Kingspan TMS300 MULTI-TANK CS Operating manual

kingspanenergymanagement.com
Smart Monitoring
TMS300 CS
Multi-Tank
User and
Installation
Manual
ENG

TMS300 CS Multi-Tank – User Manual
2
Contents
1. Specication
1.1. Dimensions
1.2. Electrical and environmental specication
1.3. Inputs
1.4. Outputs
1.5. Relay outputs
1.6. Connectivity
1.7. Sensor
1.8. Additional equipment
2. Safety precautions
3. Mounting
4. Operation manual
4.1. Tanks
4.2. Network
4.3. LCD contrast
4.4. LCD backlight ON/OFF
4.5. Buzzer ON/OFF
4.6. Webserver password
4.7. Default setting
4.8. 4-20 mA output
5. Web server connection
5.1. Network connection
5.2. Direct connection
5.3. Wi-Fi connection (USB Wi-Fi adapter required)
6. Conguring sensor and tank details
6.1. Channel wizard
6.2. Connectivity wizard
6.3. Relays
6.4. Setup summary
6.5. Real-time data
7. Software upgrade by USB cable
8. Wall mount template
4
4
4
4
4
4
5
5
5
6
7
9
10
10
10
11
11
11
11
11
12
12
12
13
14
14
15
16
17
17
18
19

· Tank levels via Local screen, embedded
webserver, App, online portal or emails
· Multi tank level measurement (wireless and
wired, up to 18 channels)
· Connectivity options via Local Network,
GSM (2G/3G) or Internet
· Volt free relay outputs for overl/leak/low level
alarms/sudden drop
· CE certicated
· Historical levels
· Levels (litres, percentage, mm)
· Alarms (sensor disconnection, leak, high and
low alarms, email alerts)
· Dry contact inputs, up to 6
Summary of features
3
TMS300 CS Multi-Tank – User Manual

1. Specication
1.1. Dimensions
4
· Width: 300 mm
· Height: 180 mm
· Depth: 100 mm
· Supply voltage: 110-240 V AC or 12-24 V DC
· Max input power: 24 VA
Note: The information supplied in this manual is for guidance only – no part of this may be used for
any agreement, whether express or implied, or to form any contract.
TMS300 CS Multi-Tank – User Manual
· Optional wireless module
- 433 MHz
- Compatible with Watchman®Sonic
transmitter family
· 6 channels, 4-20 mA with internal 12 V DC
power supply
- Compatible with any 4-20 mA sensor i.e.
relative pressure, ultrasonic etc.
· 4-20 mA output (only with RF module)
Note: The alarm relays are 2 contact arrangements which are isolated (volt-free). These relays may be
used to trigger an external bell, warning lamp or digital communicator (telephone dialler).
1.5. Relay outputs
1.4. Outputs
1.3. Inputs
· Operating temperature: 0˚C - 40˚C
· Relay’s max switching current: 5 A
1.2. Electrical and environmental specication

· TP Link Wi-Fi adapter· RF module
1.8. Additional equipment
1.5. Relay outputs
5
TMS300 CS Multi-Tank – User Manual
Number of relays
Contact mechanism
Max. switching voltage
Max switching current
Resistive load
2
DPCO
250 V AC, 220 V DC
5 A
CH1
+ - CH2
+ - CH3
+ - CH4
+ - CH5
+ - CH6
+ - 12-24 V DC
+ GND
Relay 1 Relay 2
· Connect Sensor
- GSM 2G/3G
- Internet (port forwarding required)
· Embedded Web Server
- direct connection via ethernet cable
- local network
- Internet (port forwarding required)
- Wi-Fi network (USB Wi-Fi adaptor required)
1.6. Connectivity
1.7. Sensor
· Any 4-20 mA sensor
· Watchman®Sonic - 003963
· Watchman®Sonic EU 004644
· Watchman®Sonic Alarm - 004030
· Watchman®Sonic Alarm EU 004645
· Watchman®Sonic Plus - 002893
· Watchman®Sonic Plus EU 007041
TMS300 is compatible with:
· Watchman®LT (24 V DC external power supply
required) – 026769
· Watchman®Sonic 4-20 mA waveguide - 019052
· Watchman®Sonic Waveguide EU - 019369
· Watchman®Alarm Waveguide EU - 019371
· 4-20 mA pressure sensor - 004035

