Kipor KP310V1.0 User manual

KP310V1.0 Controller
Operation Manual
VA
RModel KP310V1.0
V
O
RUN
VA
RModel KP310V1.0
V
O
RUN
www.kipor.com
Version No.:KP310.1.1.0
July 20th, 2011

KP310V1.0 Controller Operation Manual
I
Index
1.Brief Introduction................................................................................................................. - 1 -
2.Model Nomenclature Explained .......................................................................................... - 1 -
3.Performance and Features.................................................................................................... - 1 -
4.Specifications....................................................................................................................... - 2 -
5.Operation.............................................................................................................................. - 3 -
5.1 Function of keys............................................................................................................. - 3 -
5.2 Controller Layout...........................................................................................................-5 -
5.2.1 Main Display....................................................................................................... - 6 -
5.2.2 “Parameters Set” menu ....................................................................................... - 9 -
5.3 Manual Operation ........................................................................................................ - 10 -
5.4 Remote Operation ........................................................................................................ - 11 -
6.Protection ........................................................................................................................... - 11 -
6.1 Alarm............................................................................................................................ - 12 -
6.2 Time delayed stop alarms............................................................................................. - 12 -
6.3 Emergency stop alarms ................................................................................................ - 13 -
7.Wiring ................................................................................................................................ - 14 -
8.Parameter Set ..................................................................................................................... - 15 -
8.1 Parameters Set list........................................................................................................ - 16 -
8.2 Programmable output list ............................................................................................. - 21 -
8.2.1 Remote set......................................................................................................... - 21 -
8.2.2 Set Input ............................................................................................................ - 22 -
8.3 Programmable output list ............................................................................................. - 23 -
9.Commission ....................................................................................................................... - 24 -
10.Applications ............................................................................................................... - 24 -
11.Installations ................................................................................................................ - 25 -
12.Trouble shooting ........................................................................................................ - 26 -
13.Serial Communication................................................................................................ - 26 -
13.1 Physical Layer of Communication Protocol .............................................................. - 27 -
13.2 Enquiry/ Response Period.......................................................................................... - 27 -
13.3 Comm RTU ................................................................................................................ - 28 -
13.3.1 Address field ................................................................................................... - 28 -
13.3.2 Function field .................................................................................................. - 28 -
13.3.3 Data field......................................................................................................... - 28 -
13.3.4 Data CRC field................................................................................................ - 28 -
Appendix 1 CRC16-CCITT Sheet ............................................................................................. - 29 -
Appendix 2 CRC16-CCITT ....................................................................................................... - 30 -
Appendix 3 Wiring Diagram...................................................................................................... - 31 -
1)3-Phase 4-Line ........................................................................................................... - 31 -
2)3-Phase 3-Line ........................................................................................................... - 32 -
3)1-Phase 2-Line ........................................................................................................... - 33 -
4)2-Phase 3-Line ........................................................................................................... - 34 -

KP310V1.0 Controller Operation Manual
- 1 -
1. Brief Introduction
The KP310V1.0 controller has the function of manual/remote start and stop genset, data
measurement, alarm and protection. The KP310V1.0 can display detailed genset running and
alarming data through LED digit display in five numbers. RS232 interface with the host computer,
can start, stop genset and display real-time running data through the host computer. The host
computer software has the Chinese and English interface, featured by simple & reliable operation.
RS485 interface is also available for remote monitor and control genset.
2. Model Nomenclature Explained
KP310V1.0
KP310V1.0 KIPOR
KP310V1.0 Controller Model
KP310V1.0 Ve rs i o n No .
3. Performance and Features
Main features:
☞Microprocessor controller, higher hardware integration, higher reliable;
☞Display through LED display in five digital numbers; convenient to test genset by touch
buttons;
☞Manual/remote start and stop genset;
☞RS232 interface with PC to run and monitor genset; RS485 interface to remote monitor genset;
☞Applied to 3-phase 4-line, 3-phase 3-line, 1-phase 2-line, double-voltage power sources;
☞Monitor and display three-phase voltage, three-phase current, frequency, revolutions and
battery voltage;
☞Fault alarms, including over-voltage, under-voltage, over-frequency, under-frequency and
charging fault;
☞Protection against high water temperature and low oil voltage;
☞All output interface are relay output;
☞“Parameters Set” menu: parameters can be set by users through controllers or PC. All
parameter are stored in internal flash memory so they won’t lose even the power turns off;
☞Working voltage: 8-16VDC, adaptable to different batteries;
☞Maintenance remind function (fuel filter, air filter, oil filter) ;
☞Digital control, more reliable;
☞Fault alarms are recorded until manual delete;
☞Copy system configuration and restore system configuration, assure system can be restored due
to wrong action;

