Page 1-2 Kidde Remote Switch Installer Manual 26/10/2011
Attention!
Product must be installed by a qualified electrician in UK, in compliance with BS 7671
(IEE Wiring Regulations) or local Regulations if outside of UK.
Any CPC (earth) conductor in the supply cable should be terminated in the back box
and NOT connected to the circuit board.
lsolate mains supply before commencing work.
Function and Compatibility
This is a mains powered (230 vac) device for use with all Kidde hard wired smoke, heat
& CO alarms.
It is designed to control a single unit or an interlinked group of alarms and may be
connected at any part of the supply circuit where the interlink line is present.
It can be retrofitted into existing installations already equipped with Kidde alarms.
Test all interconnected Alarms
Hush unwanted alarms
Locate the initiating alarm in event of activation
Location
Ideally should be wall mounted at specified light switch height (eg to suit wheel chair
users), & is either recessed or surface mounted using any BESA standard single gang
mounting box.
These are available from all good electrical wholesalers.
Unit should be sited where the user can readily access the unit without exposing
themselves to undue risk in the event of a fire.
Escape routes and rooms leading to escape routes should provide a
safe and convenient location for both routine testing and emergency use.
Timer Set UD
Default setting is 15 minutes but you can choose which pre set time for Hush / Locate
facility is required, remove the jumper from the PCB to select 8 minutes, (times
approximate).
Connection - Isolate supply
Connections are to be made utilising 6243Y pvc/pvc insulated and sheathed cable,
minimum CSA 1.5mmz, (outside UK, use cables compliant with local Regulations).
Connect at the rear of any of the group of interlinked smoke\ heat alarms or at a suitable
junction box anywhere on the alarm circuit where there are line, neutral and interlink
conductors.
Connection is direct to the PCB, the terminal block is marked I (interlink), N (neutral) L
(line). Any CPC (earth) conductor must be made safe or terminated in the back box and
not connected to the PCB.
Fit switch plate to back box using M3.5 screws provided
Installer Manual for Kidde Remote Test_Hush_Locate Switch
Code: REMTH