KMC Controls BAC-5051E User guide

KMCAFMS
BAC-5051E Router
Application Guide
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com

Table of Contents
Getting Started 3
Introduction 3
Prerequisites 3
Accessing the Router's AFMS Features 3
Setting Up an AFMS 4
Setting AFMS Parameters 5
Before Beginning 5
Setting the Parameters 5
Calibrating the AFMS's Sensors 7
Running AFMS Learning Mode 8
Before Starting Learning Mode 8
Checking Learn Ready Status 8
Interpreting Learn Ready Status 8
Manually Starting Learning Mode 9
Enabling Learning Mode to Auto Start 9
Alternative to Running Learning Mode 10
Controlling Airflow with an AFMS 11
About 11
Controlling Outside Air Flow 11
Controlling Mixed Air Temperature 11
Commanding a Damper Position 11
Enabling Pass Through 12
Monitoring with an AFMS 13
Accessing Monitoring 13
Monitoring Operation 13
Monitoring Faults 13
Accessing the Damper Characterization Table 15
Manually Entering Damper Characterization Data 15
Accessing the AFMS Table 15
Interpreting the AFMSTable 15
Calculating the damper characterization data 15
Verifying the Damper Characterization Data 16
Important Notices 17
Trademarks 17
Patents 17
Terms of Use 17
Copyright 17
Disclaimers 17
AFMS BAC-5051E Router Application Guide 2 AG230224A

Getting Started
Introduction
The BAC-5051E router can be used to configure, control, tune, and monitor the operation of a KMCConquest
Airflow Measurement System (AFMS). AFMS features are accessible through the Balancing web page and are
active only when a valid AFMS controller has been discovered.
Prerequisites
1. Install a KMCConquest AFMS (the controller and all system components).
Note: See the
Airflow Measurement System Installation Guide,
found on any AFMScontroller's
product page.
2. Select the application (on the AFMScontroller) needed for the equipment.
Caution: Select the application
before
configuring other settings. Changing applications after
configuration will restore most parameters to their defaults. See "Selecting an Application" in the
KMCConquest AFMS NetSensor Application Guide,
found on any AFMScontroller's
product page.
Note: Complete basic configuration using a Conquest NetSensor, KMC Connect software, TotalControl
software, and/or the KMC Converge module for Niagara WorkBench.
3. Set the AFMScontroller's communication parameters.
Note: See the above note on the basic configuration methods.
4. Configure the router and set up routing.
Note: See the
Application and Installation Guide for the BAC-5051E Router
for details.
Accessing the Router's AFMS Features
1. Use an Internet browser to log in.
2. From the Advanced group, select Balancing.
3. Enter a range of device instance values that include an AFMS controller.
4. Select Discover.
Note: Up to 50 devices will be added to the list.
5. Select an AFMS controller from the list of discovered units.
AFMS BAC-5051E Router Application Guide 3 AG230224A

Note: The background of the selected unit changes to yellow and four tabs for the AFMS are added to the
bottom of the page.
Setting Up an AFMS
To set up an AFMSusing the router, complete the following processes in this order:
1.
Setting AFMS Parameters
on page 5
2.
Calibrating the AFMS's Sensors
on page 7
3.
Running AFMS Learning Mode
on page 8
Note: In environmental conditions where you can't run Learning Mode, see
Manually Entering Damper
Characterization Data
on page 15.
AFMS BAC-5051E Router Application Guide 4 AG230224A