KP310V1.0 Controller Operation Manual
- 2 -
☞ Modular structure, flame-retardant ABS shell, pluggable terminals, embedded installation,
compact structure and easy installation
4. Specifications
Working Voltage 12VDC (8~16VDC)
AC Input Voltage:
Phase voltage 10~290VAC RMS
Precision level:2.0
Voltage measurement
Three-phase four-line
Three-phase three-line
Single-phase two-line
Double-voltage output simultaneously
Double-voltage output alternative
Primary current:
1A -900A (Parameters Set)
Secondary current:
5mA
Current measurement
Precision level:
2.0
Frequency range:
20~70HZ(voltage>15V)
Frequency measurement
Precision level:
0.5
Voltage range:
5-50V
Max. frequency:
10000Hz
Revolution measurement
Flywheel tooth:
1-500
Fuel output relay:
15A/12VDC
Start output relay:
15A/12VDC
Preheat output relay:
5A/12VDC
Configuration output relay Ⅰ:
5A/12VDC
Output
Configuration output relay Ⅱ:
5A/12VDC
Ambient temperature -20~70℃

KP310V1.0 Controller Operation Manual
- 3 -
5. Operation
5.1 Function of keys
Stop/Reset
Genset is running, press to stop genset, when genset is in
alarming status, press to reset.
In “System Set”mode, press to return to the previous
sub-menu.
Manu/ATS
Press to set genset in “Manual” Mode.
In “System Set” mode, press to decrease the data value, equal
to “-”.
Remote
Control
Press to set genset in remote control mode.
In “System Set” mode, press to increase the data value,
equal to “+”.
Start In ““Manual” Mode, press can start genset.
Parameters Set Press to enter “Parameters Set” selection menu.
Note:
1 when the generator is stopped and in “Manual” Mode, press and for 5 seconds at
the same time, it displays password “Test” mode . If user doesn’t input the right
password in 60 seconds, the system will automatically exit password menu and enters System
Operation menu.
2 In “Parameters Set” menu, press , and for 5 seconds in the same time to
backup current system set, and the digital tube displays “Backup” for 2 seconds.
3 When genset is stopped, and in “Manual” Mode, press , and for 5secs to
restore system set, and the digital tube displays “Reset” for 2 seconds.
4 In the “Oil Filter Running Time” mode, press for 5 seconds, it will clear alarm of oil filter

KP310V1.0 Controller Operation Manual
- 4 -
maintenance, and reset it.
5 In the “Fuel Filter Running Time” mode, press for 5 seconds, it will clear alarm of fuel
filter maintenance, and reset it.
6 In the “Air Filter Running Time” mode, press for 5 seconds, it will clear alarm of air filter
maintenance, and reset it.
7 In the “Running Time” mode, press for 5 seconds, it will clear running time, and reset it.
8 Press and for 5 seconds until the signal twinkles, which shows that system has
blocked some protection functions (over/under frequency, over/under voltage); then press
and for 5 seconds until the signal stop flickering, which shows that system has restored the
protection functions (over/under frequency, over/under voltage).

