Specication and Installation Instructions
• Contactless feedback positioner
• Mounts easily on round and square shafts
• Manual clutch
• Maintenance-free
• Position indicator
• FT6 18/4 cable with strain release NP NEP617-2 (P/N:
BB Cable-02) (optional)
• ½” (16mm) BW BXCON-1 conduit connector (optional)
• FD5-B 5000 Ohms feedback potentiometer (optional)
• AC2-B adjustable auxiliary switch (optional)
• Fail safe by Enerdrive System
• Small dampers
• Unit ventilators
• 1/4 turn valves
• VAV box control
• Fan coils
Models
Features Applications
BT160 Actuator
BT160 Actuator: 50 in.lb. (5.6Nm) with fail safe
BT160 Actuator
Description BT160 Actuator
Torque 50 in.lb. [5.6 Nm] at rated voltage
Running Time (for 90° Rotation) 20 to 30 seconds torque dependent
Fail Safe (Enerdrive) Yes
Fail Safe Runtime (0° to 90°) 30 seconds
Capacitor Charge Time on / Power-up 60 seconds
Power Consumption 14.5VA peak, 5VA (during operation)
Overload Protection Electronic throughout, 0° to 90° rotation
Power Supply 110 to 130 Vac | 50/60Hz
Transformer Requirements None
Cable Optional 4-wire FT6 plenum cable (part#: BB Cable-02) (18AWG) with strain release (NP NEP617-2)
Electrical Connection Optional BX conduit connector (BW BXCON-1)
Impedance N/A
Control Signals On/Off or floating
Feedback Signals Optional add-on FD5-B 5000 ohms feedback potentiometer
Angle of Rotation 0° to 90°, mechanically adjustable (default: 90° stroke)
Direction of Rotation Reversible, CW: Clockwise, CCW: Counter Clockwise (default: CW)
Cycles 100,000 full cycles, 1,500,000 repositions
Noise Produced 45 dB(A)
Ingress Protection IP22 equivalent to Nema type 2
Operating Temperature 0°F to +122°F [-18°C to +50°C]
Storage Temperature -22°F to +122°F [-30°C to +50°C]
Relative Humidity 5 to 95% non-condensing
Weight 3 lb. [1.4kg]
Purpose and Action of Control Type 1 operating control, electric actuator
Construction of Control Independently mounted
Pollution Degree 2
Impulse Voltage 330V
Quality Management System ISO 9001:2015
Certication Complies to standards: UL 60730-1 & UL 60730-2-14, CSA E60730-1 & CSA E60730-2-14
Complies to Low Voltage Directive & Electromagnetic Compatibility Directive
Complies to Electrical Equipment (Safety) Regulations & Electromagnetic Compatibility Regulations
WARNING: Risk of mechanical failure. Do NOT press clutch when actuator is in operation.
BT160-231122