Setting AFMS Parameters
Before Beginning
Before setting a KMCConquest Airflow Measurement System's parameters in AFMS, ensure that the
Prerequisites
on page 3 have been met.
Caution: Select the appropriate application on the AFMScontroller
before
configuring other settings.
Changing applications after configuration will restore most parameters to their defaults. See "Selecting
an Application" in the
KMCConquest AFMS NetSensor Application Guide,
found on any
AFMScontroller's product page.
Setting the Parameters
1. Select the Configure tab.
2. For Supply Area, enter the measurement (in square feet) of the cross section where the supply airflow pickup
tubes were installed.
Note: For guidance about the location of the pickup tubes, see "Mounting the Supply Airflow Pickup Tubes"
in the
Airflow Measurement System Installation Guide
, found on any AFMScontroller's product
page.
3. Choose to either leave Enable Low Limit set to ON (the default), or to turn it OFF.
Warning: ON is recommended to prevent freezing of equipment. If not needed (due to your
equipment's particular nature), you might choose to turn it OFF.
4. Either leave Low Temp Limit set to the default (37°F), or adjust the value.
Note: If the mixed air temperature reaches the Low Temp Limit set here (and Enable Low Limit is set to
ON) the outside air damper will modulate toward closed to prevent freezing of the equipment.
5. For Stroke Time (Seconds), enter the time (in seconds) that it takes for the damper to go from 100% open to
100% closed.
6. For Damper Reverse Action:
oSelect NORMAL if the greater the output signal to the damper actuator is, the more the damper opens (if
10 volts = 100% open).
oSelect REVERSE if the greater the output signal to the damper actuator is, the more the damper closes (if
10 volts = 100% closed).
7. For Actuator Voltage, select the voltage range of the damper actuator (2 to 10 volts or 0 to 10 volts).
8. Select ON for Learn Damper Span.
AFMS BAC-5051E Router Application Guide 5 AG230224A

Calibrating the AFMS's Sensors
1. Select the Tune tab.
2. Under Offset for Supply Air Flow, enter the CFM offset (determined by a TABtechnician) for the supply air
pressure transducer.
3. Under Multiplier for Supply Air Flow, enter the multiplier (determined by a TABtechnician) for the supply air
pressure transducer.
4. Under Offset for Outside Air Temp,Return Air Temp, and Mixed Air Temp, enter the °F offsets (determined
by a TABtechnician) for the outside, return, and mixed air temperature sensors.
5. Select Save.
Note: For more information on the AFMS's sensors, see the
Airflow Measurement System Selection
Guide,
found on any AFMScontroller's product page.
Continue to
Running AFMS Learning Mode
on page 8.
AFMS BAC-5051E Router Application Guide 7 AG230224A

Running AFMS Learning Mode
Before Starting Learning Mode
For valid results, first ensure that:
lThe parameters are set correctly. (See
Setting AFMS Parameters
on page 5.)
lThe sensors are calibrated. (See
Calibrating the AFMS's Sensors
on page 7.)
lThe supply air fan is running at a normal, steady rate (without hunting or sporadic spikes).
lIf the unit has a heat recovery wheel, it is turned off.
lIf any heating or cooling sources are located upstream of the MATsensor, they are turned off.
lIf the unit has a bypass damper, it is set to 100% open.
Checking Learn Ready Status
1. Select the Learn tab.
2. Take note whether Learn Ready reports READY or NOTREADY.
Interpreting Learn Ready Status
If READY is reported, you may manually start Learning Mode. (Continue to
Manually Starting Learning Mode
on page 9.)
If NOTREADY is reported:
lCheck Sensor Fault. If FAULTis reported, fix any faults found.
Note: Go to Monitor to find more detailed information on faults. (See
Monitoring with an AFMS
on page
13.)
lEnsure that Learn Damper Span has completed.
Note: (Under Configure,) Learn Damper Span must currently be OFF, and Damper Span Learned must
report LEARNED.
lMixed Air Temp Low Limit Control may be ACTIVE. If that is the case, continue to
Enabling Learning
Mode to Auto Start
on page 9.
Note: Go to Monitor to find Mixed Air Temp Low Limit Control. Go to Configure to find Enable Low Limit
and Low Temp Limit. (See
Setting AFMS Parameters
on page 5 for important guidance on Low Limit.)
AFMS BAC-5051E Router Application Guide 8 AG230224A