2. Safety precautions
6
Installation
Note: This installation procedure is for guidance only, and its suitability should be veried by the installer.
The following safety precautions are strongly recommended:
· Before attempting to install and operate the unit, read the instruction and installation manual
carefully.
· Installation and any maintenance should only be carried out by suitably qualied personnel.
· It is recommended that the unit be connected to the mains supply via a suitably rated isolating switch.
Warning! When the unit is connected to the mains supply and the cover is open, the circuits at
mains voltage will be exposed. Therefore when installing the unit, ensure all required connections
(including battery connected, if included), are made and covers replaced before turning on the
mains supply. Ensure that all the connections made are secure. If any maintenance work e.g.
installing a new battery, is required ensure that the unit is isolated from the mains supply before
removing the cover. Never leave the unit unattended if the cover has been removed and the mains
supply is connected.
· Do not exceed unit ratings as shown on the ratings label.
· It is advisable to route mains cables away from low voltage or sensor cables.
Note: For viewing comfort, the unit should be positioned at eye level. The ideal operating temperature
of the unit is (0oC to +40oC). It is always good practice to keep electronic equipment away from cold,
heat and electrical plant, as extremes of temperature may reduce the lifetime of the device, and
heavy electrical loads, switches, relays or contactors too close to the device may cause electrical
and electro-magnetic interference when switched on or o.
TMS300 CS Multi-Tank – User Manual

3. Mounting
7
Panel mount (required panel mount kit)
· Cut a hole in the panel with the described
dimensions (page 20)
· Remove the Front Lid unscrewing two screws
· Disconnect the modules
· Separate the front cover by unscrewing two
screws
· Remove the required knock outs from Back Box
for the cables to pass through (always separate
front cover before removing the knock outs)
· Attach the Panelmount Seal, ensure that it is
on the right position
· Insert the Back Box into the panel cut out
· Attach the four panel mount xing clips
(supplied), to the four studs at either side of
the unit (page 20)
· Tighten the four Panelmount Fixing Screws
· Insert the cable glands
· Pass the cables through the glands
· Mount the Front Cover on the Back Box
· Insert the modules
· Connect the power supply cable and sensors
· Tighten the cable glands
· Mount the front lid
· Operating temperature: 0˚C - 40˚C
· Relay’s max switching current: 5 A
Wall mount
· Drill four holes in the wall, according to the
template and insert the wall plugs
· Remove the Front Lid by unscrewing two screws
· Disconnect the modules
· Separate the front cover by unscrewing two
screws
· Remove the required knock outs from Back Box
for the cables to pass through (always separate
front cover before removing the knock outs)
· Insert the cable glands
· Screw in the Back Box to the wall
· Pass the cables through the glands
· Mount the Front Cover on the Back Box
· Insert the modules
· Connect the power supply cable and sensors
· Tighten the cable glands
· Mount the front lid
TMS300 CS Multi-Tank – User Manual
Note: This device should be properly earthed. Flexible wires simplify connection to the terminals.
All connections should be secure and adequately tightened. It is good practice to keep mains cables
away from sensor cables and other low voltage signal cables.
· Supply voltage: 110-240 V AC or 12-24 V DC
· Max input power: 24 V A

3. Mounting
8
TMS300 CS Multi-Tank – User Manual
Template - page 20

4. Operation manual
9
TMS300 CS Multi-Tank – User Manual
In order to fully understand the operation
of the unit, this section should be read carefully.
Power ON/OFF indicator
Alarm Triggered Indicator
Max. Volume Alarm Hard
Max. Volume Alarm Soft (blinking icon)
Min. Volume Alarm Hard
Min. Volume Alarm Soft (blinking icon)
LAN cable connected and IP obtained
GSM/GPRS signal strength
Buzzer OFF/Alarm muted
Channel OFF
Sensor disconnection