KP310V1.0 Controller Operation Manual
- 5 -
5.2 Controller Layout
VA
RModel KP310V1.0
V
O
RUN
VA
RModel KP310V1.0
V
O
RUN
Voltage Current Frequency Revolutions Battery
voltage
Running
time
Maintenance
time
Run Low Oil
Pressure
High Water
Temperature
Starting
Failure
Emergency
Stop
Frequency
High/Low
Voltage
High/Low
Current
High/Low
Maintenance Charge
Failure
Stop Manual Remote Start

KP310V1.0 Controller Operation Manual
- 6 -
5.2.1 Main Display
Press , it will display voltage, current, frequency, revolution, battery voltage, run time and
maintenance time.
Note:
Battery charging voltage, switch value input/output state and system delay state is also available
with RS232 Port.
5.2.1.1 LED Status Indication
Genset status and working mode will be displayed in LED Panel.
When genset is stopped, will be lit up.
When genset is in “Manual” Mode, will be lit up.
When genset is in remote control mode, will be lit up.
5.2.1.2 Digital tube Status Indication
If genset switches to the following status, the digital tube will display genset status:
Preheat:
Start:
Starting idle:
Stopping idle:
Stopping delay:

KP310V1.0 Controller Operation Manual
- 7 -
Press to display running parameter, which shows as following:
Voltage
Three-phase four-line
Three-phase three-line
Single-phase two-line
Two-phase three-line
Double-voltage output alternative
120V output equals to single-phase two-line
240V output equals to two-phase three-line
Current
Three-phase four-line

KP310V1.0 Controller Operation Manual
- 8 -
Three-phase three-line
Single-phase two-line
Two-phase three-line
Double-voltage output alternative
120V output equals to single-phase two-line
240V output equals to two-phase three-line
Frequency
Revolution
✪Note: If the “Revolution low” is set as zero, then the speed won’t be displayed..
Battery voltage
Running time
Maintenance Time
Oil filter
Fuel filter

KP310V1.0 Controller Operation Manual
- 9 -
Air filter
5.2.2 “Parameters Set” menu
The followings parameters are included in “Parameters Set” menu:
★NUMBER OF ENGINE FLYWHEEL
★TRIPPING SPEED
★TRIPPING FREQUENCY
★TRIPPING CHARGING VOLTAGE
★START TIMES
★TRIPPING OIL PRESSURE DELAY
★MAX. STARTING TIME
★UNDER SPEED
★OVER SPEED
★FAULT DELAY OF UNDER SPEED
★FAULT DELAY OF OVER SPEED
★DELAY TIME FROM STOP TO STANDBY
★PREHEAT TIME
★SECURITY DELAY
★AC SYSTEM
★CURRENT RATIO
★LOW FREQUENCY
★HIGH FREQUENCY
★UNDER VOLTAGE
★OVER VOLTAGE
★OVER CURRENT 1
★OVER CURRENT 2
★FAULT DELAY OF UNDER FREQUENCY
★FAULT DELAY OF OVER FREQUENCY
★FAULT DELAY OF UNDER VOLTAGE
★FAULT DELAY OF OVER VOLTAGE
★FAULT DELAY OF OVER CURRENT 1
★FAULT DELAY OF OVER CURRENT 2
★FAULT DELAY OF OVER CURRENT 3
★FAULT DELAY OF OVER CURRENT 4
★UNDER VOLTAGE OF BATTERY
★OVER VOLTAGE OF BATTERY
★COMMUNICATION ADDRESS
★MAINTENANCE TIME FOR FUEL FILTER
★MAINTENANCE TIME FOR AIR FILTER
★MAINTENANCE TIME FOR OIL FILTER
★REMOTE CONFIGURATION