lCheck Min Delta Temp. If the current ΔT (the absolute difference between the outside and return air
temperatures) is less than the minimum difference allowed, then continue to
Enabling Learning Mode to
Auto Start
on page 9.
Note: Go to Monitor to find Outside Air Temp and Return Air Temp. Calculate the absolute difference,
then compare to Min Delta Temp.
Manually Starting Learning Mode
If Learn Ready reports READY (see
Checking Learn Ready Status
on page 8), you may start Learning Mode
manually.
1. Leave Min Delta Temp set to the default, or adjust it if needed.
Note: If the ΔT becomes less than the Min Delta Temp, the AFMScontroller will abort Learning Mode. This
is to insure that the controller does not receive unusable learning samples. Setting the Min Delta Temp at
a 10°F or larger difference is recommended.
2. Leave Time Between Samples (Seconds) set to the default, or adjust it if needed.
Note: Most often, Time Between Samples (Seconds) can be left on the default (60 seconds). You might
increase the value if the damper Stroke Time (see
Setting AFMS Parameters
on page 5) is longer than
that of a typical unit, or if the damper actuator requires extra time to respond. You might decrease it if a
large ΔT is present and time at the site is limited. However, too little time between samples could result in
inaccurate measurements.
3. For Learning Mode, select ON.
4. Select Save.
5. Wait for Learning Mode to complete.
Note: To calculate the total time (in minutes) that Learning Mode should take to complete, multiply Time
Between Samples (Seconds) by 91, then divide by 60.
Note: Learn Timer shows the elapsed time since Learning Mode started.
Enabling Learning Mode to Auto Start
If LearnReady reports NOTREADY because of currently unfavorable temperatures (see
Interpreting Learn
Ready Status
on page 8) you may enable the AFMScontroller to automatically start Learning Mode when it
detects favorable temperatures at a later time.
1. Leave Min Delta Temp set to the default, or adjust it if needed.
AFMS BAC-5051E Router Application Guide 9 AG230224A

Note: If the ΔT becomes less than the Min Delta Temp, the AFMScontroller will abort Learning Mode. This
is to insure that the controller does not receive unusable learning samples. 10°F or more Min Delta Temp
is recommended.
2. Leave Auto Start Delta Temp set to the default, or adjust it if needed.
Note: When the ΔT reaches the Auto Start Delta Temp, Learning Mode will start. Learning Mode will
complete if the ΔT remains greater than the Min Delta Temp for the entire duration. An Auto Start Delta
Temp that is at least 10°F more than Min Delta Temp is recommended.
3. Leave Time Between Samples (Seconds) set to the default, or adjust it if needed.
Note: Most often, Time Between Samples (Seconds) can be left on the default (60 seconds). You might
increase the value if the damper Stroke Time (Seconds) (found under Configure > Damper) is longer than
that of a typical unit, or if the damper actuator requires extra time to respond.
4. For Auto Learn Enable, select ON.
5. Select Save.
Note: See the Date of Last Learn and the OAT When Learned once Learning Mode has run automatically.
Alternative to Running Learning Mode
While not ideal, the damper characterization data can be calculated and entered manually. This should only be done
if — in the allotted time for setting up the AFMS — the ΔT is unlikely to remain greater than the Min Delta Temp for
the duration of Learning Mode. See
Manually Entering Damper Characterization Data
on page 15 for
guidance.
AFMS BAC-5051E Router Application Guide 10 AG230224A

Controlling Airflow with an AFMS
About
After
Setting Up an AFMS
on page 4, you can control outside air flow, or control mixed air temperature. Also, for
setup or maintenance purposes, you can command a damper position.
Alternatively, you can pass through control of the damper actuator to an external controller, using the AFMSfor
measurement and monitoring only. (See
Monitoring with an AFMS
on page 13.)
Controlling Outside Air Flow
1. Select the Configure tab.
2. From the Control Mode dropdown menu, select OA FLOWCTRL.
3. Enter an Outside Air Flow Setpoint (as CFM).
4. Select Save.
Note: The outside air damper will modulate to maintain the Outside Air Flow Setpoint. If Enable Low Limit
is ON and the mixed air temperature reaches the Low Temp Limit, the damper will modulate toward
closed to prevent freezing of the equipment. If an occupancy sensor is used, this Control Mode will only be
active when the served space is occupied.
Controlling Mixed Air Temperature
1. From the tabs that appear, select Configure.
2. From the Control Mode dropdown menu, select MATCTRL.
3. Enter a Mixed Air Temp Setpoint.
4. Select Save.
Note: The outside air damper will modulate to maintain the Mixed Air Temp Setpoint. If Enable Low Limit
is ON and the mixed air temperature reaches the Low Temp Limit, the damper will modulate toward
closed to prevent freezing of the equipment. If an occupancy sensor is used, this Control Mode will only be
active when the served space is occupied.
Commanding a Damper Position
1. From the tabs that appear, select Configure.
2. From the Control Mode drop-down menu, select DMPR POSITIONCTRL.
3. Enter an Outside Air Damper Setpoint (0–100% open).
4. Select Save.
AFMS BAC-5051E Router Application Guide 11 AG230224A