4. Operation manual
TMS300 CS Multi-Tank – User Manual
To set Automatic Network Conguration, use
the key to select DHCP and use the
key to select or deselect this option.
Indicates that the DHCP is OFF.
Indicates that the DHCP is ON.
Select and use the key to save the
settings.
It can take few minutes to save new settings.
To obtain the IP address please contact with
your Network Administrator.
This screen allows user to adjust the LCD contrast.
Use to adjust and press the key
to conrm.
Main menu
This screen allows user to choose any options
available.
To back to Main menu press the key.
These screens allow user to view all the sensor
status for each channel, e.g. Level, Disconnection,
Alarms.
Press the key to reveal the channel view,
use or to change between channels.
This screen allows user to set up the Network
connection. User can choose DHCP option
or manually enter the IP address.
OK
OK
OK
ESC
OK
4.1. Tanks
4.2. Network
4.3. LCD contrast
10

4.4. LCD backlight
ON/OFF
11
TMS300 CS Multi-Tank – User Manual
This screen allows user to reset the webserver
‘admin’ account password.
Use to choose the password and
press key to conrm.
To change the password, user will need to
conrm the old one. Default password is:
last 4 digits of unit serial number.
This option will reset all settings to the factory
settings. Password: Unit serial number.
Use to choose the channel and press
the key to confrm.
This screen allows user to switch ON/OFF ‘auto
backlight’ option.
Use to choose the option and press
the key to conrm.
Backlight will stay ON all the time.
Backlight will switch OFF automatically
in approx. 2 minutes if no key has been
pressed.
This screen allows user to switch ON/OFF internal
buzzer sound.
Use to choose the option and press
the key to conrm.
To mute the internal buzzer when alarm
activated press any key.
OK
OK
OK
OK
4.5. Buzzer ON/OFF
4.7. Default setting
4.8. 4-20 mA output
4.6. Webserver
password

5. Web server connection
To connect with unit’s embedded Web Server,
connect unit to the network (switch, hub,
router etc.) using Ethernet CAT-5 cable
or directly to the network adapter on your
computer and open a web browser - Windows
Internet Explorer (version 8.0 or higher)
or Firefox. Input the unit’s IP address (default
-192.168.0.2).
(please contact with your network administrator)
Internet - port forwarding required
12
TMS300 CS Multi-Tank – User Manual
Router
Computer Laptop
Internet
Laptop
· Check the MTMS network settings.
Use the keypad and navigate to the appropriate
screen MAIN MENU NETWORK
Note: The network setting may vary between devices.
· Connect MTMS to the computer using
Ethernet cable.
· Change the computer’s network settings.
5.2. Direct connection
5.1. Network
connection

13
Note: The last octet of the computer’s IP address
(“60” in this example) should be dierent than
the last octet of the MTMS IP address (“57”
in this example). The subnet mask and default
gateway should be identical.
Default username and password:
Administrator:
Username: admin
Password: last 4 digits of the units serial number
This password can be changed, see page 11.
User: (only for viewing levels)
Username: user
Password: last 4 digits of the units serial number
This password cannot be changed.
The USB Wi-Fi adaptor lets you create a WiFi
network from a unit to allow connection with
webserver on all of your wireless devices including
tablets, laptops / Ultrabooks and smartphones.
TMS300 CS Multi-Tank – User Manual
5.2. Direct connection
Laptop
5.3. Wi-Fi connection
(USB Wi-Fi
adapter required)

6. Conguring sensor and tank details
6.1. Channel wizard
14
This screen allows user to congure sensor and
tank details.
STEP 1
Choose the channel, set name and click NEXT.
STEP 2
Choose the sensor, ll in the required informations
and click NEXT.
Watchman®Sonic avaiable only with RF module
· 4-20 mA Pressure Sensor
· 4-20 mA Waveguide (Watchman®Sonic)
Enter the Sonic Height.
Sonic Height - distance between the base
of sensor to bottom of the tank.
· 4-20 mA utrasonic sensor
· Watchman®Sonic (only with RF module)
Enter the Sonic Height.
Sonic Height - distance between the base
of sensor to bottom of the tank.
· Dry contact
STEP 3
Choose the tank shape and ll in dimensions.
Click ‘Calculate’ to obtain tank capacity or type
in manually.
To add the strapping table, choose Irregular tank
and click ‘Next’ Fill in the table or upload le with
existing strapping table.
TMS300 CS Multi-Tank – User Manual

