
While passing from manual control to automatic control, last process
output value in manual control is accepted as first process output value in
automatic control and automatic control continues to run. Last % process
output value in automatic control is accepted as process output value of
manual control and manual control continues to run.
If there is an alarm output with latching and there is no
alarm status, latching operation will be finished by the
device. When it is finished, this parameter becomes
Automatically
If one of the analogue input modules is plugged in Module-1
or Module-2 socket, measured value from this module input
is shown in top display.
Status of the Ramp/Soak function is shown in bottom
Display.
If one of the analogue input modules is plugged in Module-1
or Module-2 socket, measured value from this module input
is shown in top display.
If CT input module (EMI-420) is plugged in Module-1 or
Module-2 socket, measured value from this module input is
shown in bottom display.
V
rmP SoA: Configuration of RAMP/SOAK Function and Step SET Values
Soft-Start parameter.
When the power is applied to the device,process value
reaches to the set value at the end of this time.
Ramp Soak Tolerance Parameter (%0;%50 Scale)
In Ramp/Soak operation,if process value is out of the
tolerance that is defined with this parameter,then time is
stopped.
Ramp/Soak program step selection parameter.
1.program 1-4 steps
2.program 5-8 steps
Steps between 1-8 is used as one program.
Ramp/Soak step set value.
For ramp operation ; process value reaches to step set values that are
defined with these parameters at the end of the time that are defined in
ramp time parameters. For soak operation ; process value is constant in
step set value that are defined in these parameters for time that are
defined in soak time parameters. Ramp/Soak step set values can be
adjusted from minimum value of set scale to maximum value of set
scale.
Ramp time for Ramp/Soak
Process value reaches to step set values at the end of the
time that are defined in these parameters.
Soak time for Ramp/SoakProcess value is constant in step
set value for time that are defined in these parameters.