Note: The AFMScontroller will command the damper to the Outside Air Damper Setpoint. If Enable Low
Limit is ON and the mixed air temperature reaches the Low Temp Limit, the damper will modulate toward
closed to prevent freezing of the equipment. If an occupancy sensor is used, this Control Mode will only be
active when the served space is occupied.
Enabling Pass Through
1. From the tabs that appear, select Configure.
2. From the Control Mode drop-down menu, select PASSTHROUGH.
3. Select Save.
Note: The external controller (if the AFMScontroller is wired to one) will be allowed to control the damper
actuator. (For wiring details, see the
Airflow Measurement System Installation Guide,
found on any
AFMScontroller's product page.) This Control Mode will only be active when Learn Damper Span and
Learning Mode (under the Learn tab) are OFF.
Warning: The Enable Low Limit and Low Temp Limit do
not
apply when in PASSTHROUGH.
Ensure the external controller has its own low limit and other safeties configured to prevent
equipment damage.
AFMS BAC-5051E Router Application Guide 12 AG230224A

Monitoring with an AFMS
Accessing Monitoring
Select the Monitor tab.
Monitoring Operation
Label Description
Outside Air Flow The AFMS controller's current outside air CFM calculation displays here.
AFMSStatus
NORMAL = No faults are detected.
LEARNMODE =Learning Mode is ON. (See
Running AFMS Learning Mode
on page 8.)
SPANMODE =Learn Damper Span is ON. (See
Setting AFMS Parameters
on page 5.)
SERVICE = One or more faults are detected. (See
Monitoring Faults
on page 13.)
Control Mode The saved Control Mode (OA FLOW CTRL,MAT CTRL,DMPR POSITION CTRL or
PASSTHROUGH) displays here. (See
Controlling Airflow with an AFMS
on page 11.)
Damper Position The damper's percentage open displays here.
Occupancy The default is OCCUPIED. If an occupancy sensor is used and the served space is vacant,
UNOCCUPIEDwill display.
Outside Air Temp The outside air temperature sensor's measurement displays here.
Return Air Temp The return air temperature sensor's measurement displays here.
Mixed Air Temp The mixed air temperature sensor's measurement displays here.
Monitoring Faults
Label Description
Outside Air Sensor Fault FAULT = The outside air temperature sensor is missing or shorted.
Return Air Sensor Fault FAULT = The return air temperature sensor is missing or shorted.
Mixed Air Sensor Fault FAULT = The mixed air temperature sensor is missing or shorted.
Sensor Fault FAULT = One or more of the three temperature sensors is missing or shorted.
Damper Control Fault
If the saved Control Mode is DMPR POSITION CTRL (see
Commanding a Damper
Position
on page 11), FAULT will display if the damper position is more than 15% off
from the Outside Air Damper Setpoint for longer than the Stroke Time (Seconds)
(found under Configure >Damper). This indicates that the damper is not moving
properly.
Outside Air Control Fault
If the saved Control Mode is OA FLOW CTRL (see
Controlling Outside Air Flow
on
page 11), FAULT will display if Outside Air Flow is more than 15% off from the Outside
Air Flow Setpoint for longer than the Stroke Time (Seconds) (found under Configure >
Damper). This indicates that the damper is not moving properly.
AFMS BAC-5051E Router Application Guide 13 AG230224A