KP310V1.0 Controller Operation Manual
- 10 -
★DELAY OF REMOTE START
★DELAY OF REMOTE STOP
★NUMBER OF REMOTE START
★INPUT 1 TYPE
★INPUT 1 FAULT DELAY
★INPUT 2 TYPE
★INPUT 2 FAULT DELAY
★CONFIGURATION INPUT 1
★CONFIGURATION INPUT 2
★START IDLE DELAY
★STOP IDLE DELAY
★PASSWORD
For example:
When genset is stopped, and is in “Manual” Mode, press and for 5 seconds at the
same time, it displays password test mode
.
After inputting the right password, press to enter the “Parameters Set” menu. Take the
settings of flywheel tooth for example, after enter the flywheel tooth menu, press to set the
number, the default value is 100. While the value twinkles, press or to increase or
decrease the value. After inputting the value, press to confirm and save the value. Press
to get back to “Parameters Set” menu.
5.3 Manual Operation
When the KP310V1.0 controller is working, it is initialized to “Manual” Mode, with
indicator lighting. Press or turn the ignition lock to start genset.
Start steps:
Preheat relay output, meanwhile the preheating timer start counting down. If the preheating time is
set as zero, the preheat relay won’t output.
After preheating, the preheating relay stop working, the fuel relay and starting relay begin to
output. The maximum starting timer begins to count down. If genset can start successfully during
the countdown, the starting relay stops outputting. If failed, the fuel relay and starting relay stop

KP310V1.0 Controller Operation Manual
- 11 -
outputting.
After starting genset, the security delay countdown timer works. During the security delay range,
low oil voltage, high temperature, under speed, under voltage, under frequency and battery
charging fault are allowed. When the configuring output is set as “4-Genset Idle”, and starting idle
time isn’t 0, the related configuring output relay outputs, the start idle timer counting down, and
generator is in idle mode.
After the starting idle status, the configuring output relay stop working and genset start to work in
rated status.
Press to stop genset.
5.4 Remote Operation
When the KP310V1.0 controller is working, it is initialized to the “Manual” Mode. Press
to login into the remote mode.
Start steps:
Preheat relay output, meanwhile the preheating timer start counting down. If the preheating time is
set as zero, the relay won’t output.
After preheating, the preheating relay stop working, the fuel relay and starting relay begin to
output. The maximum starting timer begins to count down. If genset can start successfully during
the countdown, the starting relay stops outputting. If failed, the fuel relay and starting relay stop
outputting.
After starting genset, the security delay countdown timer works. During the security delay range,
low oil voltage, high temperature, under speed, under voltage, under frequency and battery
charging fault are allowed. When the configuring output is set as “4-Generator Idle”, and starting
idle time isn’t 0, the related configuring output relay outputs, the idle time start counting down,
and generator is in idle mode.
Press remote stop key to stop genset.
6. Protection
KP310V1.0 controller has a lot of protection functions. When genset has some problems, relevant
fault LED alarms. The fault alarm includes three types: warning, delay shutdown, immediately
shutdown.

KP310V1.0 Controller Operation Manual
- 12 -
6.1 Alarm
In the following alarms, relevant LED twinkles, but genset keeps running.
No. Type Description
1 Oil filter overtime
When oil filter is overtime than the maintenance value, there will
be an oil filter overtime alarm, maintenance LED twinkles.
2 Fuel filter overtime
When fuel filter is overtime than the maintenance value, there
will be a fuel filter overtime alarm, maintenance LED
twinkles.
3 Air filter overtime
When air filter is overtime than the maintenance value, there will
be a air filter overtime alarm, maintenance LED twinkles.
4 Over battery
voltage
When the battery voltage is larger than the set value, battery
LED twinkles.
5 Under battery
voltage
When the battery voltage is lower than the set value, battery
LED twinkles.
6 Charging faults
When the charging voltage is lower than the set value, battery
LED twinkles.
6.2 Time delayed stop alarms
After detecting the time delayed stop alarms, relevant LED twinkles, and genset will be stopped
after a delayed time.
No. Type Description
1 Over Current 1
If genset current is larger than Over Current 1, over current LED
twinkles, genset will be stopped after a delayed time.
Customers can set values to disable the protection.
2 Over Current 2
If genset current is larger than Over Current 2, over current LED
twinkles, genset will be stopped after a delayed time.
Customers can set values to disable the protection.
Note: if output configuration is set as “8-Time delayed stop alarms”, breaker will be open in
event of over current fault, and genset will be stopped after a delayed time.

