Klingenburg CERTO Operating and installation instructions

Description of CERTO controller
Standard ENERGY RECOVERY
1. Functions of the controller
2. Terminal connection
3. Menu structure overview
4. Menu structure
5. Menu navigation
6. Manual mode / external control / humidity control
7. Factory-set default settings on the controller
8. Fault and error messages
9. Operating messages
10. Safety and warning notices
Page 2
Page 4
Page 6
Page 8
Page 9
Page 11
Page 13
Page 22
Page 26
Page 23

2
1. Functions of the controller
The following control units are available depending on
the pumping capacity:
CERTO FU 750 =750 Watt
CERTO FU 1500=1500 Watt
Special features:
the control units can be used worldwide
we have followed all the guidelines available to us in
the design of the control unit
it is therefore the most up-to-date generation of con-
trol units
the control unit is operated via only three keys. Re-
sults and queries are displayed on the illuminated
single-line display
Once the mains power has been switched on, the
control unit is ready for immediate operation if it is
connected
Faults are shown on the display

3
most modern processor technology
CE approved
housing IP 54
short-circuit-proof output
EN 55011 tested
EN 61000-3 tested
EN 61000-4-2 tested
EN 61000-4-3 (burst) tested
EN 61000-4-4 (surge) tested
EN 61800-3 tested
each individual module is tested
detailed error messages
thermal contact monitoring includ-
ing function display
Status message
Service indicator
Start-up and run-out circuit
Menu-guided programming
Plain text display via LCD display
Three-button operation
Third party control signal processing
Humidity sensor input
Hygiene circuit
Operating hours counter
Optional accessories:
Control range extension
Humidity sensor
Menu language extension

Maximum relay
load 250 V AC 1A
Control signal
0-10 V
4-20 mA
302928272625242322212019
Overpressure
message
Status
message
Follow-up
drying run
18
1715 161413S3S2S1NL1
Fault
message
S1 and S3
closed during
operation.S2
and S3 closed
in case of
malfunction or
power failure
Maintenance
message
34 35 36 37 38 39 40 41 42 43 44 45
4th level3rd level2nd level
Solenoid
valve
supply
PE WPE VUPEPENL1´NL1´NL1
7
1 2 3 4 5 6
8 9 10 11 12
Input 230 V
50 Hz 16 A max.
{
Regler
4
2. Terminal connection
Wiring of pump station - control unit
Wiring of pump station - control unit

Terminal connections
Pump station:
13: Low pressure switch D1 (+)
14: Low pressure switch D1 (-)
15: High pressure switch D2 (+)
16: High pressure switch D2 (-)
17: Thermal contact motor (+)
18: Thermal contact motor (-)
333231
Follow-up
drying run
Water
processing
46 47 48
Solenoid
valve
purge
PE U V W PE PE MZ 13 14 15 16
MZ
*
1
2
4
17 18 PE
∆P
2
∆P
1
D1
4
1
D2
M3~
X2
MZ * Solenoid supplypurge MR ** Solenoid valve purge
NN PE PE
MZ
**
1
2
4
N
MR
Motor
min 4 x 1,5
Pumpenstation 5
Terminal connections
Control unit:
5: Water treatment (+)
6: Water treatment (-)
7: +10 V
8: Controller signal input (+)
9: Controller signal earth (-)
10: Earth
11: Controller enable (+)
12: Controller enable (-)
13: Low pressure switch D1 (+)
14: Low pressure switch D1 (-)
15: High pressure switch D2 (+)
16: High pressure switch D2 (-)
17: Thermal contact motor (+)
18: Thermal contact motor (-)
Wiring of pump station - control unit

6
3. Menu structure overview
Select downSelect up
Start Stop
Enter|Return
Maintenance Setting the clock
Manual draining
Language German, French,
English, Dutch
Codeeinput
Manual Target
Value Start Point P-Value
Humidity target
value
I-Value
Operating
Mode
Manual
Mode Humidity
control
External
drive

7
Rinse interval
Drying
Step switch Store
Rinse duration
Drying time
Switch points
2nd, 3rd, 4th step
max. frequency
Autostart
Accelerate time
Decellerate time
Line pressure
Frequency
limit
min. frequency
Service-
hours Service Reset

V: KB5.00 DEFNL
Befeuchter
Autostart!!!
Achtung!!! R Istfreq.: xxHz
Motor Stop!
If the autostart function is enabled, the following
message appears:
If you access the menu during operation, the
following message appears:
8
4. Menu structure
The control unit has a double-line, multi-colour illuminated display and is operated via 5 keys.
Once the wiring is completed, the device version will appear on the display when the voltage is switched on:
Start Stop
Select downSelect up Enter|Return
Only for “on-site” operation - priority
The menu is accessed by pressing the keys simulta-
neously. (Control unit reset):
Navigation: The left ( ) key: selects the menu item above. The right ( ) key: selects the menu item
below. The middle ( ) key: input or acknowledgement. This takes you to the menu item settings that are set
with the selection keys and confirmed with the ( ) key. Once the settings are made, move to the next menu
item by pressing the Enter key ( ) again.
Attention: Error acknowledgement is also carried out via this key combination:

Service
Std Mi TT.MM.JJ
12 39 17.06.11
Manual draining
+: Start drainin
Sprache
Deutsch Francais
English Nederlands
9
5. Menu navigation
Pressing the three keys ( ) will take you to:
This sets the clock that controls the error log. Pressing , again will open the menu item “Manual draining”.
Prior to long downtimes, the pump station can be drained via “Manual draining”. Pressing the left selection key
() will open the solenoid valve underneath the water filter. Pressing the Enter key( ), will stop the process,
the following menu item appears:
Confirm the selection by pressing the Enter key ( ). Next appears:

Operating mode
Operating mode
External drive
Operating mode
Manual Operation
Operating mode
Moisture control
Code input:
00000
10
To access the main menu, the code 00111 must be entered. This code request protects against unauthorised
access. It is therefore advisable to keep these operating instructions in a safe place.
Main menu:
Confirming with ( ) takes you to the menu item “Operating mode” for selecting the control option.
Depending on the on-site conditions, you can choose between external control via a control signal, manual
operation and humidity control (with optional humidity sensor). The operating mode can be changed by pressing
the left ( ) and right selection key ( ).
After selecting the control option, the entry must be confirmed with the Enter key ( ).

Manual targ.valu
0-87Hz 20Hz
Limits Set value
Start point
0-40% 10%
11
Manual operation
If “Manual operation” has been selected, a manual target value between 3 Hz and the factory-set maximum
frequency can be specified. The manual target value is set by pressing the selection keys.
This value is confirmed by pressing the Enter key .
External control.
If “External control” has been selected, the following display appears:
The start point can be set from 0-40% and relates to the control signal. Example: If set at 10%, the control unit will
only react to a control signal of 1 Volt. As a result, interfering voltages, which can lead to inadvertent operation of the
control unit, are suppressed.
6. Manual operation / external control / humidity control

Desired humity
10-95% 60%
P-gain
0,2-5,0 001 ,0
Integrator time
0,1-150s 001 ,0
12
Humidity control
If “Humidity control” has been selected, the following display appears:
Here, the relative humidity the humidifier can achieve is set between 10 % and 95 %.
The PI-controller is activated duringhumidity control. This ensures that the set target value remains constant. The
Klingenburg humidity sensor is required for this purpose. The gain factor is set here.
Attention:
The value must not be set >1.0, since this could lead to strong sub-harmonics and harmonics.
This controls the reaction time of the control. The greater the time, the slower the control.

Minimal freq.
3-20Hz 10Hz
Maximal freq.
22-87Hz 60Hz
Frequenzbegrenz.
22-Fmax 50Hz
Autostartfunkt.
Autostart on
Acceler.time
1-30sec 15s
Deceler.time
1-30sec 10s
Water pressure
Störmeld. n. 30s
Wash interval
1-96h 48h
Wash.time
1-1800s 180s
Trocknungsfunkt
Drying on
Drying time
15-120min 30min
Step switch
Steps off
Step switch
Steps on
Service interval
1000 Std
13
7. Factory-set default settings on the control unit
All factory-set default settings are now displayed, and each setting must be confirmed by pressing ENTER. No
changes should be made.

Minimal freq.
3-20Hz 10Hz
Maximal freq.
22-87Hz 60Hz
Frequenzbegrenz.
22-Fmax 50Hz
14
Minimum frequency
The minimum frequency is factory set. The nozzle pressure should be set at a minimum of 5 bar in any humid-
ification situation. Changing this frequency means that humidification is not guaranteed but the humidifier is
operating all the same. Controllability is also compromised This setting value is calculated at the factory and
preset and checked during a trial run. Frequency range: 3-20 Hz. Changes can cause damage to the humidifier.
Maximum frequency
The maximum frequency is factory set. The humidifier is designed for a specific humidification capacity. To
achieve this value, the complete humidification system is synchronised. This setting value is calculated at the
factory and preset and checked during a trial run. Frequency range: 22-80 Hz. Changes can cause damage to
the humidifier.
Pressing the Enter key ( ) in the setting values of “Maximum frequency” will take you to the menu item Fre-
quency limit. If excessive humidity occurs or the water consumption is too high, the frequency can be adjusted
here. It is important to note that the maximum frequency remains unchanged.

