TPE-1001 2 Installation Guide
© 2012 KMC Controls, Inc. 858-019-01E
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long term reliability
and performance. Careful installation will also
ensure long term reliability and performance.
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
Specifications
Supply Voltage 24 VAC (+20%, –15%), Class 2
Supply Power 0.5 VA
Input Signal 0–15 psi (0–103 kPa), 30 psi
max. (207 kPa), using 1/4" (6
mm) O.D. polyethylene tubing
Output Signal 0–5 VDC, 0–10 VDC, 0–20 mA
Output Accuracy +/– 3%
Material Beige ame-retardant plastic
Wire Size 14 to 22 AWG recommended
Receiver Load 500 ohms max. for 0–20 mA
1000 ohms min. for 0–5/0–10
VDC
Weight 2 oz. (57 grams)
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Input/Output Calibration
The input and output ranges are designed so that
a normal 3–15 psi pneumatic signal will generate
output signals of 1–5 VDC, 2–10 VDC, or 4–20 mA.
These ranges are detailed in the graph below.
NOTE: A 3–15 psi signal generates 1–5 VDC, 2–10
VDC, or 4–20 mA.