KP310V1.0 Controller Operation Manual
- 13 -
6.3 Emergency stop alarms
After detecting the emergency stop alarms, relevant LED twinkles, and genset will be stopped
instantly. Buzzer will give alarms.
No. Type Description
1 Over
Frequency
If genset frequency is larger than the set value, over frequency LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
2 Under
Frequency
If genset frequency is lower than the set value, under frequency LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
3 Over
Voltage
If genset voltage is larger than the set value, over voltage LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
4 Under
Voltage
If genset voltage is lower than the set value, under voltage LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
5 Over
Frequency
If genset frequency is larger than the set value, over frequency LED
twinkles, genset will be stopped instantly.
6 Under
Frequency
If genset frequency is lower than the set value, under frequency LED
twinkles, genset will be stopped instantly.
7 Low Oil
Pressure
If oil pressure is lower than the set value, low oil pressure LED
twinkles, genset will be stopped instantly.
8 High Water
Temperature
If water temperature is higher than the set value, high water temperature
LED twinkles, genset will be stopped instantly.
9 Start failure If genset failed to start in the set time, start failure LED twinkles,
genset will be stopped instantly.
10 Emergency
Stop
While press the emergency stop button, emergency stop LED
twinkles, genset will be stopped instantly.
Note:
1、“Over frequency” protection can be disabled if “over frequency alarm delay time” is set as 0.
2、“Under frequency” protection can be disabled if “under frequency alarm delay time” is set as 0.

KP310V1.0 Controller Operation Manual
- 14 -
7. Wiring
The back panel of KP310V1.0 controller is as follows:
31 30 29 28 27 26 25 23 22 21 20 1924
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
12345678910 11 12 13 14 15 16 17 18
1921 2022232425262728293031
KP310V1.0 GENSET CONTROLLER
ABCN
Genset Voltage
IA IB ICICOM
Current
(Rated 5mA)
DIR
TXD
RXD
Comm_GND
Comm_VCC
B-
B+
EM Stop
+
Fuel
High Temp
Oil Press
Aux_In1
Aux_In2
Remote
120/240 Select
Crank
Start sw
Bat Charge
Preheat
Aux_Out1
Aux_Out2
+
-
MPU
Description of wiring terminals:
No. Function Diameter Note
1 DC Working power input:B- 1.0mm2Connect with the battery cathode
2 DC Working power input:B+ 1.0mm2Connect with the battery anode
3 Emergency stop input 1.0mm2Connect with B+ with emergency stop button
4 Fuel relay output 1.0mm2Rated current:15A, provide B+ by port 3
5 Start relay output 1.0mm2Rated current:15A, provide B+ by port 3
6 Dual voltage selection input 1.0mm2Active if lower voltage circuit is closed
7 Ignition lock start input 1.0mm2Connect to the ignition lock start terminal
8 Remote control input 1.0mm2Remote input terminal, low voltage active
9 Revolution sensor input + 1.0mm2
10 Revolution sensor input - 1.0mm2
Recommend to connect the revolution sensor
with shielding wire
11 Water temperature switch
input 1.0mm2Connect with water temperature sensor
12 Oil pressure switch input 1.0mm2Connect with oil pressure sensor 连接机油压
力传感器
13 Programmable configuration
input 1 1.0mm2Provide B+ by port 2
14 Programmable configuration
input 2 1.0mm2Provide B+ by port 2
15 Charging voltage detect 1.0mm2Connect with generator D+ terminal
16 Preheat relay output 1.0mm2Normal open output, rated current:1A, provide
B+ by port 2
17 Programmable relay output 1 1.0mm2Normal open output, rated current:1A