5
Unit selection
Unit°C
Unit °F
Operating Scale Minimum Value
(Scale Low Point, Scale High Point)Unit
Used for Proportional band calculation and display blink.
Display offset for process value (Scale -10%, Scale
+10%)Unit This parameter value is added to the process value.
Unit is Voltage.Active if Voltage / Current input is selectedZ
No unit.Active if oltage / current input is selectedZV
Coefficient value (1.000, 9.999)
Process value is multiplied with this value.
Active if Voltage / Current input is selected.Z
mV Z
50
Po00 = 0
Po01
Po02
Po03
Po04
Po05
Po16
Po06
Po15
Po07
Po08
Po09
Po10
3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125
3.125 6.25 9.375 12.5 15.625 18.75 21.825 25 28.125 31.25 34.375 37.5 40.625 43.75 46.875
Po14
Po13
Po12
Po11
Process
Set value
0-50 mV range are divided into 16 egual parts. Every “Poxx” SET value is defined
50 / 16 = 3.125 mV range.
Z
Z
Filter Time (0.0, 900.0)Second
Defines filter time for display value.
Cold Junction Compensation
This parameter is active if process input is selected TC input.
Cold junction compensation is active.
Cold junction compensation is not active.
Operating Scale Maximum Value
(Scale Low Point, Scale High Point)Unit
Used for Proportional band calculation and display blink.
Scale: The difference, between high point and low point of the process
input type. Example: If tCSL = 2 (low point is -200, high point is 900),
then scale is 1100. If input type is Voltage/Current, then the scale is
difference between tPoH and tPoL parameters.
PID ConF: PID Configuration Parameters
PROPORTIONAL BAND (0.0, 999.9)%
If = 1000 °C, = 0 °C and = 50.0
then Proportional Band = ( - ) * / 100.0
Proportional Band = (1000-0)*50.0/100.0 = 500 °C
INTEGRAL TIME (0, 3600)Second
Can be changed by the user. After complated the tunning
correctly, integral time value changes automatically. If it is 0,
integral control is deactivated.
DERIVATIVE TIME (0.0, 999.9)Second
Can be changed by the user. After complated the tunning
correctly, integral time value changes automatically. If it is 0,
derivative control is deactivated.
CONTROL PERIOD TIME (1, 150)
Process output period time
Second
MINIMUM CONTROL OUTPUT (0.0, )%
Even as a result of the PID calculation device calculates the
%output value less than this parameter, heating or cooling
output is active minimum for OLL parameter.
MAXIMUM CONTROL OUTPUT ( , 100.0)%
Even as a result of the PID calculation device calculates the %
output value greater than this parameter, heating or cooling
output is active maximum for OUL parameter.
HEATING MINIMUM CONTROL OUTPUT TIME(0.0, )sec
Heating output can not be active less than this parameter.
Even if this parameter is 0, this parameter is accepted
50 msecs for security.
COOLING PROPORTIONAL BAND COEFFICIENT (0.0, 100.0)
If heating and cooling PID is used in a system, tune operation is
performed by heating output.Cooling proportional parameter is
calculated with heating proportional band value and coefficient(P-
CL = P-Ht * CCoE / 100.0)
COOLING PROPORTIONAL BAND ( 000.0% , 999.9% )
If
Proportional Band
Proportional Band
= 1000 °C, = 0 °C and = 50.0 ise
=( - ) * / 100.0
= (1000-0)*50.0/100.0 = 500 °C
COOLING INTEGRAL TIME (0000 sec, 3600 secs)
It can be changed by the user. When tune operation finishes,
it can be changed by the device. If it is 0, integral control
part does not perform.
COOLING DERIVATIVE TIME (000.0 sec, 999.9 secs)
It can be changed by the user. When tune operation finishes, it can be
changed by the device. If it is 0, derivative control part does not perform.
When tune operation finishes if this parameter is 0, it can not
be changed because derivative control part does not perform.
COOLING OUTPUT PERIOD TIME (1 sec, 150 secs)
It is control period of cooling output.
COOLING MINIMUM CONTROL OUTPUT( 0.0, )%
,100.0)%
It is % of cooling minimum output. If heating and cooling PID
control functions operate together, this parameter is not
considered. Even as a result of the cooling PID calculation device
calculates the output value less than this parameter, cooling
output is active minimumor OLLC parameter.
COOLING MAXIMUM CONTROL OUTPUT (
It is % of cooling maximum output.
Even as a result of the cooling PID calculation device
calculates the output value greater than this parameter,
cooling output is active maximum for OULC parameter.
COOLING MINIMUM CONTROL OUTPUT ( 0.0% , )
Cooling output can not be active less than this parameter.
Even if this parameter is 0, this parameter is accepted 50
msecs for security.
ANTI-RESET WINDUP 0-SCALE HIGH POINT( , )UNIT
*/ ( - )
While PID operation is running if
- <= process value <= +
condition is true, integral value is calculated. If the condition
is not true, integral value is not calculated and last
calculated integral value is used. If Ar Parameter is
selected , heating proportional band is used for
heating PID process instead of Ar Parameter and cooling
proportional band is used for cooling PID process instead of
Ar Parameter.
SET VALUE OFFSET
((- SCALE HIGH POINT / 2) , (SCALE HIGH POINT / 2) )Unit
+ is used as set value in PID calculations. This
parameter is used for shifting the proportional band.
PID OUTPUT OFFSET
(FOR HEATING PID 0.0, 100.0)%
(FOR COOLING PID -100.0, 0.0)%
(FOR HEATING & COOLING PID : -100.0, 100.0)%
This parameter is added to “Output %” which is calculated at
the end of the PID.
OUTPUT OFFSET RELATED TO PID SET
(FOR HEATING PID 0.0, 100.0)%
(FOR COOLING PID -100.0, 0.0)%
(FOR HEATING & COOLING PID : -100.0, 100.0)%
This parameter is added to the %process output that is
calculated at the end of the PID according to process set value
Process Value Low Point Adjustment Parameter
(For TC and RTD input scales)
It can be adjusted -50% to 50% of scale.
Process Value Up Point Adjustment Parameter
(For TC and RTD input scales)
It can be adjusted -50% to 50% of scale.