STEP 4
Set the alarm thresholds.
STEP 5
Check the actual reading from sensor and click
‘FINISH’ to apply settings.
15
TMS300 CS Multi-Tank – User Manual
6.1. Channel wizard
This screen allows user to connect to remote server.
· GSM - Kingspan SIM CARD
For SIM CARD activation please contact
Customer Service.
Click on ‘Send registration le to connect
sensor’ and wait for ‘SUCCESS’.
Warning! When success, FINISH button must be
clicked to save the settings!
6.2. Connectivity
wizard

16
TMS300 CS Multi-Tank – User Manual
· GSM - 3rd PARTY SIM CARD
For connection using 3rd party SIM CARD.
Enter the APN details from your SIM CARD
provider.
Please wait for GPRS reg: OK and then click
TEST button. Test results will be displayed in few
minutes.
If Success, click FINISH. Do not proceed if the
test has failed as this will not allow to register
on Connect Sensor.
· INTERNET (port forwarding required, please
contact with your Network Administrator).
6.2. Connectivity wizard
Clik TEST button. Test results will be displayed in
few minutes.
If Success, click FINISH. Do not proceed if the
test has failed as this will not allow to register
on Connect Sensor.
This screen allows user to associate any channel
with a number of relay outputs, (i.e. alarm relays)
e.g. if channel 1 goes into alarm mode, each
alarm associated with channel 1 will be triggered.
6.3. Relays

17
This screen allows user to view all the settings for
each channel, e.g. tank details, relays etc.
This screen allows user to view all the data from
the channels.
TMS300 CS Multi-Tank – User Manual
6.4. Setup summary
6.5. Real-time data

7. Software upgrade
by USB cable
18
STEP 1
Switch OFF the power supply.
STEP 2
Take o the front lid and switch the battery
backup o.
STEP 3
Press and hold the “OK” button.
STEP 4
Connect the unit to PC via male-male USB cable.
STEP 5
Wait few seconds and release the button.
STEP 6
The unit should enumerate as a “BOOTLOADER”
USB Mass Storage.
STEP 7
Open the “BOOTLOADER” folder and drag-n-drop
the s19 le.
STEP 8
After copying le has been completed, disconnect
the cable.
STEP 9
Switch the battery backup ON.
STEP 10
Close the lid and switch the power ON.
TMS300 CS Multi-Tank – User Manual
ON
Battery switch
OFF Mains
Fuse 1A
Warning: Always disconnect power supply from the unit before opening the lid.

8. Wall mount template
19
Wall mount template on the next page has dimensions of 296x169 mm.
It represents in 1:1 scale the area required to be cut out for panel mount.
The four studs at the corners are showing the exact position of the four panel mount xing clips.
TMS300 CS Multi-Tank – User Manual

21
Other manuals for TMS300 MULTI-TANK CS
1
Table of contents
Popular Control Unit manuals by other brands

Vimar
Vimar BY-ALARM PLUS quick start guide

Texas Instruments
Texas Instruments BOOSTXL-TPS652170 user guide

ShangHai Sunray Technology Co.,Ltd
ShangHai Sunray Technology Co.,Ltd SRWF-8009G user manual

Pilz
Pilz PNOZ m0p operating instructions

NXP Semiconductors
NXP Semiconductors TDA8920 quick start guide

CKD
CKD USB2 Series instruction manual

TriangleTube
TriangleTube INSRKIT06 manual

TGW
TGW CRUZCONTROL GENERATION 2 FOR NBC Installation, operation & maintenance manual

Nice
Nice FGR-223 instruction manual

Exar
Exar XR77XXEVB-XCM-V80 manual

Blackrock Microsystems
Blackrock Microsystems CerePlex m Instructions for use

Keithley
Keithley 7054 instruction manual