KP310V1.0 Controller Operation Manual
- 15 -
18 Programmable relay output 2 1.0mm2Normal open output, rated current:1A
19 Communication port-DIR 1.0mm2
20 Communication port-TXD 1.0mm2
21 Communication port-RXD 1.0mm2
22 Communication port-GND 1.0mm2
23 Communication port-VCC 1.0mm2
Genset can communicate with PC through
RS232 communication adapter.
Genset can communicate with remote
controller through RS485 communication
adapter
24 Current transformer C phase
detecting input 1.0mm2Connect with CT secondary wiring(Rated
current: 5mA)
25 Current transformer B phase
detecting input 1.0mm2Connect with CT secondary wiring(Rated
current: 5mA)
26 Current transformer A phase
detecting input 1.0mm2Connect with CT secondary wiring(Rated
current: 5mA)
27 Current transformer common
terminal 1.0mm2Refer to the description on the back of
controller.
28 Generator N phase voltage
input 1.0mm2Connect with N wire
29 Generator C phase voltage
input 1.0mm2Connect with the C wire(4A fuse)
30 Generator B phase voltage
input 1.0mm2Connect with the B wire(4A fuse)
31 Generator A phase voltage
input 1.0mm2Connect with the A wire(4A fuse)
8. Parameter Set
After login into the Parameter Set menu, remote mode lighter twinkles, parameters will be
displayed on the controller.
Press to return to “System Operation” menu.
Press or to select parameters.
Press to set parameters
Press to return to “System Operation” menu.
Press and to plus or minus values.
Press or for long time to plus or minus values automatically.
Press to save the data, and exit the parameters set.

KP310V1.0 Controller Operation Manual
- 16 -
If there is no operation for more than 60s, system will automatically exit Parameter Set menu, and
enter the System Operation menu.
8.1 Parameters Set list
VA
RModel KP310V1.0
V
O
RUN
VA
RModel KP310V1.0
V
O
RUN
No. Parameters Code Range Accuracy Defaults Description
Engine
1 Flywheel Gears ○○○○○● 1-500 1 100
2 Tripping speed ○○○○●○ 0-3000 1rpm 600 Engine RPM when starter is
tripping
3 Tripping
frequency
○○○○●● 0-600 0.1Hz 200 Genset Frequency when starter is
tripping
4 Tripping
charging voltage
○○○●○○ 0-400 0.1V 50 Charging alternator voltage when
starter is tripping
5 Starting timer ○○○●○● 1-100 0.1s 5 Genset start timer
6 Tripping oil
pressure delay
○○○●●○ 1-100 0.1s 5 Oil pressure when starter is tripper
7 Maximum
starting time
○○○●●● 1-100 0.1s 30 Average starter working Time
8 Under RPM ○○●○○○ 0-6000 1rpm 0 Engine under speed
9 Over RPM ○○●○○● 0-6000 1rpm 1600 Engine over speed
10 Under RPM
fault delay
○○●○●○ 0-65535 0.1s 0 Engine under speed delay
11 Over RPM fault
delay
○○●○●● 0-65535 0.1s 0 Engine over speed delay
12 Engine Stop To
Start Delay
○○●●○○ 10-65535 0.1s 30 Engine Stop to start delay timer
Parameter Code
Data

KP310V1.0 Controller Operation Manual
- 17 -
13 Preheat delay ○○●●○● 0-100 0.1s 50
Set Output 1 or Set Output 2 is
setted as “ Genset Preheat ”, it
works when genset starts,
controller start to count down..
14 Safety Delay ○○●●●○ 20-255 0.1s 60
Within the safety delay, under oil
pressure, high water temperature,
under speed 、under voltage 、
under frequency 、charging fault.
Generator
15 Phase Type
○○●●●● 0-4 1 0
0- 3-Phase 4-Line/3P4L
1- 3-Phase 3-Line/3P3L
2- 1-Phase 2-Line/1P2L
3- Double voltage
4- Double voltage select
16 Current Ratio ○●○○○○ 1-65535 1A/5mA 50 External CT ratio
17 Under
Frequency
○●○○○● 0-800 0.1Hz 450
18 Over Frequency ○●○○●○ 0-800 0.1Hz 550
19 Under Voltage ○●○○●● 0-5000 0.1V 2050
20 Over Voltage ○●○●○○ 0-5000 0.1V 2450
21 Over Current 1 ○●○●○● 0-65535 0.1A 450 Generator pre-overload
22 Over Current 2 ○●○●●○ 0-65535 0.1A 500 Generator overload
23
Under
Frequency Fault
Delay
○●○●●● 0-65535 0.1S 20
Generator output under frequency
Stop Delay
24 Over Frequency
Fault Delay
○●●○○○ 0-65535 0.1S 5 Generator output over frequency
Stop Delay
25 Under Voltage
Fault Delay
○●●○○● 0-65535 0.1S 20 Generator output voltage low Stop
Delay
26 Over Voltage
Fault Delay
○●●○●○ 0-65535 0.1S 5 Generator output voltage high
Stop Delay
27 Over Current 1
Fault Delay
○●●○●● 0-65535 0.1S 600 Genset pre-overload delay timing
28 Over Current 2
Fault Delay
○●●●○○ 0-65535 0.1S 50 Genset overload delay timing
29 Over Current 1
Stop Delay
○●●●○● 0-65535 0.1S 300 Genset pre-overload stop delay
timing
30 Over Current 2
Stop Delay
○●●●●○ 0-65535 0.1S 300 Genset overload stop delay timing
Battery
31 Under Voltage ○●●●●● 0-400 0.1V 100 Battery voltage under voltage
alarm
32 Over Voltage ●○○○○○ 0-400 0.1V 180 Battery voltage over voltage alarm