6
PROCESS VALUE STABILIZATION
(1, SCALE HIGH POINT)Unit
It is used for controlling if process value oscillates or not
when Parameter is or If;
condition is not true, then device start tunn operation
- <= Process Value <= +
SCALE LOW POINT :
SCALE HIGH POINT :
Minimum process input value in Pt-100
and Tc inputs. -1999 for fixed dual point display adjustment
used inputs, Scale low point is the lowest one from or
for selectable dual point display adjustment used inputs
lowest
display adjustment
Maximum process input value in Pt-100
and Tc inputs. 9999 for fixed dual point display adjustment used
inputs, Scale high point is the biggest one from or
for selectable dual point display adjustment used inputs
display adjustment
Scale low point is the one from or for multi
point used inputs
Scale high point is the biggest one from or for
multi point used inputs
PROPORTIONAL BAND SHIFTING
((- SCALE HIGH POINT / 2 ) , ( SCALE HIGH POINT / 2 ) )Unit
SENSOR BREAK OUTPUT VALUE
(FOR HEATING PID 0.0, 100.0)%
(FOR COOLING PID -100.0, 0.0)%
If cooling function is performed ;
Cooling process set value is calculated by adding set value
With parameter
Control form can be ON/OFF or PID.
If set value for heating = + ;
Then set value for cooling = + +
When sensor breaks, controlling of the process can continue
by entering %output value to parameter.
If this parameter 0.0, process control output does not perform
an output when sensor breaks.
ýoP1 ConF:MODULE-1 Configuration Parameters
These devices are equipped with a 0/4 to 20 mA analog
i input plugged into Module-1
Configuration of analog input module in Module-1socket.
TC input type selection. This must be selected if analog
input module in Module-1 socket is EMI-430.
PT-100 input type selection. This must be selected, if
analog input module in Module-1 socket is EMI-440.
Z Voltage / Current input type selection. This must be
selected since analog input module is in Module-1 socket.
Input Module Selection
MODULE-1 Z
Z
Voltage/Current
Voltage/Current
It is active if input type of Module-1 is selected
0...50mV Z( -1999 ; 9999 )
0...5V Z( -1999 ; 9999 )
0...10V Z( -1999 ; 9999 )
0...20mA Z( -1999 ; 9999 )
4...20mA Z( -1999 ; 9999 )
point position for display
.It is active if input type of Module-1 is selected ZVoltage /Current.
No point
000.0
00.00
0.000
Calibration type
.It is active if input type of Module-1 is selected ZVoltage /Current.
Fixed dual point calibration is performed. Minimum
value of calibration is -1999 and maximum value of
calibration is 9999.
Selectable dual point calibration is performed.
Defines minimum value for selectable dual point calibration.
.It is active if input type of Module-1 is selected ZVoltage /Current.
Defines maximum value for selectable dual point calibration.
.It is active if input type of Module-1 is selected ZVoltage /Current.
Unit selection
Unit is °C
Unit is °F
Unit is U.
No unit.
Minimum value of operating scale (Low Limit). It can be
changed according to analog input type and scale.
Maximum value of operating scale (High Limit). It can be
changed according to analog input type and scale
Display offset for value in analog input module. It can be
adjusted from -10% to +10% of scale. This value is added to
the process value.
It is filter time for input signal. It can be adjusted from 0.0 to
900.0
It determines if the measured value from analog input module in
Module-1 socket is used as Remote Set or not. This parameter is
visible if point position and unit parameters are same for process
input and analogue input module.
Measured value from analogue input module in Module-1
socket is used as process set value. User defined process
set value is not considered
Measured value from analogue input module in Module-1
socket is not used as process set value. User defined
process set value is considered