Label Description
Mixed Air Flow Fault
If the saved Control Mode is MAT CTRL (see
Controlling Mixed Air Temperature
on
page 11), FAULT will display if Mixed Air Temp is more than 15°F off from the Mixed
Air Temp Setpoint for longer than the Stroke Time (Seconds) (found under Configure >
Damper). This indicates that the damper is not moving properly.
Outside Air Flow Fault
FAULT = The calculation of the airflow based on the damper characterization data (see
Accessing the Damper Characterization Table
on page 15) has differed from the
calculation using the current temperatures by more than the tolerance (20% difference
default) for longer than 10 minutes. Ensure that the equipment is in the same physical
condition as it was when Learning Mode was run. Learning Mode may need to be run
again and/or sensors re-calibrated.
Mixed Air Temp Low Limit
Control
ACTIVE = The damper is modulating toward closed to prevent freezing of the equipment
because the Mixed Air Temp is lower than the Low Temp Limit (found under Configure
>General).
INACTIVE = Either the Mixed Air Temp is higher than the Low Temp Limit, or Enable
Low Limit is set to OFF.
See the related low limit information in
Setting AFMS Parameters
on page 5.
AFMS BAC-5051E Router Application Guide 14 AG230224A

Accessing the Damper Characterization Table
Manually Entering Damper Characterization Data
While not ideal, the damper characterization data can be calculated and entered manually in the AFMSTable. This
should only be done if — in the allotted time for
Setting Up an AFMS
on page 4 — the ΔT is unlikely to be greater
than the Min Delta Temp for the duration of Learning Mode. In that case, for reliability, running Learning Mode at a
later available time is still recommended.
Accessing the AFMS Table
Select the Tune tab.
Interpreting the AFMSTable
Label Description
Flow Percentage (expressed as a decimal) of the supply airflow that is outside
airflow at the given outside air damper position
Diff Pressure
(pressure assist application only)
The pressure differential (in inches of water column) at the given outside air
damper position
See the KMCConquest AFMSdocumentation for pressure assist
information.
Outside Air Closed Outside air damper at closed position
Outside Air 5 Outside air damper at 0–5% open
Outside Air 10 Outside air damper at 5–10% open
Outside Air 15 Outside air damper at 10–15% open
Outside Air 20 Outside air damper at 10–20% open
Outside Air 30 Outside air damper at 20–30% open
Outside Air 40 Outside air damper at 30–40% open
Outside Air 50 Outside air damper at 40–50% open
Outside Air 60 Outside air damper at 50–60% open
Outside Air 70 Outside air damper at 60–70% open
Outside Air 80 Outside air damper at 70–80% open
Outside Air 90 Outside air damper at 80–90% open
Outside Air 100 Outside air damper at 90–100% open
Calculating the damper characterization data
Use the %OA equation found in ASHRAEStandard 111, section 7.6.3.3: "Flow Rate Approximation by Temperature
Ratio".
AFMS BAC-5051E Router Application Guide 15 AG230224A

Note: Find ASHRAE Standard 111 on this page of read-only versions of ASHRAE standards.
Note: See
Controlling Airflow with an AFMS
on page 11 for how to set the outside air damper to the required
positions for the measurements.
Note: See
Monitoring with an AFMS
on page 13 for where to find the sensor readings.
Continue to
Getting Started
on page 3.
Verifying the Damper Characterization Data
Should the damper characterization data require verification, measurements should only be made using NIST-
traceable instruments and the method described in ASHRAE Standard 111. (See the details in
Manually Entering
Damper Characterization Data
on page 15.)
AFMS BAC-5051E Router Application Guide 16 AG230224A

©2023 KMC Controls, Inc. Specifications and design subject to change without notice AG230224A
Important Notices
Trademarks
KMC Conquest™, KMC Controls®, and the KMC logo are registered trademarks of KMC Controls, Inc. All other
products or name brands mentioned are trademarks of their respective companies or organizations. All rights
reserved.
Patents
Pat. https://www.kmccontrols.com/patents/
Terms of Use
https://www.kmccontrols.com/terms/
Copyright
No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated
into any language in any form by any means without the written permission of KMC Controls, Inc.
Disclaimers
The material in this document is for information purposes only. The contents and the product it describes are
subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this
document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or
related to the use of this document.
Other manuals for BAC-5051E
2
Table of contents
Other KMC Controls Industrial Equipment manuals