Autostartfunkt.
Autostart on
Acceler.time
1-30sec 15s
15
Autostart function
The Start and Stop button under the display screen has priority. The “Autostart on” function puts the control unit
in Run mode, when menu navigation is completed and after a control unit reset, i.e. if approval is given and a
control signal is present, the control unit starts the humidifier up again.
If “Autostart off” is programmed, the control unit must be activated via the Start button ( Start ). This setting is
useful for maintenance or during longer downtimes.
Power-up time
The power-up time is factory set. This is the time required to reach the designed maximum speed. This is to
ensure that the components of the drive system are not put under unnecessary strain.
This value is preset at 15 seconds. Years of experience have shown that this can extend the service life. Adjust-
ment range: 1-30 s. Changes can cause damage to the humidifier.

Deceler.time
1-30sec 10s
Water pressure
Störmeld. n. 30s
16
Power-down time
The power-down time is factory set. In contrast to the power-up time, this is the time required for the motor to
get from maximum speed to zero. Again, the aim is to protect the mechanical components. This value is preset
at 10 seconds. Adjustment range: 1-30 s. Changes can cause damage to the humidifier.
Line pressure fault message
If several appliances are using the osmosis system and are running simultaneously, the line pressure can drop
below 1.6 bar. This causes the humidifier to stop or switch off. In this menu item, the tripping time of the line
pressure fault message can be extended (up to 30 minutes) or the fault message can even be switched off (Fault
message off). This means that the humidifier is on standby for longer or all the time, when the line pressure is
above 2 bar.

Wash.interval
1-96h 48h
Wash.time
1-1800s 180s
17
Rinse interval
To ensure hygienic operation of the humidifier, the control unit has an automatic rinsing cycle as standard. The
rinse interval is preset at the factory for 48 hours. The value is adjustable between 1 hour and 96 hours. This is
the period between two rinsing cycles. Rinsing is activated if the humidifier is enabled via terminals 11 and 12,
but no humidification is provided via the control signal or the humidity sensor. Changes lead to increased water
consumption and should only be made if bacterial growth due to stagnant water is found during the hygiene
inspection.
Purge duration
The time of the actual purge process is adjustable between 10 and 1800 seconds. The factory
default setting is 180 seconds. The nozzle assemblies are rinsed for half the set time. Afterwards the solenoid
valve under the filter opens and the filter is flushed.

Trocknungsfunkt
Drying on
Drying time
15-120min 30min
Step switch
Steps off
Step switch
Steps on
18
Drying run
The control unit is equipped with a delayed shut-off control for drying the humidifier. This function allows an
enforced shut-off delay of the ventilation system. During operation and after the pump has been switched off, the
floating output is switched on for the set time. Adjustment range: 15 - 120 min. or off.
Step switch
For large humidifiers that use a lot of water, it may be useful to switch the nozzle assemblies in groups. In
transitional periods when less humidification is required, this can be achieved with fewer nozzles and higher
pressure. Depending on the frequency, the nozzle assemblies can be switched on in succession via high pressure
solenoid valves.

Step switch
Steps on
2nd Stage on
0-87Hz 30Hz
2nd Stage off
0-87Hz 27Hz
ru.hours: 00xxxh
19
Up to 3 levels can be switched.
... etc. ...
Reset service message
This menu item is only available, if the “Service” message appears during operation and the recom-
mended oil change intervals have been exceeded. Once the oil change has been carried out, the mes-
sage can be reset by pressing the left selection key ( ) and confirming with the Enter key ( ),
thus initiating a new interval cycle. Proof that the oil change has been carried out must be provided.
Attention! Resetting the service message without an oil change will damage the pump and void the warranty.

Store data?
Stored!
Not stored!
Sollfrequ.: 60Hz
R Istfreq.: 60Hz
Sollfrequ.: 00Hz
S Istfreq.: 00Hz
20
Saving the settings
The changes made must now be saved. This is necessary in
order to start the control unit in the selected mode.
Pressing the Enter key ( ) saves the values.
If the changes should not be saved, the action can be can-
celled by pressing the selection keys ( ).
Messages displayed for different control options during operation
For external control:
The display (Control signal is present, release enabled) is shown in the event of external control.
„R“ for Run „S“ means stopped via Stop button ( Stop )
Press the Start key ( Start ) , to activate auto-
start.
Other manuals for CERTO
1
This manual suits for next models
2
Table of contents
Other Klingenburg Controllers manuals
Popular Controllers manuals by other brands

AUTLED
AUTLED LC-006-001 user manual

IBM
IBM Netfinity ServeRAID-3H Installation and user guide

Endress+Hauser
Endress+Hauser RMS621 operating manual

P.L.LIGHT SYSTEMS
P.L.LIGHT SYSTEMS P.L.LIGHT IQ user manual

Advantech
Advantech UNO-2182 user manual

Johnson Controls
Johnson Controls S321-IP Hardware installation