7
out3 ConF: Output-3 Configuration Parameters
Defines output function for Output-3
Heating
Cooling
Logic output
Defines control algorithm of Output-3.
It is active if output function of Output-3 is heating or cooling
ON/OFF control algorithm
PID control algorithm
Hysteresis value for OUT-3. It can be adjusted from 0% to
50% of defined scale. ( It is active if ON/OFF control is selected)
It determines operation form of hysteresis. ( It is active if
ON/OFF control is selected)
SV+ HYS/2 and SV- HYS/2
SV and SV+HYS or SV and SV-HYS
In ON/OFF operation, this time must be passed for the output to
be energised again. ( It is active if ON/OFF control is selected)
It determines logic output function of Output-3.
It is active if output function of Output-3 is Lout(Logicoutput)
Alarm output
Manual /Automatic data output
Sensor break alarm output
POutput is active when the process value is out of the band
which is defined with minimum value of operating scale
And maximum value of operating scale
Output indicates that Ramp/Soak function has finished
Sensor break alarm output for analogue input module in
Module-1or Module-2 socket. ( It is visible if one of analogue
input modules is plugged in Module-1 or Module-2 socket )
If process value is less than minimum value of operating scale
or for analogue input module in Module-1 or Module-2 socket
or greater than maximum value of operating scale or for
analogue input module in Module-1 or Module-2 socket,
process output becomes active.(This parameter is visible if
one of the analogue input modules is plugged in Module-1 or
Module-2 socket)
Measurement input selection for Output-3 alarm output.
This parameter is visible if Logic output function of Output-3 is
Alarm output and one of the analogue input modules is
plugged in Module-1 or Module-2 socket
Alarm output runs according to the process input
Alarm output runs according to the analogue input module
(2nd sensor input) in Module-1 or Module-2 socket.
It determines alarm
It is active if logic output function of Output-3
is alarm output.
Process high alarm
Process low alarm
Deviation high alarm.
Deviation low alarm.
Deviation band alarm.
Deviation range alarm
IsýtýcýArýzasýAlarmý. It is active if VCT input module is
plugged in Module-1 or Module-2 socket.
Alarm- 3 hysteresis value. (Scale 0% , scale 50%)Unit
It is active if logic output function of Output-3
Alarm on delay time(0, 9999)Seconds
It is active if logic output function of Module-1 is alarm output.
Alarm off delay time
When the value is than 9998, is seen on the display.
It means alarm latching output is selected. It is active if
logic output function of Output-3 is alarm output.
(0, 9998)Seconds
ýoP1 ConF: MODULE-2 Configuration Parameters
These devices are equipped with an additional Relay
iOutput plugged into Module-2socket.
Defines output function for Module-2
Heating
Cooling
Logic output
It is active if output function of Module-1 is heating or cooling.
ON/OFF
PID
Hysteresis value for OUT-2. It an be adjusted from 0% to 50%
of defined scale. ( It is active if ON/OFF control is selected. )
It determines operation form of hysteresis. ( ON/OFF )
SV + HYS/2 and SV - HYS/2
SV and SV+HYS or SV and SV-HYS
In ON/OFF operation, this time must be passed for the
output to be
logic output function of output module in Module-2
It is active if output function of Module-2 is Lout (Logic Output)
Alarm output
Manual /Automatic data output
Sensor break alarm output
Output is active when the process value is out of the band
which is defined with minimum value of operating scale
And maximum value of operating scale
Output indicates that Ramp/Soak function has finished
Sensor break alarm output for analog input module in
Module-1 socket. ( It is visible if one of analog input modules
is plugged in Module-1 socket )
If process value is less than minimum value of operating
scale for analogue input module in Module-2 socket
or greater than maximum value of operating scale for
analogue input module in Module-2 socket, process output
becomes active.(This parameter is visible if one of the analogue
input modules is plugged in Module-2 socket)
Measurement input selection for Module-2alarm output.
This parameter is visible if Logic output function of Module-2
is Alarm output and one of the analogue input modules is
plugged in Module-1 socket
Alarm output runs according to the process input.
Alarm output runs according to the analogue input module
(2nd sensor input) in Module-1 socket
MODULE-2 alarm
It determines alarm type. It is active if logic output function of
Module-1 is an alarm output.
Process high alarm
Process low alarm
Deviation high alarm
Deviation low alarm
Deviation band alarm.
Deviation range alarm
Heater failure alarm does not
apply on these devices
MODULE-2 Alarm- 2 hysteresis value.
It is active if logic output function of Module-2 is an alarm
output.
Alarm on delay time
It is active if logic output function of Module-2 is an alarm
output
(0, 9999)Seconds
Alarm off delay time
Alarm off delay time. It can be adjusted from 0000 to 9998
seconds.When the value is greater than 9998 , is
seen on the display. It means alarm latching output is
selected.
(0, 9998)Seconds
out 2
2
2
2
2
2
2
2
2
2
2

