І. Application
The distribution bus is intended for use in collector boxes for controlling heating
systems, by facilitating the connection of electric actuators and similar control devices
such as room thermostats of different types, controllers, etc.
It is particularly suitable for controlling underfloor heating circuits.
II. Way of working
It is possible to control up to 9 heating circuits to the distribution bus, and two valve
actuators can be connected to each circuit.
Also, the distribution bus has the possibility to control the circulation pump as well as
the heating boiler.
The separate circuits are controlled by switching on the input devices /room regulators,
etc./, when a contact of a room thermostat is closed, voltage 230V/AC is supplied to the
corresponding actuator, which opens the valve of the corresponding heating circuit.
In the absence of a signal from all inputs, i.e. all thermostats are turned off, the
circulation pump is turned off and a signal is given to stop the boiler from Module 1.
In the case of a switch-on signal, even on only one input, the circulation pump is switched
on after 3 minutes and at the same time a signal is given to switch on the boiler.
Module 1 has an input from an independent contact from an external thermostat to
protect the floor circuit, when the contact is opened the circulation pump is immediately
switched off. If it is not used, a bridge should be made at this entrance.
The distribution bus consists of two Modules, Module 1 and Module 2, each module
can work independently or together.
Module1 has 3 inputs and 3 outputs for controlling 3 heating circuits, there are outputs
for controlling the circulation pump and the boiler, as well as a supply voltage output for
powering Module 2.
Module 2 has the ability to control up to 6 heating circuits, it can also work
independently without Module 1.
ІІI. Technical Specifications:
1. Supply voltage 230V/50Hz
2. Inputs for control devices 9
3. Outputs for use of actuators for valves 9 /230V/50Hz/
4. Outlet for circulation pump 230V/50Hz
5. Boiler control output independent contact NO/NC
6. Availability of outputs status indications.
7. Ambient temperature 5 to 40C
8. Relative humidity of environment up to 80%
9. Degree of protection IP-20