KP310V1.0 Controller Operation Manual
- 18 -
Communication
33 Communication
Address
●○○○○● 0-32 1 1 Communication address with the
PC
Maintenance
34
Fuel filter
maintenance
time
●○○○●○ 0-65535 0.1Hr 5000
Engine Fuel filter replace
countdown
35
Air filter
maintenance
time
●○○○●● 0-65535 0.1Hr 5000
Engine Air filter replace
countdown
36
Oil filter
maintenance
time
●○○●○○ 0-65535 0.1Hr 5000
Engine Oil filter replace
countdown
Programmable Input Set
37 Remote set ●○○●○● 0-5 1 4
0-Remote Start Normally Open
1-Remote Start Normally Closed
2-Remote Stop Normally Open
3-Remote Stop Normally Closed
4-Remote Start & Stop Normally
Open
5-Remote Start & Stop Normally
Closed
38 Remote start
delay
●○○●●○ 0-65535 0.1s 50 In remote mode, timing from give
start signal to successfully start.
39 Remote Stop
Delay
●○○●●● 0-65535 0.1s 50 In remote mode, timing from give
Stop signal to successfully stop.
40 Remote start
Times
●○●○○○ 1-10 1 3 In remote mode, start times in the
normal range
41 Input 1 Type ●○●○○● 0-3 1 0
0-Warning Normally Open
1-Warning Normally Closed
2-Stop Normally Open
3-Stop Normally Closed
42 Input 1 Fault
Delay
●○●○●○ 0-65535 0.1s 0 Set input 1 Fault Delay timing
43 Input 2Type ●○●○●● 0-3 1s 0
0-Warning Normally Open
1-Warning Normally Closed
2-Stop Normally Open
3-Stop Normally Closed
44 Input 2 Fault
Delay
●○●●○○ 0-65535 0.1s 0 Set input 2 Fault Delay timing
Programmable Output Set
45 Set Output 1 ●○●●○● 0-16 1 0
0-Reserved
1-Genset Stop
2-Genset Preheat
Table of contents
Popular Controllers manuals by other brands

Adaptive
Adaptive JUNIOR user guide

iNels
iNels SOPHY2 instruction manual

Enertronica Santerno
Enertronica Santerno ASAC-1 Series manual

Excelitas Technologies
Excelitas Technologies OmniCure SC Series Installation reference guide

Carlisle
Carlisle Binks 84-409 Service manual

Brooks
Brooks 4800 Series Supplemental manual

Nexmosphere
Nexmosphere XPERIENCE XN-125 quick start guide

DynaGen
DynaGen RA400 Installation and user manual

Regin
Regin RDAS18S-24C Mounting instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

Neousys Technology
Neousys Technology POC-700 Series user manual

Savant
Savant SmartControl 12 Quick reference guide