8
Alarm Types
Deviation high alarm
HYS
ON
OFF
Process
Set Process Set + Alarm Set
Alarm
Output
Process Value
HYS
ON
OFF
Process Set - Alarm Set
Alarm
Output
Deviation low alarm
Process Value
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation Band Alarm
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation Range Alarm
Process high alarm
HYS
ON
OFF
Alarm
Set
Alarm
Output
Process Value
Alarm Types
Process low alarm
HYS
ON
OFF
Alarm
Set
Alarm
Output
Process Value
Gen ConF: General Parameters
Minimum value for process set and alarm set values
Maximum value for process set and alarm set values
2. Sensor Set Point Low Limit .sensor scale min. )
2. Sensor Unit
Module-1 or Module-2 socket Analog Input Modules.
(If you have any of these parameters is observed)
2. Sensor Set Point Hýgh Limit .sensor scale min. )
2. Sensor Unit
Module-1 or Module-2 socket Analog Input Modules.
(If you have any of these parameters is observed)
While the motor is completely off the valve fully open
While the fully open or fully closed for the pass time required.
Value between 5 and 600 seconds can be entered.
(If motorized valve control is selected this parameter is active)
The minimum duration of the valve motor drive output (0.1, 5.0)%
Ultt = 100 sec and = %1.0 and the motor driving the
valve outlet. The minimum time to be active in 100 * 1.0%=1 sec.
(If motorized valve control is selected this parameter is active)
Com ConF: Parameters for Configuration of Serial Communication
Communication Accessing Address (1,247)
Communication accessing address of device. It can be
adjusted from 1 to 247.
Communication Baud Rate
1200 Baud Rate.
2400 Baud Rate .
4800 Baud Rate
9600 Baud Rate
19200 Baud Rate
Process Set

9
Failure Messages
1 - Sensor failure in analogue inputs. Sensor
connection is wrong or there is no sensor
connection.
4- If top display blinks : If analogue input
value is less than minimum value of
operating scale top display starts to
blink.
5- If top display blinks : If analogue input
value is greater than maximum value of
operating scale top display starts to
blink.
6- If operator or technician password is
different from “0” and user accesses to the
parameter by Set button without entering
the operator or technician password and
wants to change a parameter, the warning
message is shown on the bottom display
as shown on the left. Device does not
allow to do any changes without entering
the password correctly.
7- If tuning operation can not be completed
in 8 hours, AT led starts to blink.Blinking
can be canceled by pressing Enter button.
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
2- If parameter in “Disp List” menu is and
analogue input module is plugged in Module-
1 or Module-2 socket, this is sensor failure of
analogue input module. Sensor connection is
wrong or there is no sensor connection.
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
3-If parameter is and parameter is and
analogue input module is plugged in Module-
1 or Module-2 socket, this is sensor failure of
analogue input module. Sensor connection is
wrong or there is no sensor connection.
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
8-If user does not do anything for 120
seconds while device is on operator or
technician menus, device turns to
operation screen.
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
9- The device is powered up, the normal
does not begin to run, and the bottom of the
screenAs the side flashing;
Module-1 and Module-2 slots, EMIX10
EMI-X30, X40-EMI, EMI-X50 Analog input
modules installed at the same time the
event occurs. The unit normal to return to
work, the device energy cut-off and Analog
Input one of the modules must be removed.
10- When power is on ; not starting the
normal operation and blinking the bottom
display as shown on the left; It appears
when two analogue input modules ( EMI-
410, EMI-430,EMI-440, EMI-450 ) are
plugged in Module-1 and Module-2 socket
at the same time. For starting normal
operation power off and pull out one of the
analogue input modules.
Parity Selection for Communication
No parity.
Odd parity.
Even parity.
Stop Bit Selection for Communication
1 stop bit
2 stop bit
It is used for accessing to the technician parameters.
If it is no password protection while entering to the
technician Parameters.
f user does not enter password correctly It turns
to operation screen without accessing to parameters.
When in top display and in bottom display
are seen, if user presses SET button without entering
Password (For observing the parameters):
Operator can see operator menus and parameters but
operator can not change the parameters.
If it is different from “ 0” and user wants to access to
the technician parameters;
I :
:
1-
PASS ConF: Operator and Technician Passwords
Technician Passwords(0, 9999)
It is used for accessing to the operator parameters.
If it is no password protection while entering to
the operator Parameters.
If user does not enter password correctly It turns
to operation screen without accessing to parameters.
When in top display and in bottom
display are seen, if user presses SET button without entering
Password (For observing the parameters):
Operator can see operator menus and parameters but
operator can not change the parameters
If it is different from “ 0” and user wants to access to
the operator parameters;
;
:1-
2-
Operator Passwords (0, 9999)

10
Installation
cBefore beginning installation of this product, please
read the instruction manual and warnings below
carefully.
In package ,
- One piece unit
- Twopiece mounting clamp
- One piece instruction manual
A visual inspection of this product for possible damage occured during
shipment is recommended before installation. It is your responsibility to
ensure that qualified mechanical and electrical technicians install this
product.
If there is danger of serious accident resulting from a failure or defect in
this unit, power off the system and seperate the electrical connection of
the device from the system.
The unit is normally supplied without a power switch or a fuse. Use
power switch and fuse as required.
Be sure to use the rated power supply voltage to protect the unit
against damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric
shock and trouble with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering
with the unit may results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous
atmospheres.
During the equipment is putted in hole on the metal panel while
mechanical installation some metal burrs can cause injury on hands,
you must be careful.
Montage of the product on a system must be done with it’s own
fixing clamps. Do not do the montage of the device with
inappropriate fixing clamps. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not
specified in this instruction manual.
a
cThis symbol is used for safety warnings. User must pay
attention to these warnings.
i
This symbol is used to determine the dangerous
situations as a result of an electric shock. User must
pay attention to these warnings definitely.
This symbol is used to determine the important notes
about functions and usage of the device
Company Information:
Kessler-Ellis Products
10 Industrial Way East
Eatontown, NJ 07724
Phone: 800-631-2165 or 732-935-1320
Fax:
Email:
Web:
732-935-9344
www.kep.com • www.kepmline.com
Kessler-Ellis Products warrants that the equipment delivered is free
from defects in material and workmanship. This warranty is
provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and
responsibilities which are determined in warranty document and
instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized
personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene etc.). Use of these solvents can reduce the
mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
Warranty
Maintenance
Other Information
Ordering Information
Model Number
mL-PIDC6
Description
PID PROCESS CONTROLLER 48 X 96 1/8 DIN
100-240 VAC (-15%; +10%) 50/60Hz
Universal process input (TC, RTD, mV, V, mA) Additional 0/4 -
20 mA Input
RS-485 serial communication with Modbus RTU protocol
1 Form C Relay Alarm Output (5A @ 250VAC with Resistive
Load)
1 Form A Relay Control Output (3A @ 250VAC with Resistive
Load)
mLINE
mL-PIDC8
Description
PID PROCESS CONTROLLER 96 X48 1/8 DIN
100-240 VAC (-15%; +10%) 50/60Hz
Universal process input (TC, RTD, mV, V, mA) Additional 0/4 -
20 mA Input
RS-485 serial communication with Modbus RTU protocol
1 Form C Relay Alarm Output (5A @ 250VAC with Resistive
Load)
1 Form A Relay Control Output (3A @ 250VAC with Resistive
Load)
This manual suits for next models
2
Table of contents
Popular Control Unit manuals by other brands

Honeywell
Honeywell VQ400M Series Product handbook

Cooper Wiring Devices
Cooper Wiring Devices AD130 quick start guide

Kuhse
Kuhse KEA 291 NSTR operating instructions

TRAUSCH DYNAMICS
TRAUSCH DYNAMICS PoppetPLUS 2 installation guide

STATUS SCIENTIFIC CONTROLS
STATUS SCIENTIFIC CONTROLS LC Series Installation and Hardware Configuration Manual

Honeywell
Honeywell V4043A manual